IEEE及美国标准ANSIC37.2-1970

代号保护英文

2 计时器(延时起动或闭合) timer

12 过速控制装置over speed

13 同步速控制器synchronous speed

14 低速控制装置low speed

17 旁路或放电开关discharge switch

21 距离保护distance

21P 相间距离phase distance

21N 接地距离ground distance

23 温度控制装置temperature

24 过励磁保护Volts/Hertz

25 检同期装置synchronism-check

27 低电压继电器undervoltage

30 保护动作指示annunciator

32 功率方向元件directional power

33 位置开关switch position

37 低电流或低功率保护low current/power relay

40 失磁保护loss-of-field

41 灭磁开关field circuit breaker 43 重合器reclosure cutout switch

46 逆相序保护(负序过流) I22 t Neg-Seq Overcurrent

47 负序电压保护Neg-Seq voltage

49 热保护thermal

49M 电动机热保护induction motor thermal 49T 变压器热保护transformer motor thermal 50 电流速断保护instantaneous overcurrent

50P 过流保护phase overcurrent

50N 零序过流保护neutral overcurrent

50G 漏电流保护residual overcurrent

50BF 失灵保护Circuit Breaker Failure

51 反时限过流保护time overcurrent

52 交流断路器AC circuit breaker

52CC 合闸线圈circuit breaker closing coil 52TC 跳闸线圈circuit breaker trip coil 55 功率因数继电器power coefficient

57 短路或接地保护short circuit/earthing rela

y

59 过电压保护over voltage

60 电压或电流平衡保护unbalance current/voltage

62 延时继电器time delay

63 压力开关pressure switch

64 接地检测继电器grounding detection

64G 发电机100%定子接地保护100%stator ground

67 方向过流保护AC directional overcurrent

67N 接地方向过流ground directional overcurre

nt

67P 方向过流phase directional overcurren

t

67Q 负序方向过流Neg-Seq Dir.Overcurrent 68

闭锁blocking

振荡闭锁power swing blocking 70 可变电阻rheostat

72 直流断路器DC circuit breaker

74 告警alarm

76 直流过流DC overcurrent

78 失步保护loss synchronous

79 重合闸reclosing

81 频率保护frequency

82 直流重合闸继电器DC reclosing

85 载波信号或导引线信号carrier or pilot wire receive

r relay

86 保护闭锁lockout

87 差动保护differential

87G 发电机差动保护generator differential 87T 变压器差动保护transformer differential 87B 母线差动保护bus bar differential 87V 电压差动voltage differential 89 隔离刀闸line switch

91 方向性电压继电器Directional voltage relay

92 电压和功率方向继电器Directional voltage/power r

elay

94 跳闸trip

101 断路器控制接点circuit breaker control swit

ch

101C 断路器合闸close 101T 断路器跳闸trip

欢迎您的下载,

资料仅供参考!

致力为企业和个人提供合同协议,策划案计划书,学习资料等等

打造全网一站式需求

浅谈继电保护常见问题

浅谈继电保护常见问题 摘要:继电保护是是电网安全稳定运行的重要保证,也是电力系统中的一个非常重要组成部分。继电保护出现故障会给电力系统带来不利影响,因此,如果了解了继电保护过程中的一次常见问题,就能对这些问题的预防和解决制定好的对策,平常维护时多加注意,出现问题时也能快速地得到解决。本文主要介绍了继电保护的作用和特点,叙述了继电保护常见问题及其解决方法。 关键词:继电保护常见问题解决 1、引言 继电保护是指研究电力系统故障和危及安全运行的异常工况,以探讨其对策的反事故方法。随着电力系统的不断发展,电网结构更加复杂,分布范围更为广泛,可靠性要求也越来越高,所需的各种继电保护装置也越来越多,但是继电保护装置在运行过程中本身也可能出现各种各样的问题。如果了解了继电保护过程中的一次常见问题,就能对这些问题的预防和解决制定好的对策,平常维护时有针对性的加以重视,出现问题时也能快速地得到解决。既能节约成本,又能提高效率。从而来保证电力设施的安全、经济、可靠投入运行,确保电力系统正常运转,防止事故的发生。 2、继电保护的作用和特点 2.1 继电保护的作用 2.1.1 警告作用 当电力系统设备出现异常工况或者是发生轻微故障时,继电保护装置会出现一定的信号,也即向值班人员发出警告,以便他们能够尽快发现问题,从而及时找到故障或异常工况的问题根源,并采取相应措施进行解决。 2.1.2 保护作用 继电保护最基本的作用就是保护作用,这主要体现在继电保护装置对变压器、电动机、发电机、电力电缆、电力线路、断路器、母线、电力电容器、电抗器以及其他各种电气设备运行的保护。 2.1.3 切除作用 切除作用主要是指继电保护装置可以快速地切除故障,以减少短路电流对电气设备的损害。快速切除故障的时间是保护动作时间和断路器跳闸的时间的总和,因此,为了提高切除故障的速度,应采用和断路器相一致的快速保护装置。 总之,继电保护可以为电力系统的安全性提供保障,继电保护装置能在其提供保护的电力系统元件和设备在发生故障时使迅速准确地脱离电网;能够对处于不正常状态的设备进行提示,以便得到快速处理和恢复;能够监控电力系统的运行状况,从而实现自动化。 2.2 继电保护的特点 2.2.1 监控性好 继电保护操作性监控管理好,主要体现在它的一些核心部件几乎不受外部环境变化的影响,能够产生较好的使用功率,而且能够通过计算机信息系统进行有效的监控,从而提高了设备运行的效率,降低了运行成本。 2.2.2 正确率高 继电保护之所以重要,最主要的一个原因在于其具有正确率高的特点。特别是随着现代社会的发展,在自动化运行率逐渐提高的情况下,继电设备的记忆功

电力系统继电保护技术中英文对照外文翻译文献

中英文对照外文翻译文献 (文档含英文原文和中文翻译) 原文: Relay protection development present situation Abstract: Reviewed our country electrical power system relay protection technological development process, has outlined the microcomputer relay protection technology achievement, propose the future relay protection technological development tendency will be: Computerizes, networked, protects, the control, the survey, the data communication integration and the artificial intellectualization. Key word: relay protection, present situation development, future development 1 relay protection development present situation - 1 -

The electrical power system rapid development to the relay protection propose unceasingly the new request, the electronic technology, computer technology and the communication rapid development unceasingly has poured into the new vigor for the relay protection technology development, therefore, the relay protection technology is advantageous, has completed the development 4 historical stage in more than 40 years time. After the founding of the nation, our country relay protection discipline, the relay protection design, the relay manufacture industry and the relay protection technical team grows out of nothing, has passed through the path in about 10 years which advanced countries half century passes through. The 50's, our country engineers and technicians creatively absorption, the digestion, have grasped the overseas advanced relay protection equipment performance and the movement technology , completed to have the deep relay protection theory attainments and the rich movement experience relay protection technical team, and grew the instruction function to the national relay protection technical team's establishment. The relay factory introduction has digested at that time the overseas advanced relay manufacture technology, has established our country relay manufacturing industry. Thus our country has completed the relay protection research, the design, the manufacture, the movement and the teaching complete system in the 60's. This is a time which the mechanical and electrical relay protection prospers, was our countries relay protection technology development has laid the solid foundation. From the end of the 50's, the transistor relay protection was starting to study. In the 60's to the 80's,it is the times which the transistor relay protection vigorous development and widely used. Tianjin University and the Nanjing electric power automation plant cooperation research 500kV transistor direction high frequency protection the transistor high frequency block system which develops with the Nanjing electric power automation research institute is away from the protection, moves on the Gezhou Dam 500kV line , finished the 500kV line protection to depend upon completely from the overseas import time. - 2 -

继电保护国际通用符号含义

中国电网https://www.doczj.com/doc/153012843.html, 电气符号含义 如果是初次接触外方提供的图纸,你可能会被图纸上的各种元件编号搞得不知所云,其实这些编号是有标准的,无论是TOSHIBA 还是GE 设计的图纸,同样的一个元器件,其编号是不变的,如87就是代表差动继电器,51就是代表过流继电器。这些编号实际上是遵循IEEE Std C37.2-1996标准,这种编号系统已用于各种接线图、手册和说明书中。参照右边的表格,你可以很容易地查到每个编号所代表的元件和功能,让你轻松成为读图高手! 1--master element 主要元件,是指控制开关等元件。它直接地或间接地通过保护继电器、延时继电器等中间元件,使设备投入或撤出运行。 注:本编号通常用于手动操作的元件,若某一电气或机务元件无其它功能编号可表示则也可使用本编号。 2--time-delay starting or closing relay 延时起动或闭合继电器,其功能是在切换程序或保护继电器系统动作之前或之后的任一时刻提供所希望的延时量。功能号48,62,79及82定义的除外。 3--checking or interlocking relay 校验或联锁继电器,在装置中,反映其它元件的工作位置或一些预定条件的元件,可用来确定一个工作程序是否继续进行,或停止或对一些元件的工作位置和一些预定条件进行校验。 4--master contactor 主接触器是一种由元件1及其相当的元件、中间继电器、保护元件等控制的元件。其工作是接通或断开必要的控制回路,以便在规定条件下使设备投入运行,或在其它条件和异常条件下,使之退出运行。 5--stopping device 停机元件是一种控制元件,主要用来使一台设备停止运转和退出运行。这一元件可手动或自动操作,但在发生异常情况时,它能闭锁电气功能(见元件86功能) 6--starting circuit breaker 启动断路器,其主要功能是在启动电压下将一台机器接入电源。 7--rate-of-change relay 变化速率继电器。当被测量的变化速率超过门限值时动作。元件63定义的除外。 8--control power disconnecting device 操作电源切断元件是一种隔离元件,如刀开关、断路器、或插入式熔丝等。用于将控制母线或设备与操作电源接通或断开。(操作电源中包括供给小型电机、加热器等设备的辅助电源。) 9--reversing device 反向元件用于实现电机磁场的反向或完成其它任何反向功能。 10--unit sequence switch 单元顺序开关用于变换顺序,使各个单元从多元设备中投入或撤出工作。 11--multifunction device 多功能元件。可完成3个或以上比较重要的功能,而这些功能只能由多个功能元件组合完成。该元件所有能完成的功能应在图纸、元件功能定义清单或继电器整定单中说明。 注:如果元件仅具有2个功能,则以这两个功能的编号表示。 12--overspeed device

继电保护心得体会

继电保护心得体会 【篇一:对继电保护故障分析和处理的心得体会】 对继电保护故障分析和处理的心得体会 摘要:随着科技的发展各种类型的电气设施出现在人们日常生活和工 作中,这些电气设施对供电提出了质量和稳定性的要求,这就使如何保 证电网安全稳定成为电力工作的重要环节。在现代化电力事业的规划、经营和管理等各项活动中,继电保护是一项重要的工作,继电保护 是维护供电稳定、维持电网的正常工作、确保用电安全的重要举措。本文从电力工作的经验出发,对继电保护故障的分析和处理进行讨论, 希望对继电保护工作提供参考和借鉴。 关键词:继电保护故障分析和处理 科技的进步和经济的发展,各种类型的电气设施出现在人们日常生活 和工作中,新型电气设施对供电提出了质量和稳定性的要求,这就使如 何保证电网安全稳定成为电力工作的重要环节。在现代化电力事业 的发展规划、经营活动和监督管理等各项工作中,继电保护成为电力 工作的重中之重。 1、继电保护的概述 (1)继电保护的定义。继电保护是研究电力系统故障和危及安全运行 时应对和处理的办法和措施,探讨对电力系统故障和危及安全运行的 对策,通过自动化处理的办法,利用有触点的继电器来保护电力系统及 其元件的安全,使其免遭损害。 (2)继电保护的功能。当电力系统发生故障或异常工况时,继电保护可 以实现的最短时间和最小区域内,将故障设备和元器件断离和整个电 力系统;或及时发出警报信号由电力工作者人工消除异常工况,达到减 轻或避免电力设备和元器件的损坏对相邻地区供电质量的影响。(3) 继电保护的分类。首先,从功能和作用的角度进行划分,继电保护分为:

异常动作保护、短路故障保护。其次,从保护对象的角度进行划分,继 电保护分为:主设备保护、输电线保护等。其三,从动作原理的角度进 行划分,继电保护分为:过电压、过电流、远距离保护等。最后,从装置 结构的角度进行划分,继电保护分为:数字保护、模拟式保护、计算保护、信号保护等。 2、常见的继电保护故障分析 由于新型电力控制设备和继电保护信息系统的使用,目前电力网络继 电保护工作的整体管理水平有了显著的提升,不过,毕竟电网和电力设 施是一个复杂的、庞大的系统,由于主客观各方面的因素影响,在继电 保护工作中仍然存在较多的问题,在日常的电力工作中常见的继电保 护故障主要有如下几种类型: (1)继电保护的运行故障。继电保护的运行故障是电力系统中危害性 最大且最常见的一种故障形式,表现为:主变差动保护、开关拒合的误 动等。例如:在电路网络的长期运行中,局部温度过高有可能导致继电 保护装置失灵。继电保护的运行故障最为常见的是电压互感器的二 次电压回路故障,是电力网络运行和围护中的薄弱环节之一。(2)继电 保护的产源故障。继电保护的产源故障是保护装置本身出现的故障, 在继电保护装置的实际运行中,其元器件的质量高低于继电保护产源 故障出现频率呈反相关。在电网和用电器中,继电保护装置对于零部 件的精度差、材质等都有严格的要求,如果采用质量不合格的零部件 和元器件将会增加继电保护产源故障发生的可能性。(3)继电保护的 隐形故障。继电保护的隐形故障既是又是大规模停电事故和电力保 护系统运行故障出现的根本原因,也是引发电力火灾的主要因素,电力 企业继电保护工作人员必须引起高度的重视。 3、处理继电保护故障的措施 为了实现电力事业又好又快地发展,进一步提高电力行业的经济和社 会效益, 【篇二:电力系统继电保护和自动化专业实习总结范文】

继电保护测试仪说明书

微机继电保护测试仪 使 用 说 明 书

目录 目录 (1) 第一部分微机继电保护测试仪使用说明 (3) 第一章装置特点与技术参数 (4) 第二章装置硬件结构 (6) 第三章单机操作模块功能说明 (8) 第四章外接PC机操作说明 (21) 第二部分继保软件操作说明 (21) 第五章软件操作方法简介 (22) 第六章交流试验 (24) 第七章直流试验 (32) 第八章状态系列 (34) 第九章谐波叠加试验 (38) 第十章频率及高低周试验 (41) 第十一章功率方向及阻抗试验 (45) 第十二章同期试验 (49) 第十三章整组试验Ⅰ和Ⅱ (54) 第十四章距离和零序保护 (59) 第十五章线路保护 (64) 第十六章阻抗特性 (70) 第十七章差动保护 (73) 第十八章6-35KV微机线路保护综合测试 (80) 附录1:外接电脑串行通信口的设置 (85) 附录2:插接U盘等设备时设备驱动安装方法 (87) 附录3:各种继电器的试验方法 (87)

第一部分继保使用说明

第一章装置特点与技术参数 第一节主要特点 ◆标准的4相电压3相电流输出具有4相电压3相电流输出,可方便地进行各种组合输出进行各种 类型保护试验。每相电压可输出120V,电流三并可输出120A,第4相电压Ux为多功能电压项,可设为4种3U0或检同期电压,或任意某一电压值的情况输出。 ◆单机操作方便单机由方便灵活的旋转鼠标通过大屏幕液晶显示屏进行操作,全部中文显示。可 完成现场大多数试验检定工作,可对各种继电器及微机保护进行检定,并可模拟各种复杂的瞬时性、永久性、转换性故障进行整组试验。开机即可使用,操作方便快捷。 ◆双操作方式,联接电脑运行通过Windows平台上的全套中文操作软件,可进行各种大型复杂 及自动化程度更高的校验工作,可方便地测试及扫描各种保护定值,可实时存贮测试数据,显示矢量图,绘制故障波形,联机打印报表等。 ◆软件功能强大可完成各种自动化程度高的大型复杂校验工作,如三相差动试验、厂用电快切、 备自投试验、线路保护检同期重合闸等,能方便地测试及扫描各种保护定值,进行故障回放,实时存储测试数据,显示矢量图,联机打印报告等。 ◆开关量接点丰富7路接点输入和2对空接点输出。输入接点为空接点和0~250V电位接点兼容, 可智能自动识别。输入、输出接点可根据用户需要扩展。 ◆大屏幕LCD显示屏本机采用320×240点阵大屏幕高分辨率图形液晶显示屏,全部操作过程均在 显示屏上设定,操作界面和试验结果均汉化显示,显示直观清晰。 ◆自我保护采用合理设计的散热结构,并具有可靠完善的多种保护措施及电源软启动,和一定的 故障自诊断及闭锁功能。 ◆具有独立专用直流电源输出装置设有一路110V 及220V专用可调直流电源输出。 ◆性价比高属于跨专业联合设计产品,综合了多专业的先进科技成果。兼具大型测试仪的性能, 和小型测试仪的价位,具有很高的性能价格比。

继电保护发展现状外文翻译

Relay protection development present situation [ Abstract ] reviewed our country electrical power system relay protection technological development process, has outlined the microcomputer relay protection technology achievement, proposed the future relay protection technological development tendency will be: Computerizes, networked, protects, the control, the survey, the data communication integration and the artificial intellectualization. [ Key word ] relay protection present situation development,relay protections future development 1 relay protection development present situation The electrical power system rapid development to the relay protection proposed unceasingly the new request, the electronic technology, computer technology and the communication rapid development unceasingly has poured into the new vigor for the relay protection technology development, therefore, the relay protection technology is advantageous, has completed the development 4 historical stage in more than 40 years time. After the founding of the nation, our country relay protection discipline, the relay protection design, the relay manufacture industry and the relay protection technical team grows out of nothing, has passed through the path in about 10 years which advanced countries half century passes through. The 50's, our country engineers and technicians creatively absorption, the digestion, have grasped the overseas advanced relay protection equipment performance and the movement technology , completed to have the deep relay protection theory attainments and the rich movement experience relay protection technical team, and grew the instruction function to the national relay protection technical team's establishment. The acheng relay factory introduction has digested at that time the overseas advanced relay manufacture technology, has established our country relay manufacturing industry. Thus our country has completed the relay protection research, the design, the manufacture, the movement and the teaching complete system in the 60's. This is a time which the mechanical and electrical relay protection prospers, was our country relay protection technology development has laid the solid foundation. From the end of the 50's, the transistor relay protection was starting to study. In the

继电保护专业常用标准

继电保护专业标准和有关技术文件 一、继电保护专业常用国家标准有: 1)GB 6592-1986《电子测量仪器误差的一般规定》 2)GB/T 7261-2000《继电器及继电保护装置基本试验方法》 3)GB/T 9361-1988《计算站场接地安全要求》 4)GB/T 2887-2000《电子计算机场地通用规范》 5)GB/T 2423-1989《电工电子产品基本环境试验规程》 6)GB/T 14537-1993《量度继电器和保护装置的冲击和碰撞试验》 7)GB/T 15145-1994《微机线路保护装置通用技术条件》 8)GB /T 14598-1996《静态继电器及继电保护装置的电气干扰试验》 9)GB/T 16836-1997《量度继电器和保护装置安全设计的一般要求》 10)GB/T 11287-2000《电气继电器》 11)GB 14285-1993《继电保护和安全自动装置技术规程》 12)GB50171—92《电气装置安装工程盘、柜及二次回路结线施工及验收规范》 二、继电保护专业常用行业标准有: 1)DL 408-1991《电业安全工作规程》(发电厂和变电所电气部分) 2)DL 5009.1-2002《电力建设安全工作规程》(火力发电厂部分) 3)DL 755-2001《电力系统安全稳定导则》 4)DL-5000-2000《火力发电厂设计技术规程》 5)DL/T 5147-2001《电力系统安全自动装置设计技术规定》 6)DL400-1991《继电保护和安全自动装置技术规程》 7)DL/T 5149-2001《220kV-550kV变电所计算机监控系统设计技术规程》

【机械专业文献翻译】故障切除继电保护装置

翻译文献(英译中) 原文: Fault—clearing Protective Relays(1) Overcurrent relaying.Slow—speed relays.The most obvious effect of a fault is t o change the current in the faulted conductor from a normal value to an abnormall y large one.Therefore it is not surprising that the earliest methods of clearing fault s were based on the utilization of that effect(overcurrent).Early methods included f uses,circuit breakers with series trip coils,and slow—speed overcurrent relays. Slow—speed overcurrent relays are mostly of the induction type.To obtain selec tivity without unnecessarily long delay,such relays usually have a delay which vari es inversely with the current.Both time and current settings are adjustable.Since t he fault current decreases,on account of the increased impedance of the line betw een the fault and the source. as the fault is mo,ved farther from the source of power,it follows that the relay o perating time increases as the distance to the fault increases. The time—distance curves change with such conditions as connected generating capacity and the connection or disconnection of other transmission lines,and ther efore,to ensure selectivity,curves should be checked for several conditions to asc ertain that.under the worst condition,an adequate interval exists between the oper ating times of relays 1 and 3,and, similarly,between each pair of relays on adjoi ning line sections.Coordination may be accomplished by judicious choice of both ti me settings and current settings. If the relay current changes but little with fault location,the curve of relay time versus fault position becomes more like curve a than ike curve b.Such a condition

电气常用文字符号及二次接线图的识别

电气常用新旧文字符号对照表

附表一二次回路接线图中常见的文字符号 序号符号文字解释序号符号文字解释 1 DL 继路器及其辅助触点31 JSJ 加速继电器 2 WJ 温度继电器32 YZJ 电压中间继电器 3 G 隔离开关及其辅助触点33 ZXJ 指挥信号中间继电器 4 WSJ 瓦丝继电器34 WH 有功电度表 5 LH 电流互感器35 XKJ 选控继电器 6 ZCH 重合闸继电器36 VARH 无功电度表 7 YH 电压互感器37 XCJ 选测继电器 8 BCJ 保护继电器38 KK 控制开关 9 HQ 合闸线圈39 FJ 复归继电器 10 ZJ 中间继电器40 HK 转换开关 11 HC 合闸接触器41 ZZJ 重复中间继电器 12 HWJ 合闸位置继电器42 ZK 自动开关 13 TQ 跳闸线圈43 XZJ 信号中间继电器 14 TWJ 跳闸位置继电器44 CK 测量转换开关 15 LJ 电流继电器45 XJJ 信号监察继电器 16 HJ 合闸继电器46 XK 信号转换开关 17 YJ 电压继电器47 TBJ 跳跃闭锁继电器 18 TJ 跳闸继电器48 DK 刀开关 19 SJ 时间继电器49 YJJ 压力监视中间继电器 20 TJJ 同步检测继电器50 MK 灭磁开关 21 CJ 差动继电器51 A 电流表 22 XMJ 信号脉冲继电器(冲击继电器) 52 LK 联动开关 23 GJ 功率继电器53 V 电压表 24 JJ 监察继电器54 XWK 限位开关 25 XJ 信号继电器55 W 有功功率表 26 SXJ 事故信号中间继电器56 XD 信号灯 27 RJ 热继电器57 WAR 无功功率表 28 YXJ 预告信号中间继电器58 LD 绿色信号灯 29 BSJ 闭锁继电器59 STK 手动同期转换开关 30 HZ 频率表60 QA 起动按钮 续附表一 序号符号文字解释序号符号文字解释 61 HD 红色信号灯91 YM 电压互感器二次电压小母线 62 RD 熔断器92 L 电感 63 GD 光字牌93 ZM 转角变压器小母线 64 JRD 击穿保险94 D 二极管 65 WS 位置指示灯95 XDC 蓄电池

常见继电保护类型及原理

A、过电流保护---是按照躲过被保护设备或线路中可能出现的最大负荷电流来整定的。如大电机启动电流(短时)和穿越性短路电流之类的非故障性电流,以确保设备和线路的正常运行。为使上、下级过电流保护能获得选择性,在时限上设有一个相应的级差。 B、电流速断保护---是按照被保护设备或线路末端可能出现的最大短路电流或变压器二次侧发生三相短路电流而整定的。速断保护动作,理论上电流速断保护没有时限。即以零秒及以下时限动作来切断断路器的。 过电流保护和电流速断保护常配合使用,以作为设备或线路的主保护和相邻线路的备用保护。 C、定时限过电流保护---在正常运行中,被保护线路上流过最大负荷电流时,电流继电器不应动作,而本级线路上发生故障时,电流继电器应可靠动作;定时限过电流保护由电流继电器、时间继电器和信号继电器三元件组成(电流互感器二次侧的电流继电器测量电流大小→时间继电器设定动作时间→信号继电器发出动作信号);定时限过电流保护的动作时间与短路电流的大小无关,动作时间是恒定的。(人为设定) D、反时限过电流保护---继电保护的动作时间与短路电流的大小成反比,即短路电流越大,继电保护的动作时间越短,短路电流越小,继电保护的动作时间越长。在10KV系统中常用感应型过电流继电器。(GL-型) E、无时限电流速断---不能保护线路全长,它只能保护线路的一部分,系统运行方式的变化,将影响电流速断的保护范围,为了保证动作的选择性,其起动电流必须按最大运行方式(即通过本线路的电流为最大的运行方式)来整定,但这样对其它运行方式的保护范围就缩短了,规程要求最小保护范围不应小于线路全长的15%。另外,被保护线路的长短也影响速断保护的特性,当线路较长时,保护范围就较大,而且受系统运行方式的影响较小,反之,线路较短时,所受影响就较大,保护范围甚至会缩短为零。 ②、电压保护:(按照系统电压发生异常或故障时的变化而动作的继电保护) A、过电压保护---防止电压升高可能导致电气设备损坏而装设的。(雷击、高电位侵入、事故过电压、操作过电压等)10KV开闭所端头、变压器高压侧装设避雷器主要用来保护开关设备、变压器;变压器低压侧装设避雷器是用来防止雷电波由低压侧侵入而击穿变压器绝缘而设的。 B、欠电压保护---防止电压突然降低致使电气设备的正常运行受损而设的。 C、零序电压保护---为防止变压器一相绝缘破坏造成单相接地故障的继电保护。主要用于三相三线制中性点绝缘(不接地)的电力系统中。零序电流互感器的一

继电保护中英文对照要点

序号英文全称中文解释 1 A lagging power-factor 滞后的功率因数 2 A mutualky induced e.m.f 互感电动势 3 a retarding torque 制动转矩 4 Abnormal operating condition 不正常运行状态 5 Abnormal overload 异常过载 6 Abnormal overvoltage 事故过电压 7 Abnormal state 非常态 8 Above earth potential 对地电势 9 Abrupt signal analysis 突变信号分析 10 Absolute potential 绝对电势 11 AC circuit breaker 交流断路器 12 AC component 交流分量 13 AC directional over current relay 交流方向过流继电器 14 AC distribution system 交流配电系统 15 AC reclosing relay 交流重合闸继电器 16 Accelerating protection for switching onto fault 重合于故障线路加速保护动作 17 Acceleration Trend Relay(ATR) 加速趋势继电器 18 Accurate Working Current 精确工作电流 19 Accurate Working voltage 精确工作电压 20 Activate the breaker trip coil 起动断路器跳闸 21 Adaptive features 自适应特性 22 Adaptive relay protection 自适应继电保护 23 Adaptive relaying 自适应继电保护 24 Adaptive segregated directional current differential protection 自适应分相方向纵差保护 25 Admittance relays 导纳型继电保护装置 26 AI(artificial intelligence) 人工智能 27 Air brake switch 空气制动开关 28 Air breaker 空气断路器 29 Air-blast circuit breaker 空气灭弧断路器 30 Air-blast switch 空气吹弧开关 31 Air-space cable 空气绝缘电缆 32 Alarm 报警 33 Alarm relay 报警信号继电器 34 Alarm signal;alerting signal 报警信号 35 Alive 带电的 36 All-relay interlocking 全部继电连锁 37 All-relay selector 全继电式选择器 38 Amplitude Comparison 绝对值比较 39 Analogue 模拟 40 Angle of maximum sensitivity 最大灵敏角 41 Annunciator relay 信号继电器

继电保护知识点总结

电力系统中常见的故障类型和不正常运行状态 故障:短路(最常见也最危险);断线;两者同时发生 不正常:过负荷;功率缺额而引起的频率降低;发电机突然甩负荷而产生的过电压;振荡 继电保护在电力系统发生故障或不正常运行时的基本任务和作用。 迅速切除故障,减小停电时间和停电范围 指示不正常状态,并予以控制 继电保护的基本原理 利用电力系统正常运行与发生故障或不正常运行状态时,各种物理量的差别来判断故障或异常,并通过断路器将故障切除或者发出告警信号 继电保护装置的三个组成部分。 测量部分:给出“是”、“非”、“大于”等逻辑信号判断保护是否启动 逻辑部分:常用逻辑回路有“或”、“与”、“否”、“延时起动”等,确定断路器跳闸或发出信号 执行部分 保护的四性 选择性:保护装置动作时仅将故障元件从电力系统中切除,使停电范围尽量减少速动性:继电保护装置应尽可能快的断开故障元件。 灵敏性:继电保护装置应尽可能快的断开故障元件。故障的切除时间等于保护装置和断路器动作时间之和 可靠性:在保护装置规定的保护范围内发生了它应该反映的故障时,保护装置应可靠地动作(即不拒动,称信赖性)而在不属于该保护装置动作的其他情况下,则不应该动作(即不误动,称安全性)。 主保护、后备保护 保护:被保护元件发生故障故障,快速动作的保护装置 后备保护:在主保护系统失效时,起备用作用的保护装置。 远后备:后备保护与主保护处于不同变电站 近后备:主保护与后备保护在同一个变电站,但不共用同一个一次电路。 继电器的相关概念: 继电器是测量和起动元件 动作电流:使继电器动作的最小电流值 返回电流:使继电器返回原位的最大电流值 返回系数:返回值/动作值 过量继电器:返回系数Kre<1 欠量继电器:返回系数Kre>1 绩电特性:启动和返回都是明确的,不可能停留在某个中间位置 阶梯时限特性: 最大(小)运行方式: 在被保护线路末端发生短路时,系统等值阻抗最小(大),而通过保护装置的电流最大(小)的运行方式 三段式电流保护:由电流速断保护、限时电流速断保护及定时限过电流保护相配合构成的一整套保护 工作原理: 电流速断保护:当所在线路保护范围内发生短路时,反应电流增大而瞬时动作切

35kV电网继电保护设计说明书(精)

1 设计说明书 一、 d 5点短路电流计算 由于短路电流计算是进行电网继电保护配置设计的基础,加上时间的关系,指导老师只要求每个小组计算一个短路点。本小组计算第五个短路点。 (一三相短路电流计算: 最大运行方式:两电站的六台机组全部投入运行,中心变电所在地110 KV母线上的系统等值标么电抗为0.225。城关变电所总负荷为240A (35KV侧 ,由金河电站供给110KA、青岭电站供给130KA。剩余的110A经中心变电所送入系统。 根据题意转换出电抗标么值: 排除城关变电所,合并整理其它电抗值得:

整理合并得: X25=3.918 X26=1.833 整理合并得: X27=0.275 X28=0.175 合并、星-三角等值转换: X29=0.5 X30=7.583 X31=3.547 等值电抗转换: X32=0.712 X33=10.791 X34=5.047 计算得出的最大短路电流分别为:I S =7.731 I q =0.541 I j =1.115 第1页 (二两相短路电流计算:

最小运行方式:两电站都只有一台机组投入运行, 中心变电所110KV母线上的系统等值标么电抗为0.35城关变电所总负荷为105A(35KV侧 ,由金河电站供给40A、青岭电站供给65A。剩余的15A经中心变电所送入系统。 1、两相短路电流正序电抗化简: 最小运行方式下转换的电抗标么值: X1=0.35 X2=0.55 X3=0 X4=0.35 X5=0.55 X6=0 X9=0.292 X10=1 X12=5.33 X16=0.876 X19=0.75 X20= 4 合并青中线、金中线、中变电抗: X21=0.275 X22=0.175 X23=5.918 X24=6.33 整理、合并得: X25=0.625 X26=8.178 X27=8.751 整理、合并得: X28=0.825 X29=10.805 X30=11.562 2、两相短路电流负序电抗化简: 最小运行方式下转换的负序电抗标么值:

常用电气元件文字符号表

常用电气元件文字符号表

各种配电箱的符号 civilcn 高压开关柜AH 高压计量柜AM 高压配电柜AA 高压电容柜AJ 低压电力配电箱柜AP低压照明配电箱柜AL应急电力配电箱柜APE应急照明配电箱柜ALE低压负荷开关箱柜AF低压电容补偿柜ACC或ACP直流配电箱柜AD 操作信号箱柜AS控制屏台箱柜AC继电保护箱柜AR计量箱柜AW励磁箱柜AE 低压漏电断路器箱柜ARC 双电源自动切换箱柜AT 多种电源配电箱柜AM 刀开关箱柜AK 电源插座箱AX 建筑自动化控制器箱ABC 火灾报警控制器箱AFC 设备监控器箱ABC 住户配线箱ADD 信号放大器箱ATF 分配器箱AVP 接线端子箱AXT 这个定义很不错。 矿用铠装控制电缆; MKVV22,MKVV322*0.5,3*0.75,4*4,------37*1.5mm 铠装控制电缆;KVV22,KVV32,KVVR222*0.5,3*0.75,4*4, ----- 37*1.5mm 铠装屏蔽控 制电缆 KVVP-22,RVVP-22,KVVRP-22,KVVP2-22,KVVRP2-222*0.5,3*0.75,4* 4, ----- 37*1.5mm 铠装阻燃控制电 缆;ZR-KVV22,ZR-KVV32,ZR-KVVR222*0.5,3*0.75,4*4,——37*1.5 mm 铠装阻燃屏蔽控制电 缆;ZR-KVVP22,ZR-KVVRP22,ZR-KVVP2-22,ZR-KVVRP2-222*0.5,3*0. 75,4*4, ----- 37*1.5mm 铠装通信电 缆;HYA22,HYA23,HYA53,HYV22,HYV23 5 对,10 对——2400 对,0.4-0.5-0.6-0.7-0.8-0.9 线径铠装充油通信电 缆;HYAT22,HYAT23,NYAT53 5 对,10 对——800 对 0.4-0.5-0.6-0.7-0.8-0.9 线径铠装阻燃通信电 缆;ZR-HYA22,ZR-HYA23,ZR-HYA53,WDZ-HYA23,WDZ-HYA535 对,10 对 ---- 2400 对,0.4-0.5-0.6-0.7-0.8-0.9 线径矿用铠装阻燃通信电 缆;MHYA22,MHYV22,MHYA32,MHYV325 对,10 对——200 对,0.5-0.6-0.7-0.8-0.9-1.0 线径铠装计算机电缆; DJYVP22,ZR-DJYVP22,DJYVRP22,DJYPV22,ZR-DJYPV22DJYPVR22DJ