施工现场临时用电组织设计
一、编制依据
《低压配电设计规范》GB50054-95中国建筑工业出版社
《建筑工程施工现场供电安全规范》GB50194-93中国建筑工业出版社《通用用电设备配电设计规范》GB50055-93中国建筑工业出版社
《供配电系统设计规范》GB50052-95中国建筑工业出版社
《施工现场临时用电安全技术规范》JGJ46-2005中国建筑工业出版社《建筑施工安全检查标准》JGJ59-99
二、施工条件
三、设计内容和步骤
1、现场勘探及初步设计:
(1)本工程所在施工现场范围内施工前无各种埋地管线。
(2)现场采用380V低压供电,设一配电总箱,内有计量设备,采用TN-S系统供电。
(3)根据施工现场用电设备布置情况,总箱进线采用导线直接埋地敷设,干线采用穿硬塑料管敷设,用电器导线采用穿硬塑料管敷设。布置位置及线路走向参见临时配电系统图及现场平面图,采用三级配电,三级防护。
(4)按照《JGJ46-2005》规定制定施工组织设计,接地电阻R≤4Ω。
2、确定用电负荷:
(1)、塔式起重机
K
x
=0.3,Cosφ=0.6,tgφ=1.33
将J
c =40%统一换算到J
c1
=25%的额定容量
P
n
=48kW
P
e =n×(J
c
/J
c1
)1/2×P
n
=1×(0.4/0.25)1/2×48=60.72 kW
P
js =K
x
×P
e
=0.3×60.72=18.21kW
Q
js =P
js
×tgφ=18.21×1.33=24.29kvar
(2)、建筑施工外用电梯
K
x
=0.3,Cosφ=0.6,tgφ=1.33
P
js
=0.3×30=9kW
Q
js =P
js
×tgφ=9×1.33=12kvar
(3)、自落式混凝土搅拌机 K
x
=0.6,Cosφ=0.85,tgφ=0.62
P
js
=0.6×7.5=4.5kW
Q
js =P
js
×tgφ=4.5×0.62=2.79kvar
(4)、对焊机
K
x
=0.35,Cosφ=0.7,tgφ=1.02
将J
c =50%统一换算到J
c1
=100%的额定容量
P
n
=100kW
P
e =n×(J
c
/J
c1
)1/2×P
n
=1×(0.5/1)1/2×100=70.71 kW
P
js =K
x
×P
e
=0.35×70.71=24.75kW
Q
js =P
js
×tgφ=24.75×1.02=25.25kvar
(5)、钢筋调直机
K
x
=0.65,Cosφ=0.7,tgφ=1.02
P
js
=0.65×7.5=4.88kW
Q
js =P
js
×tgφ=4.88×1.02=4.97kvar
(6)、钢筋弯曲机
K
x
=0.65,Cosφ=0.7,tgφ=1.02
P
js
=0.65×3=1.95kW
Q
js =P
js
×tgφ=1.95×1.02=1.99kvar
(7)、钢筋切断机
K
x
=0.65,Cosφ=0.7,tgφ=1.02
P
js
=0.65×5.5=3.58kW
Q
js =P
js
×tgφ=3.58×1.02=3.65kvar
(8)、直滚滚丝机
K
x
=0.65,Cosφ=0.6,tgφ=1.33
P
js
=0.65×4=2.6kW
Q
js =P
js
×tgφ=2.6×1.33=3.47kvar
(9)、木工圆锯
K
x
=0.65,Cosφ=0.6,tgφ=1.33
P
js
=0.65×3=1.95kW
Q
js =P
js
×tgφ=1.95×1.33=2.6kvar
(10)、木工电刨
K
x
=0.65,Cosφ=0.6,tgφ=1.33
P
js
=0.65×0.7=0.45kW
Q
js =P
js
×tgφ=0.45×1.33=0.61kvar
(11)、真空吸水泵
K
x
=0.75,Cosφ=0.8,tgφ=0.75
P
js
=0.75×4=3kW
Q
js =P
js
×tgφ=3×0.75=2.25kvar
(12)、高扬程水泵
K
x
=0.75,Cosφ=0.8,tgφ=0.75
P
js
=0.75×20=15kW
Q
js =P
js
×tgφ=15×0.75=11.25kvar
(13)、插入式振动器
K
x
=0.3,Cosφ=0.7,tgφ=1.02
P
js
=0.3×2.2=0.66kW
Q
js =P
js
×tgφ=0.66×1.02=0.67kvar
(14)、平板式振动器
K
x
=0.3,Cosφ=0.7,tgφ=1.02
P
js
=0.3×1.1=0.33kW
Q
js =P
js
×tgφ=0.33×1.02=0.34kvar
(15)、交流电焊机
K
x
=0.5,Cosφ=0.4,tgφ=2.29
将J
c =50%统一换算到J
c1
=100%的额定容量
P
n =S
n
×Cosφ=9×0.4=3.6kW
P
e =n×(J
c
/J
c1
)1/2×P
n
=1×(0.5/1)1/2×3.6=2.55 kW
P
js =K
x
×P
e
=0.5×2.55=1.27kW
Q
js =P
js
×tgφ=1.27×2.29=2.92kvar
(16)、交流电焊机
K
x
=0.5,Cosφ=0.4,tgφ=2.29
将J
c =50%统一换算到J
c1
=100%的额定容量
P
n =S
n
×Cosφ=38.6×0.4=15.44kW
P
e =n×(J
c
/J
c1
)1/2×P
n
=1×(0.5/1)1/2×15.44=10.92 kW
P
js =K
x
×P
e
=0.5×10.92=5.46kW
Q
js =P
js
×tgφ=5.46×2.29=12.51kvar
(17)、高压汞灯
K
x
=0.6,Cosφ=0.7,tgφ=1.02
P
js
=0.6×6×1.1=3.96kW
Q
js =P
js
×tgφ=3.96×1.02=4.04kvar
(18)、碘钨灯
K
x
=0.3,Cosφ=0.7,tgφ=1.02
P
js
=0.3×5×1=1.5kW
Q
js =P
js
×tgφ=1.5×1.02=1.53kvar
(19)、白炽灯
K
x
=0.9,Cosφ=1,tgφ=0
P
js
=0.9×2×1=1.8kW
Q
js =P
js
×tgφ=1.8×0=0kvar
(20)、空调机
K
x
=0.9,Cosφ=0.9,tgφ=0.48
P
js
=0.9×9×1=8.1kW
Q js =P js ×tgφ=8.1×0.48=3.92kvar (21)、荧光灯
K x =0.75,Cosφ=0.85,tgφ=0.62 P js =0.75×1.5×1.2=1.35kW Q js =P js ×tgφ=1.35×0.62=0.84kvar (22)、碘钨灯
K x =0.3,Cosφ=0.7,tgφ=1.02 P js =0.3×6×1=1.8kW
Q js =P js ×tgφ=1.8×1.02=1.84kvar (23)、碘钨灯
K x =0.3,Cosφ=0.7,tgφ=1.02 P js =0.3×10×1=3kW
Q js =P js ×tgφ=3×1.02=3.06kvar (24)、白炽灯
K x =1,Cosφ=1,tgφ=0 P js =1×2.2×1=2.2kW Q js =P js ×tgφ=2.2×0=0kvar
(25)总的计算负荷计算,总箱同期系数取Kx=0.95 总的有功功率
P js =K x ×ΣP js =0.95×(18.21+9+4.5+24.75+4.88+1.95+3.58+2.6+1.95+0.45+3+15+0.66+0.33+1.27+5.46+3.96+1.5+1.8+8.1+1.35+1.8+3+2.2)=115.23kW
总的无功功率
Q js =K x ×ΣQ js =0.95×(24.29+12+2.79+25.25+4.97+1.99+3.65+3.47+2.6+0.61+2.25+11.25+0.67+0.34+2.92+12.51+4.04+1.53+0+3.92+0.84+1.84+3.06+0)=120.44kva r
总的视在功率
S
js =(P
js
2+Q
js
2)1/2=(115.232+120.442)1/2=166.68kVA
总的计算电流计算
I
js =S
js
/(1.732×U
e
)=166.68/(1.732×0.38)=253.25A
3、1号干线(1号总配电柜)线路上导线截面及分配箱、开关箱内电气设备选择:
在选择前应对照平面图和系统图先由用电设备至开关箱计算,再由开关箱至分配箱计算,选择导线及开关设备。分配箱至开关箱,开关箱至用电设备的导线敷设采用铜橡皮绝缘导线穿硬塑料管。
(1)、塔式起重机开关箱至塔式起重机导线截面及开关箱内电气设备选择(开关箱以下用电器启动后需要系数取1):
i)计算电流
Kx=1,Cosφ=0.6,tgφ=1.33
I
js =K
x
×P
e
/(1.732×U
e
×Cosφ)=1×60.72/(1.732×0.38×0.6)=153.75A
ii)选择导线
选择BX-3×70+2×35,穿硬塑料管时其安全载流量为175A。
iii)选择电气设备
选择开关箱内隔离开关为DZ10-250/3 ,其脱扣器整定电流值为Ir=200A,熔断器RT0-200其最大熔体电流为I
RD
=200A,可根据实际电流的2.5倍选择额定电流较小的熔丝,漏电保护器为DZ20L-160/3。
(2)、建筑施工外用电梯开关箱至建筑施工外用电梯导线截面及开关箱内电气设备选择(开关箱以下用电器启动后需要系数取1):
i)计算电流
Kx=1,Cosφ=0.6,tgφ=1.33
I
js =K
x
×P
e
/(1.732×U
e
×Cosφ)=1×30/(1.732×0.38×0.6)=75.97A
ii)选择导线
选择BX-3×25+2×16,穿硬塑料管时其安全载流量为90A。
iii)选择电气设备
选择开关箱内隔离开关为DZ15-100/3 ,其脱扣器整定电流值为Ir=80A,熔