摘要

摘要

本次毕业设计的主要内容是对天津市某酒店进行中央空调系统设计。该建筑位于天津市,共5层,总制冷负荷约为900KW,室内采用风机盘管系统为主。本次设计涉及到空调系统的划分,冷热负荷的计算,空调设备的选型,风管的水力计算和布置,管道的消声,防震,冷冻机房的设计,水系统的划分,水管的水力计算及水管布置,水泵和通风机的选择,通风系统的自动控制等。

关键词:中央空调、通风设计、设备选择、水力计算、冷冻机房

Abstract

the main content of this graduation design is a four-star hotel in Tianjin for central air conditioning system design. The building is located in Tianjin, a total of 5 layers, total cooling load is 900KW, indoor fan coil system. This design involves the division of the air conditioning system, cooling and heat load calculation, the selection of air conditioning equipment, duct hydraulic calculation and arrangement of pipeline of noise elimination, shockproof, the design of the cooling room, the division of water system, the hydraulic calculation of pipe and pipe arrangement, the choice of the pump and fan, ventilation system, such as automatic control

目录

第1章工程概况 (1)

1.1室外气象参数 (1)

1.2室内设计参数 (1)

第2章负荷计算 (2)

2.1冷负荷理论根据 (3)

2.1.1房间冷负荷的构成: (3)

2.1.2.房间湿负荷的构成: (3)

2.1.3主要计算公式: (3)

2.2新风量的计算 (7)

2.2.1新风量标准的选取 (8)

2.2.2新风量的确定 (8)

2.2.3新风量计算结果与分析 (8)

第三章方案选择与计算 (9)

3.1空调系统方案选择 (9)

3.2空调冷热源选择 (10)

3.2.1 空调冷热源选择原则 (10)

3.2.2冷热源方案比较 (11)

3.2.3本工程选择计算 (12)

3.3新风系统的方案确定 (13)

3.4 空调水系统论证 (13)

3.4.1按调节特征分类 (13)

3.4.2按管路布置方式分类 (15)

第四章空调设备的选择与计算 (15)

4.1 风机盘管的计算与选择 (16)

4.1.1 风机盘管的选择计算 (16)

4.1.2 风机盘管选型 (17)

4.2 新风机组的选择 (18)

4.2.1 新风方案....................................................................... 错误!未定义书签。

4.2.2新风机组的选择计算 (18)

4.2.3 排风热回收的节能效益 (19)

4.2.4新风机组的布置 (20)

第五章气流组织 (21)

5.1空调房间的气流组织形式 (21)

5.2空调房间的送回风口形式 (22)

5.2.1 送风口的选择 (22)

5.2.2 回风口的选择 (23)

5.3 气流组织计算 (23)

5.3.1风机盘管散流器风口选择 (24)

5.3.2风机盘管侧送风口选择计算 (24)

5.3.3排风口的选择 (25)

第六章水力计算 (27)

6.1 风系统水力计算 (27)

6.1.1通风管道的设计原则 (27)

6.1.2通风管道的选择 (27)

6.1.3计算方法 (27)

6.2 空调水系统的水力计算 (28)

6.2.1空调水系统的设计原则 (28)

6.2.2水力计算及水泵选型方法与注意 (29)

6.2.3水力计算结果与设备选择 (29)

6.3水系统附件的设计 (30)

6.3.1膨胀水箱的设计计算 (30)

6.3.2集水器和分水器 (31)

6.3.3除污器和水过滤器 (31)

6.3.4放空气器 (32)

6.3.5阀门 (32)

6.3.6水系统安转要求 (32)

第7章机房的设计与布置 (34)

第8章通风与防排烟 (36)

8.1概述 (36)

8.1.1卫生间通风设计 (36)

8.1.2设备房的通风设计 (36)

8.1.3建筑防排烟设计 (37)

8.1.4高层建筑防排烟 (37)

8.2地下室通风、排烟设计与计算 (38)

第9章消声、减振与保温设计 (39)

9.1消声与隔声设计 (39)

9.2减振设计 (39)

9.2.1冷冻机、水泵及风机等设备的减振 (39)

9.2.2管道减振 (40)

9.3保温设计 (40)

参考文献 (41)

致谢 (42)

前言

空调技术是伴随着现代文明社会的进步而发展起来的。而当人们在享受着空调技术给人们的生产与生活带来方便和舒适时,紧接着也就在思考如何减少空调所需要销耗的能量。特别是进入20世纪70年代以来,以石油危机为标志的世界能源危机更加促使一些发达国家在各业中研究和推广节能技术。

改革开放以来,随着我国国民经济的飞速发展、人民生活水平的逐步提高,人们对自身生活环境也越来越重视,尤其是室内的空气环境。我国幅员辽阔,气候复杂,室内空气调节就显得非常必要,而且需求量越来越大。特别是近十年来,空调技术在我国得到空前发展,从事空调行业的专业技术队伍日益壮大,同时,大量的空调设计资料也日益完善。

目前,几乎所有的大型公共建筑都要安装中央空调系统,对生产工艺和室内洁净度有特殊要求的地方还必须建立洁净室。本设计便是针对天津市某酒店的空调设计。设计内容在本设计说明上均有详细的说明和计算,图纸包括空调系统平面图、空调水系统图、制冷机房布置图、、及主要材料明细表。

本设计中所有计算及文字说明均参考目前通行的相关规范、设计及施工手册。系统方案由本人单独完成,而系统自动控制、消声防震及防排烟等部分,由于本人所学知识所限不能对其进行更具体详细的设计,只能依据设计手册中的相关资料,对其原理进行说明。

但作为我们毕业前的一次综合实践,我觉得本次毕业设计对我们专业素质提高有非常积极的意义也为我们今后的出色工作打下了坚实的基础。在这里还需要强调的是,在设计过程中,承蒙李红枫老师的耐心指导和大力支持,在此表示衷心感谢

第1章工程概况

1.1室外气象参数

地点:天津市

地理位置:北纬39o48′,东经116 o28′,海拔高度为31.2m;

夏季数据:

表1.1夏季数据

1.2室内设计参数

表1.2室内设计参数

新风标准的确定:查《空调工程》课本表3-34得

1.3土建资料:

1.3.1外墙属于Ⅱ型,传热系数K=1.64 W/(m2?0C),

由外至内为:1)水泥砂浆抹灰

2)轻混凝土板(矿渣和炉渣混凝土,膨胀珍珠岩混凝土, 陶粒混凝土,矿渣浮石混凝土)

3)白灰粉刷

4)壁厚0.3mm

5)保温层ρ=1950

内墙传热系数取1.64 W/(m2?0C)

1.3.2屋顶属于Ⅱ型,传热系数K=0.48 W/(m2?0C),由上至下分别为:

1)预制细石混凝土板25mm,表面喷白色水泥浆。

2)通风层≥200mm。

3)卷材防水层。

4)水泥砂浆找平层20mm。

5)保温层,沥青膨胀珍珠岩125mm。

6)隔汽层。

7)现浇钢筋混凝土板70mm。

8)内粉刷。

1.3.3选用单层铝合金属窗框5mm厚的普通玻璃,80%的玻璃。窗帘为浅蓝色外门选铝合金金属门,传热系数0.57 W/(m2?0C)。

室内压力稍高于室外大气压力,所以不考虑空气渗入所产生的负荷

第2章负荷计算

2.1冷负荷理论根据

2.1.1房间冷负荷的构成:

(1)通过围护结构传入室内的热量;

(2)透过外窗进入室内的太阳辐射热量;

(3)人体散热量;

(4)照明散热量;

(5)设备散热量;

(6)其它室内散热量。

2.1.2.房间湿负荷的构成:

(1)人体散湿量;

(2)其它室内散湿量。

2.1.3主要计算公式:

1)外墙和屋面瞬变传热引起的冷负荷

在日射和室外气温综合作用下,外墙、外窗和屋面瞬变传热引起的逐时冷负荷可按下式计算:

CL=KF(t′wl-t Nx)(2.1)

式中: CL——通过外墙或屋顶瞬变传热形成的逐时冷负荷(W);

K ——外墙或屋顶的传热系数W/(m2?℃);

F ——外墙和屋顶的传热面积m2;

t′wl——外墙和屋面冷负荷计算温度的逐时值℃;

t

Nx

——室内设计温度℃;

t′wl =(twl+ t

d )k

αkρ;

twl——以天津地区的气象条件为依据计算出的外墙和屋顶冷负荷计算温度的

逐时值℃,根据外墙和屋顶的不同类型分别在《空调工程》附录7和附录8中

查取;

t

d

——不同类型构造外墙和屋顶的地点修正值℃;根据不同的设计地点在《空调工程》附录9中查取;

k

a

——外表面放热系数修正值在《空调工程》表3-7中查取;

k

ρ——外表面吸收系数修正值在《空调工程》表3-8中查取,考虑到城市大气

污染和中浅颜色的耐久性差,建议吸收系数一律采用ρ=0.90,即k

ρ=1.0。2)内墙等室内传热围护结构形成的瞬时冷负荷

当空调房间的温度与相邻非空调房间的温度大于3℃时,要计算通过空调房间隔墙、楼板、内墙、内门等内围护结构的温差传热而产生冷负荷CL:

CL=KF(t′ls-t Nx))(2.2)式中: CL、K、F、t Nx——同式(2-1);

t

l s

——相邻非空调房间的平均计算温度℃。

t'l s按下式计算:t′ls=t wp+Δt ls (2.3)

式中:t wp——夏季空调房间室外计算日平均温度,℃;

Δt ls——邻室计算平均温度与夏季空气调节室外计算日平均温度的差值℃,可按《空调工程》表3-9选取。

3)外玻璃窗瞬变传热引起的冷负荷

在室内外温差的作用下, 通过玻璃窗瞬变传热引起的冷负荷可按下式计算:CL=C w·K w·F w·(t wl+t d-t Nx) (2.4)式中:CL、t Nx——同式(2-1)

F w——玻璃窗口面积m2;

K w——玻璃窗的传热系数W /( m2·℃) ;

t wl——外玻璃窗冷负荷计算温度的逐时值可查手册;

C w ——玻璃窗的传热系数修正值可查手册;

t d——玻璃窗的地点修正值℃;

4)透过玻璃窗的日射得热引起的冷负荷

透过玻璃窗进入室内的日射得热形成的逐时冷负荷按下式计算: CL=C c,s·C a·F w·D j,max C LQ(2.5)

其中C c,s=C s·C i

式中:F w——玻璃窗的面积m2;

Cc,s——玻璃窗的综合遮挡系数Cc,s=Cs·Cn;

C

s

——玻璃窗的遮挡系数;

C

n

——窗内遮阳设施的遮阳系数;

C a——窗的有效面积系数;

C LQ——玻璃窗的冷负荷系数,按南北区划分而不同;

D j,max——不同朝向的逐时日射得热因数最大值;

5)空调区设备散热形成的冷负荷

A设备和用具散热形成的冷负荷按下式计算:

q s =Fq

f

(2.6)

式中:q

s

——设备的散热量W;

F——空调区面积m2;

q

f

——设备单位面积平均散热指标(w/m2)

B照明散热形成的冷负荷

根据照明灯具的类型和安装方式的不同,其冷负荷计算式分别为:

白炽灯:CL =1000·N·C

LQ

(2.7)

荧光灯:CL =1000·n

1·n

2

·N·C

LQ

(2.8)

式中: CL——照明设备散热形成的冷负荷W;

N——照明灯具所需功率 W;

n 1——镇流器消耗功率系数,当明装荧光灯的镇流器装在空调房间内时,取n

1

=1.2;当暗装荧光灯镇流器装设在顶棚内时,可取n

1=1.0;本设计取n

1

1.0

n

2

——灯罩隔热系数,当荧光灯上部穿有小孔(下部为玻璃板),可利用自然通

风散热与顶棚内时,取n

2=0.5~0.6;而荧光灯罩无通风孔时,取n

2

=0.6~

0.8;本设计取n

2

=0.6;

C

LQ

——照明设备散热冷负荷系数W。

本设计照明设备为暗装荧光灯,镇流器设置在顶棚内,荧光灯罩无通风孔。6)人体散热形成的冷负荷

人体散热引起的冷负荷计算式为:

CL=q

s ·n·φ·C

LQ

+q

2

·n·φ(2.9)

式中:CL——人体散热形成的冷负荷W;

q

s

——不同室温和劳动性质成年男子显热散热量W;

n——室内全部人数;

φ——群集系数;

C

LQ

——人体显然散热冷负荷系数,人体显然散热冷负荷系数。

q

——一名成年男子每小时潜热散热量W;

2

注意:对于人员密集的场所,如电影院、剧院、会堂等,由于人体对维护结构和室内

=1.0;

物品的辐射换热量相应减少,可取C

CL

=1.0

若在全天24h内室温不能保证恒定,(如夜间停止使用供冷系统),可取C

CL

7)新风冷负荷

目前我国空调设计中对新风量的确定仍采用现行规范、设计手册中规定或推荐的原

则。

q m,W,min=q m,W,p·n (2.10)

——夏季最小新风冷负荷(m3/h);

式中: q

m,W,min

——每人每小时所需要的最小新风量m3/(人·h);

q

m,W,p

n——室内人数;

当计算新风量值不满足系统送风量的10%,则新风量应按总送风量的10%计算

8)湿负荷

室内的湿负荷是人体的散湿量W按下式计算:

W=ω·n1·n2 (2.11) 式中:W ——夏季人体散湿量kg/s;

ω——单个成年男子的人体散湿量g/h;

n1——室内的人数;

n2——群集系数。

说明: 冬季的人员散湿量与夏季的一样,设备的散湿量不予考虑,仅有人员散湿

量,可按夏季人员散湿量的 1/2 计算。

2.2 新风量的计算

空调系统中引入室外新鲜空气是保证良好室内空气品质的关键。我国空调设计中

对新风量的确定,应采用规范和手册中的规定。

2.2.1 新风量标准的选取

《空调通风工程系统运行管理规范》中规定:

空调通风系统运行期间,新风量宜满足下表的规定值,或者满足空气调节房间内二氧化碳浓度小于 0.1%。

2.2.2 新风量的确定

对标准房间没房入住两人,每层共 14 间房间,故新风量每层为:

L=14*40*2=1120m3/h

按照建筑设计查询娱乐室人数为每层 180 人,故新风量为:

L=180*15=2700 m3/h,

又 ASHRAE 中规定:对于出现人数持续时间少于 3h 的房间,按平均人数确定新风量,平均人数≥总人数×0.5

因此,娱乐室每层新风量为:

L=0.7*2700=1890 m3/h

2.2.3 新风量计算结果与分析

第三章方案选择与计算

3.1 空调系统方案选择

冷热源方案的选择是空调系统设计过程中的一个重要的决策环节,关系到项目的投资、运行费用、对环境的影响、能耗等重要问题,是影响社会总能耗和工程投资的重要因素。

如何根据工程的实际条件,科学合理地选择冷热源,已成为工程技术人员和用户经常碰到且非常关注的问题。

空调系统的分类,按照使用功能可以分为舒适性空调和工艺性空调;按照空气处理空调方式可以分为集中式,半集中式和局部式。

表 3.1 全空气系统与风机盘管系统比较

全空气系统和风机盘管加独立新风系统各有各的优势,宾馆各客房及娱乐室包间,会议室等采用风机盘管加新风系统,便于管理,不使用时可以关闭系统。

3.2 空调冷热源选择

业主和工程设计人员自项目方案设计阶段就非常重视空调冷热源的选择问题,冷热源形式不同,初投资和能耗差别会很大,因此,相关人员需进行多次调研和咨询。如何根据实际条件正确选择冷热源,已成为设计工作者和用户经常碰到的一个问题,也是影响社会总能耗和工程投资的重要因素。

3.2.1 空调冷热源选择原则

空调冷热源方案选择的具体原则可归纳为以下几点:

1)热源设备的选用,应按照国家能源政策和符合环保、消防、安全技术规定,及

根据当地能源供应情况来选择,应以电和天然气为主,大中城市宜选用燃气、燃油锅

炉,乡镇可选用燃煤锅炉。

2)若当地供电紧张,有热电站供热或有足够的冬季供暖锅炉,特别是有废热、余热可资利用时,应优先选用溴化锂吸收式制冷机;

3)当地供电紧张,且夏季供应廉价的天然气,同时技术比较合理时,可选用直燃式溴化锂吸收式制冷机;

4)直燃式溴化锂吸收式制冷机与溴化锂吸收式制冷机相比,具有许多优点,因此,在同等条件下特别是有廉价天然气可资利用时,应优先选用;

5)制冷机与溴化锂吸收式制冷机相比,具有许多优点,因此,在同等条件下特别是有廉价天然气可资利用时,应优先选用;

6)按性能系数高低来选择制冷设备的顺序为:离心式、螺杆式、活塞式、吸收式、涡旋式

7)考虑建筑全年空调负荷分布和制冷机部分负荷下的调节特性,合理选择机型、台数和调节方式,提高制冷系统在部分负荷下的运行效率,以降低全年总能耗;

8)为了平衡供电峰谷差,有条件时应积极推广蓄冷空调和低温送风或大温差供水相结合的系统;

10)选用风冷还是水冷机组须因地制宜,因工程而异。一般大型工程宜选用水冷机组,小型工程或缺水地区宜选用风冷机组;

上述 10 个基本的选型原则,并非选型中考虑的全部因素和问题,但它是基本的、必要的。其它诸如产品的冷量调节范围、水资源状况、噪声、外形尺寸、电源的电压等级、占地、重量、无故障运行周期、服务质量等多种因素,也可能阶段性地升为突出问题

3.2.2 冷热源方案比较

空调的冷热源具体形式很多,并且均有各自的特点。常用的空调冷热源组合

A:电动冷水机组供冷+燃油锅炉供热;

B:蒸汽型溴化锂吸收式冷水机组供冷+热网供热;

C:电动压缩式冷水机组+外热网供热;

D:热泵技术供冷、供热;

本设计空调冷热源方案选择为热泵技术,热泵即通过少量的高位热能的输入,把不能直接利用的低位热能转化为可以利用的高位能,从而达到节约部分高位能的目的。

以下是各种热泵技术的比较:

(1)空气源热泵在以供暖为主的寒冷地区受到室外温度的限制,能源利用效率很

低,在以制冷空调为主的热带或亚热带地区不可避免地给城市区域带来热岛效应。另外,空气热容量小,机组容量及项目规模受到限制。

(2)地下水源热泵存在的主要问题是:我国水资源贫乏,地下水作为可再生性冷热源受到水资源保护等问题的限制,井水回灌技术要求高,不合理的成规模应用可能引发环境地质问题,另外还有水井枯竭、老化等。

(3)土壤源热泵系统传热效率低,埋管数量与占地空间很大,初投资高,在住宅密集度、容积率高的繁华城市区域内受到地理条件限制,机组装机容量要小,目前还难以实现大规模应用

(4)太阳能与日照时间及昼夜变化有关,需要附辅热源或蓄能系统,太阳能集热器初投资很大,目前建筑用能还很难承当,仅限于太阳能热水器的使用,另外太阳能制冷系统还处于研制开发阶段。

(5)对于回收工企业余热的热泵系统,通常需要具体的定量设计,如何保证系统的真节能,需要基于可靠的系统设计方法和先进的控制技术

本设计中,受各方条件制约,选择使用空气源热泵机组:

空气源热泵以室外空气作为冷热源,具有系统简单、年运行时间长、初始投资较低、技术比较成熟等优点,在冬季气候较温和的地区,如我国长江中下游地区,已得到相当广泛的应用。

空气源热泵的主要缺点是受室外环境的制约,在遇到夏季高温和冬季寒冷的天气时热泵的效率大大降低,而且制热量随室外空气温度降低而减少,制冷量随室外温度升高而降低,这与建筑物的冷、热负荷需求趋势正好相反。其次在供热工况下空气源热泵的蒸发器上会结霜,需要定期除霜,这也消耗大量的能量,特别是在寒冷地区和高湿度地区,热泵蒸发器的结霜成为较大的技术障碍,除霜损失约占热泵总能耗的10%。另外,空气源热泵体型较大,占地面积大;噪声较高。空气源热泵还会使得外界局部空间环境条件恶化,存在热岛效应。

3.2.3 本工程选择计算

主要根据热泵机组制冷量来选取机组,校核机组冷热水流量是否满足系统要求。机组型号如下表

表 3.2 风冷热泵模块机组参数

3.3 新风系统的方案确定

采用风机盘管+新风系统,新风的处理方式的不同,对室内有不同的影响,其新风有以下几种处理方式:

(1) 新风处理到低于室内含湿量,承担室内湿负荷。此时风机盘管在干工况下运行。

(2) 新风处理到室内焓值,而风机盘管承担室内冷负荷

(3) 根据室内的冷负荷、湿负荷和风机盘管的热湿比确定新风的处理状态点。

综合分析几种处理方式,本设计选择第二种,即将新风处理到室内焓值,由风机盘管承担室内的冷负荷。

房间中新风的送风方式共有两种方式:

(1)直接送到风机盘管吸入端,与房间的回风混合后送入风机盘管中冷却(或加热),送入室内。

(2)新风与风机盘管的送风并联送出,可以混合后再送出,也可以各自单独送入室内

综合分析两种送风方式,本设计选择第二种:新风与风机盘管并联送出,并采用各自单独送入室内的方式。这种方式虽然从安装方面讲,稍微复杂一些,但是避免了第一种送风方式的确定,很好的保证室内的卫生条件。

3.4 空调水系统论证

3.4.1 按调节特征分类

从调节特征上分,空调水系统可分为定水量系统和变水量系统两种形式。前者通过改变供回水温差来适应房间的负荷变化要求,系统中的水流量是不变的;后者则通

过改变水的流量(供回水温差不变)来适应房间负荷变化要求。所以,变水量系统要求空调负荷侧的供水量随负荷增减而变化,故输送能耗也将随之变化。

1)定水量系统

在定水量系统中,没有任何自动控制水量的措施,系统水量的变化基本上由水泵的运行台数决定。因此通过各末端的水量也是一个定值。这带来的一个缺点是当末端负荷减少时,无法控制温、湿度等参数,造成区域的过冷或过热。为了解决末端控制问题,也有的工程在末端设置三通自动调节阀,如图 4.2 所示。当负荷变化时,通过自动控制三通阀开度,调整旁流支路与直流支路的水量,从而控制末端设备的水量。

定水量系统管道简单,控制方便不需控制,因此在我国目前仍有一些使用标准较低的民用建筑中采用。但无论其末端是否设三通自控阀,系统本身存在下列缺点:

①冷水机组总容量及水泵总流量必须按各末端冷量的最大值之和来计算而不能按各末端冷量逐时之和的最大值来决定,否则会因水流量不够而造成部分末端冷量不足。从负荷和冷量计算中我们已知道;各末端冷量最大值之和必然小于整个系统的逐时最大值,尤其是各末端设备所服务的区域处于不同朝向和使用时间不一致时,这种情况更为明显。因此,这使得冷水机组和水泵的安装容量过大能耗过高,其他有关费用也随之增加。

②采用多台冷水机组和水泵联合运行时,其系统工作情况取决于水泵的运行方式。

(2)变水量系统

目前通常所说的―变水量系统‖,是指在水路循环的空调末端使用二通控制阀的系统,是与水路系统空调末端使用三通控制阀的―定流量系统‖相对而言的。变水量的目的是要使由冷源输出的流量,其所载冷量与经常变化着的末端所需冷量相匹配,从而节约冷量输送动力和冷源运行费用。

变水量系统常采用一级泵系统。

冷源侧设置多台冷水机组,负荷侧由室内恒温器调节二通阀进行控制,冷源侧和负荷侧之间的供回水管路上设有旁通阀。在旁通管上装压差调节器,控制旁通管上的二通阀,当用户负荷及负荷水流量减少时,供回水总管之间压差增大,通过调节器使旁通上的二通调节阀开大,让一部分水旁流;反之,用户侧水量增加时,供回水管总压差减小,调节器使旁通阀关小,使旁通水流量减小,从而保持冷水机组的水流量不变,同时也使负荷侧供回水温差恒定。旁通水量的多少亦影响了回水温度的高低,并由回水温度调节冷冻及冷量,以保持一定的蒸发器供水温度。与此同时,供回水总管的压差变化冷冻水泵和冷水机组运行台数(每台冷冻水泵对应一台冷水机组,且互为

连锁),以使冷冻机在部分负荷下进行节能运行。

3.4.2 按管路布置方式分类

按管路布置方式分为同程式系统与异程式系统,同程式系统是流经各终端设备的水流程相等,而异程式系统则相反。同程式系统的优点是各末端环路的水流阻力较接近, 有利于水力平衡,可以减少系统初调试的工作量;但同程式系统比异程式系统多用管材,同时由于采用回程管,管道的长度增加,水阻力增大,使水泵的能耗增加,并且增加了初投资。异程式系统中通常越远离冷源机房的末端,环路阻力越大;主要优点是节省管道及其占用空间(一般来说它与同程式系统相比可节省一条回水总管) ,对初投资较为有利。

由于本次设计的对象是酒店,室外机设在楼顶,层高均为 3.4 米,故选择水系统形式为同层水管同式,立管比摩阻较小,采用异程式

哈尔滨通达6号楼采暖及换热站设计_建环暖通毕业设计说明书 (NXPowerLite)

毕业设计(论文) 哈尔滨通达6号楼采暖及换热站设计 Harbin Tongda Building 6, heating and heat transfer station design 长 春 工 程 学 院 学生姓名 学历层次 所在系部 所学专业 所在班级 指导教师 教师职称 完成时间

摘要 现如今,随着经济的发展,人们生活水平的提高,大家对室内环境的要求也随之提高,集中供热被广泛地应用,采用集中供暖可以减少能量的浪费,提高供热效率,减少环境污染,利于管理。我国的供暖设计、施工和运行管理工作,主要是以学习前苏联供暖技术为依据。经过了数十年供暖通风技术人员的努力,在1975年建设部颁布的设计规范基础上,1987年颁布了适合我国国情的总结了供暖通风技术经验的国家标准《采暖通风与空气调节设计规范》(GBJ19-87)。规范中对室外计算温度和供暖热负荷的确定以及计算原则和方法,进行了大量的研究和编制工作,其成果与世界先进国家的相比毫不逊色。3003年颁布了现行的《采暖通风与空气调节设计规范》(GBJ50019-2003)。 在进行采暖设计的时候,系统大容易出现系统的垂直失调或者水平失调,无论出现何种的失调现象,都乎对采暖系统的预期效果产生很大的影响,所以我们在进行设计的同时一定要注意这一点。为了防止失调的产生,本设计对建筑划分成六个采暖分区进行设计,这样就能有效的防止在本设计中出现水力失调的产生。 关键词: 集中供热规范水力平衡节能

Abstract Now, along with economic development, people's living standards improve, people on the indoor environment requirements also will increase, central heating is widely used, the use of central heating can reduce energy waste, improve heating efficiency and reduce environmental pollution, which will help manage. The heating of the design, construction and operation management of the former Soviet Union, mainly to learn heating technology as the basis. After decades of heating, ventilation efforts of technical staff, the Ministry of Construction issued in 1975 on the basis of the design specifications, in 1987 issued a summary suitable for China's national experience in the heating and ventilation technology standard "heating, ventilation and air conditioning design specifications" (GBJ19-87). Specification of the outdoor temperature and heating load calculation to determine and calculate the principles and methods, a great deal of research and preparation, the results with the world advanced countries compared favorably. 3003 was enacted in the current "heating, ventilation and air conditioning design specification" (GBJ50019-2003). During heating design, the system is prone to large systems or horizontal vertical imbalance disorders, regardless of what kind of imbalances occur, are almost the expected result of the heating system have a huge impact, so we must at the same time during the design attention to this point. In order to prevent the generation of offset, the design of the building is divided into six heating partition design, this can effectively prevent the water appears in the design of the generation of imbalance. Keywords: Central heating specification hydraulic balancing energy

暖通空调设计毕业设计说明书

摘要 本设计为哈尔滨望江集团办公楼空调系统工程设计。哈尔滨望江集团办公楼属中小型办公建筑,本建筑总建筑面积4138m2,空调面积2833m2。地下一层,地上八层,建筑高度33.9m。全楼冷负荷为191千瓦,全楼采用水冷机组进行集中供给空调方式。 此设计中的建筑主要房间为办公室,大多面积较小,且各房间互不连通,应使所选空调系统能够实现对各个房间的独立控制,综合考虑各方面因素,确定选用风机盘管加新风系统。在房间内布置吊顶的风机盘管,采用暗装的形式。将该集中系统设为风机盘管加独立新风系统,新风机组从室外引入新风处理到室内空气焓值,不承担室内负荷。风机盘管承担室内全部冷负荷及部分的新风湿负荷。风机盘管加独立新风系统由百叶风口下送和侧送。水系统采用闭式双管同程式,冷水泵三台,两用一备;冷却水泵选三台,两用一备。 在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定新风机和水泵。 依据相关的空调设计手册所提供的参数,进一步完成新风机组、水泵、热水机组等的选型,从而将其反应在图纸上,最终完成整个空调系统设计。 关键词:风机盘管加独立新风系统;负荷;管路设计;制冷机组:冷水机组

Abstract The design for the Harbin Wangjiang Design Group office building air conditioning system. Harbin Wangjiang Group is a small and medium-sized office building office buildings, the total floor area of building is 4138m2, air-conditioned area is 2833m2. There are eight floor of the building, building height is 33.9m. Cooling load for the entire floor, 191 kilowatts, the whole floor using Central Cooling Chillers to focus on the way . This design of the main room of the building for office, most of them is very small, and the rooms are not connected, the selected air-conditioning system should be able to achieve independent control of each room, considering the various factors to determine the selection of fan-coil plus fresh air system. Arrangement in the room ceiling fan coil units, using the dark form of equipment. Set the focus on fan-coil system, plus an independent air system, fresh air from the outdoor unit to deal with the introduction of a new wind to the indoor air enthalpy value, do not bear the load of indoor. All bear the indoor fan-coil cooling load and part of its new rheumatoid load. Fan-coil plus an independent air system sent by the Venetian and the under side air delivery. Closed water system with a dual-track program, three cold-water pump, dual-use a prepared; cooling pumps three elections, one prepared by dual-use. In the cooling load calculation based on the completion of the selection of host and fan coil units, and air volume, the calculation of water, the wind pipe and water pipes to determine the specifications of the road and check the resistance to the most disadvantaged and the loop to determine the pressure head new fans and pumps. Based on the relevant manuals provided by air-conditioning design parameters, and further completion of the new air units, water pumps, hot water units, such as the selection, which will be reflected in their drawings, the final design of the entire air-conditioning system Key words: PAU+FCU systems; load; pipeline design; refrigeration machine; Chillers

空调毕业设计说明书

……………………. ………………. ………………… 山东农业大学 毕 业 设 计 题目:南京实验楼集中空调系统设计 院 部 水利土木工程学院 专业班级 建筑环境与设备工程2010级3班 届 次 2010 学生姓名 孙晴 学 号 20103496 指导教师 王萌 二O 一四年六月十四日 装 订 线 ……………….……. …………. …………. ………

目录 一. 设计资料及说明 (1) 二. 空调设计方案分析 (2) 三. 负荷计算 (4) 四.空气处理过程设计 (12) 五. 房间气流组织方案设计 (14) 六. 水系统的水力计算 (15) 七.风系统的水力计算 (17) 八. 冷热源的设计和布置 (19) 九.空调设备明细表 (20) 十.空调系统消声减振的设计方案 (22) 十一.空调系统控制和调节 (24) . . . 参考文献 (24) 致谢词 (25) 附录(附件) (26)

南京实验楼集中空调系统设计 作者:孙晴 10建环3班 指导老师:王萌 设计内容简介: 对南京实验楼集中空调系统进行了设计。该实验楼共三层,建筑总面积6738.24m2,其功能包括:实验室、教室、办公室。该中心总冷负荷880.83kw,总热负荷744.02kw。基于冷负荷、湿负荷、热湿比及其功能区特点,并考虑到经济性和可行性,确定出了该实验楼的具体所适用的空调系统方案,并针对此方案进行了水管风管的布置、水力计算、设备选型及设备布置及对设备的消声减振的设计。

1 设计说明及资料 1.1原始资料 1.1.1 设计地区:江苏南京 1.1.2 建筑资料:该实验楼为五层建筑,第一、二、三层有实验室,内厅,卫生间等,第四层有实验室,教室,办公室,卫生间等。第五层有教室,卫生间。现以提供各层结构平面图等。每层层高除二层为5.4m外均为4.5m,吊顶3m(局部可低)1.1.3 室内设计参数 表1-1-1 1.2 室外气象资料和围护结构资料 1.2.1室外气象资料 表1-2-1 1.2.2围护结构资料 外窗-------普通玻璃,传热系数为3.6 w/m2.℃

中央空调设计说明书

第1章工程概况 第1章工程概况 1.1建筑概况 星城酒店广东省汕头市,总建筑面积为19595㎡,地上9层,地下一层,总建筑高度为34.3m。其中地下一层主要为休闲运动场所,一层为餐厅、会议室、办公室等,二层主要为桑拿中心,三层以上为客房。 1.2 计算参数 1.2.1 室外计算参数 表1.1 广州市夏季室外气象参数 大气压力(Pa)空调室外计算干球温度(℃)空调室外计算湿球温度(℃) 室外平均风速(m/s)100287 33.4 27.7 2.7 1.2.2 室内计算参数 表1.2 各空调房间室内计算参数 房间名称 夏季新鲜空气量噪声标准温度(℃) 湿度(%) m3/h·人dB(A) 客房25 50~65 30 < 45 乒乓球室、壁球室、桌 球室、美容美发、棋牌 室、投影室、健身房、 阅览室、银行 25 55~65 30 < 50 餐厅、会议室、茶室25 55~65 25 < 45 1.2.3 其他设计参数 表1.3 照明功率密度值(W/㎡) 建筑类别房间类别照明功率密度 酒店 餐厅13 中庭、大厅15 银行18 其他11

广东石油化工学院本科毕业设计:星城酒店空调工程设计 表1.4 不同类型房间人均占有的使用面积(㎡/人) 建筑类别房间类别人均占有的使用面积㎡ 酒店 客房10 餐厅 2 运动场所 5 其余 2 1.3 主要设计依据 1.3.1建筑与暖通空调工程制图标准 1、房屋建筑制图统一标准(GBJ 1—86); 2、采暖通风与空气调节制图标准(GBJ 114—88)。 1.3.2 通用设计规范 1、采暖通风与空气调节规范(GBJ 19—87); 2、民用建筑节能设计标准(JGJ 26—95); 3、民用建筑热工设计规范(GB 50176—93); 4、民用建筑设计通则(JGJ 37—87); 5、建筑设计防火规范(TJ 36—79); 1.3.3专用设计规范 1、办公建筑设计规范(JGJ 67—89); 2、综合医院建筑设计规范(JGJ 49—88); 1.3.4暖通空调工程施工及验收规范 1、通风与空调施工及验收规范(GB 50243—97); 2、压缩机、风机、泵安装工程施工及验收规范(JBJ 29—96); 3、制冷设备、空气分离设备安装工程施工及验收规范(GB 50274—98); 4、制冷设备安装工程施工及验收规范(GBJ 66—84)。

综合办公楼空调系统设计说明书

综合办公楼空调系统设 计说明书 空调系统 过去 50 年以来,空调得到了快速的发展,从曾经的奢侈品发展到可应用于大多 数住宅和商业建筑的比较标准的系统。在 1970 年的美国, 36% 的住宅不是全空气调节就是利用一个房间空调器冷却;到1997年,这一数字达到了 77%,在那年作的第一 次市场调查表明,在美国有超过一半的住宅安装了中央空调 (人口普查局, 1999)。在1998年,83%的新建住宅安装了中央空调 ( 人口普查局, 1999)。中央空调在商业建筑物中也得到了快速的发展,从 1970年到1995年,有空调的商业建筑物的百分比从54% 增加到 73%(杰克森和詹森,1978)。 建筑物中的空气调节通常是利用机械设备或热交换设备完成.在大多数应用中,建筑物中的空调器为维持舒适要求必须既能制冷又能除湿,空调系统也用于其他的场所,例如汽车、卡车、飞机、船和工业设备,然而,在本章中,仅说明空调在商业和住宅 建筑中的应用。 商业的建筑物从比较大的多层的办公大楼到街角的便利商店,占地面积和类型差 别很大,因此应用于这类建筑的设备类型比较多样,对于比较大型的建筑物,空调设 备设计是总系统设计的一部分,这部分包括如下项目:例如一个管道系统设计,空气 分配系统设计,和冷却塔设计等。这些系统的正确设计需要一个有资质的工程师才能 完成。居住的建筑物(即研究对象)被划分成单独的家庭或共有式公寓,应用于这些 建筑物的冷却设备通常都是标准化组装的,由空调厂家进行设计尺寸和安装。 本章节首先对蒸汽压缩制冷循环作一个概述,接着介绍制冷剂及制冷剂的选择,最后介绍冷水机组。 1.1 蒸汽压缩循环

建环专业课程教学大纲——毕业设计

《毕业设计》课程教学大纲 课程中文名称:毕业设计 课程英文名称:Undergraduate Thesis 课程编号: 适用专业:建筑环境与设备工程 学时数:13周学分数:13 课程性质:应开课学期:42 执笔者:徐文忠审核人:刘靖 批准人:定稿日期: 一、课程的性质和目的 毕业设计是本科教学的必修环节。是学生综合素质与培养效果的全面检验;是学生毕业及学位资格认证的重要依据;也是专业教学质量的综合反映。 毕业设计的目的在于: ⑴通过毕业设计,使学生进一步巩固加深所学的基础理论、基本技能和专业知识,使之系统化、综合化; ⑵在毕业设计过程中着重培养学生独立工作、独立思考并运用已学的知识解决实际问题的能力,同时培养学生独立获取新知识的能力; ⑶通过毕业设计加强对学生野外调查、资料获取、实验方法、数据资料的综合处理、计算机应用等最基本的工作实践和科研能力的培养; ⑷通过毕业设计的训练,使学生树立起严谨、负责、实事求是、刻苦钻研、勇于探索并具有创新意识及与他人合作的工作作风; 二、课程教学的主要内容及学时分配 设计时间为13周。 根据指导教师拟订的设计题目及毕业设计任务书完成如下一项或二项任务: ⑴大中型工业或民用建筑工程的采暖通风及空调工程设计; ⑵大中型锅炉房的工艺设计; ⑶城市换热站的工艺设计; ⑷大中型制冷机房的工艺设计;

⑸城市燃气工程的设计; ⑹大中型工业与民用建筑工程的给排水及消防工程设计。 学生应完成的具体内容包括: ⑴有关系统的设计资料的收集(1周); ⑵有关系统的设计与工艺计算(3周); ⑶设计工艺图的绘制(2周); ⑷设计平面图、系统图及大样图等施工图的绘制(4周); ⑸设计计算说明书的整理(2周); ⑹毕业设计的总结和毕业答辩(1周)。 三、课程教学的基本要求 毕业设计计算说明书应内容完整、计算准确、论述简洁、论据充分、层次清晰、文理通顺、装订整齐,且不少于20000字;毕业设计图纸应能较好地表达设计意图,图面布局合理、正确清晰、符合制图标准及有关规定。 四、本课程与其他课程的衔接与分工 本教学环节应安排在全部理论教学和其他实践环节的完成以后,即毕业设计应为本科教学的最后一个环节。 五、考核方式 1、毕业设计结束后,每个学生必须按任务中所规定的文件、图纸、实验报告等,整理装订成册,于答辩前一周交给指导教师。 2、指导教师评阅后,交由答辩委员会(答辩小组)确定的本专业负责评阅学生毕业设计评阅教师,评阅教师根据学生毕业设计文件质量写出评语并给出评语。 3、毕业设计经过审查、评阅,可以参加答辩者,须按时参加答辩。答辩时间控制在40分钟左右。 4、学生答辩结束后,答辩委员会(答辩小组)可根据每个学生毕业设计的质量及答辩情况,并参考指导教师和评阅教师的评分意见,按优秀、良好、中等、及格、不及格评定毕业设计成绩。同时对每个学生填写毕业设计成绩评定表。 六、建议教材与教学参考书

格力中央空调设计说明

方 案 设 计 (X X X) 昆明XXXX工程有限公司 地址:XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX 电话:XXXXXXXXXXXXXXXXX 传真:XXXXXXXXXXXXXXXXXX 日期: 二〇一二年二月八日 一、工程概况 该工程位于云南省曲靖市 二、设计原则 A.本工程按舒适性空调设计,满足室内的空气品质要求

B.选用空调机的噪音等符合国家相关标准。 C.选用空调机能效比符合国家相关标准。 D.选用空调系统与建筑协调、美观。 E.采暖通风与空气调节设计规范 F.室内空气质量标准 G.全国民用建筑节能设计标准 H.格力空调产品样本 三、气象参数 . 昆明市地处北纬23°38′,东经103°38′ 冬季室外平均气温8℃ 大气压:夏季864。4hPa 夏季空调计算干球温度:30℃夏季空调计算湿球温度:22℃冬季空调计算干球温度:4℃冬季空调计算相对湿度:69% 四、设计方案 (一)、系统选择 本项目采用格力MB系列风冷模块中央空调机组——水系统,由新型风冷模块主机集中提供冷热源;经保温管路送至各空调区域,由各室内机就近进行热湿处理,满足空调区域的人体舒适度要求。(二)、设备选择 主机选用珠海格力电器股份有限公司生产的MB系列中央空调机组LSQWRF80M/B 一台,单台夏季制冷量为80Kw.末端设备选用珠海

格力电器股份有限公司生产的风机盘管共14台,其型号规格见配置表与报价清单。 (三)该空调系统特点 方案选择 a、方案选择 本工程选用全封闭涡旋压缩机产生冷热原。靠风冷方式冷却。室内外机连接管路用镀锌钢管。 b、方案特点 (1)低能耗设计 采用风冷式、大于4.0的cop值。 (2)空调系统管理简便,成本低廉: 风冷系统为全主机微电脑自动控制,无需专业人员专门管理,管理成本低廉。 (3)系统简单 针对传统冷水机组加热水机组的中央空调系统,省略了冷却水系统、冷却塔等设施,简化了安装,维护难度,在达到设计效果的基础上节约了成本。 设备选择 依据设计负荷指标,在各空调区域选择相应的室内机组,并综合配套选择室外机组,满足冬夏季室内空气舒适度要求。

空调系统设计说明书_范文

设计总说明 本设计为上海市某办公楼空调通风系统设计。该办公楼属大型办公建筑,总建筑面积约为55000㎡。地下两层,地上二十八层,建筑总高度为99.6m。地下两层为车库及设备用房,地上二十八层均为办公用房。该建筑的主要功能间有办公室、会议室、接待室等。全楼冷负荷为3080千瓦,全楼采用风冷热泵机组进行集中供给空调方式。 本建筑位于上海市。上海市地处我国东部沿海地区,东经121°43′,北纬31°16′。属于亚热带季风气候区,四季分明,夏热冬冷,春秋短暂,但由于地处沿海,雨季较为分散,以夏季雨量最大。夏季空调室外日平均温度30.4℃,办公室室内温度26℃,湿度65%,室内风速v ≤0.3 m/s;冬季办公室室内温度20℃,湿度40%,室内风速v≤0.2 m/s。 设计的依据主要有同济大学浙江学院毕业设计(论文)任务书《上海市某办公楼空调通风系统设计》、采暖通风与空调设计规范GBJ19—87、HV AC暖通空调节设计指南、高层民用建筑设计防火规范GB50045—95(2005版)、GB 50189-2005 公共建筑节能设计标准、简明通风设计手册等。 考虑该大厦为办公楼,空调的运行时间主要在上班时间,所以计算负荷时本设计取的时间为6—18时。此设计中的建筑主要房间为办公室,大多面积较小,且各房间互不连通,应使所选空调系统能够实现对各个房间的独立控制,综合考虑各方面因素,确定选用风机盘管加新风系统。在房间内布置吸顶式风机盘管,嵌入暗装的形式。将该集中系统设为风机盘管加独立新风系统,新风机组从室外引入新风处理到室内空气焓值,不承担室内负荷。风机盘管承担室内全部冷负荷及部分的新风湿负荷。风机盘管加独立新风系统由百叶风口下送和侧送。水系统采用闭式双管异程式,冷水泵四台,三用一备。 在冷负荷计算的基础上完成主机和风机盘管的选型,并通过风量、水量的计算确定风管路和水管路的规格,并校核最不利环路的阻力和压头用以确定风机和水泵。 通风设计方面,地下室为车库及设备用房,设计成机械送排风为主,自然进排风为辅的方式,其换气每小时不小于6次;卫生间排风设计为排风扇机械排风到外阳台,排风量按每小时不小于10次的换气量计算;考虑到办公室吸烟问题,也采用排风扇机械排风到外阳台,排风量为送风量的80%。电梯前室及楼梯间设计加压送风。 该设计按照建筑结构及其要求制定空调方案,力求能够满足使用的要求,即能够满足办公舒适性。此外还要从空调设计的科学合理性和经济性,以及建筑整体的美观度考虑。中央空调在现代建筑中越来越多的应用,技术也越来越成熟先进。能够有效的管理,一次性投资,后期使用方便,并且不占用建筑的有效空间。本文就是对中央空调的设计到选型,到校核计算的一个说明。从使用性到科学性再到经济性上做到好的结合。方案选择是整体考虑以及设计的总体思想,计算部分是整个设计的基础,绘图部分是与设计施工相联系的实际的走管和安装。三个部分相依相承,都与整个工程密不可分。各个部分都要保证科学合理,正确无误,经济适用。 本设计是真实性课题的典例。其中,有理论的分析计算,有中央空调方案的选择论证,有实际的绘图安装。是一个完整的工程设计实例。设计计算主要有冷负荷的计算,送风量的计算,管路的计算等。冷负荷的计算确定了各个房间的空气状况和调节条件,以及整个工程的负荷量。是确定室内空调调节方案的主要数据。也是选择冷水机组最主要的参考数据。送风量和管路的计算是面向实际设备和管路的数据资料。都是整个设计的基础。 在上面主要阶段完成以后还要对一些具体细节的问题加以论证思考并列出解决方案。比如管

中央空调分类及主要设备

核心提示:讯中央空调的分类一、按照能源方式分类:1、电制冷空调2、溴化锂制冷空调3、其他能源空调二、电制冷空调是我们用到最多的空调形式,具体谈谈电制冷空调的分类:按照冷却方式分类:1、风冷:冷凝器采用强制空气对流的方式进行换热,家用空调基本上都是这种,风冷空调又有单冷型和热泵型两种,单冷型顾名思义只可以夏天制冷,热泵型既可以夏天制冷又可以冬天制热。2、水冷:从冷凝器散发的热量用水流进行冷却,为达到节水的目的 讯 中央空调的分类 一、按照能源方式分类: 1、电制冷空调 2、溴化锂制冷空调 3、其他能源空调 二、电制冷空调是我们用到最多的空调形式,具体谈谈电制冷空调的分类: 按照冷却方式分类: 1、风冷:冷凝器采用强制空气对流的方式进行换热,家用空调基本上都是这种,风冷空调又有单冷型和热泵型两种,单冷型顾名思义只可以夏天制冷,热泵型既可以夏天制冷又可以冬天制热。 2、水冷:从冷凝器散发的热量用水流进行冷却,为达到节水的目的,冷凝器出来的冷却水被水泵输送到冷却水塔,与空气进行热交换后在回到冷凝器。水冷系统一般只能制冷。 按照主机压缩机的形式分类: 1、活塞式压缩机:是早期空调曾普遍使用的压缩机,因为零部件过多,故障率较高,且生产成本也比较高,运行稳定性差,压缩机抗液击的能力差,现在已经很少使用。 2、涡旋式压缩机:目前使用频率很高的一种压缩机,压缩机由定盘、动盘、电机、机体四大部分组成,最大的特点是零部件少,运行稳定性高,使用寿命长,广泛的运用于小型制冷机组,如后面讲到的模块机、家用空调等。 3、螺杆式压缩机:在大型中央空调主机上使用最频繁的压缩机,其特点是零部件少、稳定性高、使用寿命长、维修方便等,还有很重要的一点是螺杆机的能效比很高,同样的制冷量,螺杆机比活塞机节能25%以上。螺杆机有单螺杆和双螺杆之分。 4、离心式压缩机:离心机的外观看起来就像是个大的离心式水泵,其结构和水泵结构也比较相似。离心式压缩机往往用在功率比较大的中央空调主机上,特点是单机制冷量大,结构简单、性能可靠、运行稳定,由于其对生产工艺的要求很高,目前只有几家国际大公司,如特灵、约克等大规模的生产销售,国产品牌美的在重庆的工厂也可以生产。 按照室内系统的不同分类:

(WI-FM-004)约克中央空调系统操作手册

北京XXXXX物业管理服务有限公司广州分公司XXXXX南方工厂B区综合设施管理项目部 B2中央空调操作流程 XXXXX/WI

目录 1.目的 (3) 2.范围 (3) 3.定义 (3) 4.职责 (3) 5.程序 (3) 6.相关文件.......................................... 错误!未定义书签。 7.相关记录.......................................... 错误!未定义书签。

1. 目的 指导运维对中央空调设备进行正确的操作及检查,保障中央空调设备的正常、高效、节能运行,为客户的生产和办公提供符合KPI要求的环境。 范围 本程序适用于XXXXX XXXXX南方工厂B区项目。 2.定义 无 3.职责 暖通工程师 1.负责制定设备操作程序; 2.制定教育培训资料及培训计划,并对运行和维护人员进行定期培训与考核; 3.处理设备重大故障,制定重大异常故障的改善方案及执行。 BMS 1.带领本班组技术员对设施运行进行监控及时发现问题、解决问题,并按照汇报程序及时向上级汇报; 2.监控设备运行情况,确保它们在高效方式下运行。 运行班长 1.监督运行技术员每日例行检查的完成情况,确保按照部门规定对设备设施进行日常检查; 技术员 1.严格执行本程序,确保信息及时有效地传递给运行值班长及主管; 部门经理: 1.负责与客户沟通和协调。 4.操作程序 启动: 1.确认现场冷水主机、冷却塔、冷冻泵、冷却泵在”自动“远程控制状态下且供电正常。 2.检查现场阀门正常开启状态。 3.进入“XXXXX南方工厂冷源系统界面” 自动运行: 1.将主机1-5锁定值设定为“UNL ock”。

毕业设计说明书

毕业设计说明书 设计题目:家居设计之现代简约风格作者姓名:xxx 班级学号:装饰艺术09A1 091043034 系部:艺术系 专业:装饰艺术设计 指导教师:xXx x 年x 月x日

家居设计之现代简约风格 摘要:现代简约风格是近来比较流行的一种风格,其室内布置整体设计就两个字概括“简约”。没有繁琐的装饰,不要附加物,只要能表达出意图即可,材料多为磨砂玻璃、不锈钢和石膏板等,地面、天花板均朴素、淡雅,无一多余饰物,显得简洁、舒适、大方,令人赏心悦目,这样的设计风格崇尚少即是多,装饰少,功能多,十分符合现代人渴求简单生活的心理。因而很受那些追求时尚又不希望受约束的青年人所喜爱。 关键词:设计风格简约材料心理关系

目录 摘要…………………………………………………………………………( 2 ) 前言…………………………………………………………………………( 4 ) 1.现代简约设计风格整体介绍………………………………………………( 5 ) 1.1 简约风格的基本特点…………………………………………………( 5 ) 1.2 简约风格中的色彩搭配体现和分析………………………………( 6 ) 2. 课题研究的背景及意义…………………………………………………( 7 ) 2.1研究背景………………………………………………………………( 7 ) 2.2 研究意义………………………………………………………………( 7 ) 3.设计概述……………………………………………………………………( 8 ) 3.1 设计理念与原则………………………………………………………( 8 ) 3.2 客厅的设计……………………………………………………………( 8 ) 3.3 厨房的设计……………………………………………………………( 9 ) 3.4 主卧的设计……………………………………………………………( 9 ) 3.5书房的设计……………………………………………………………( 10 ) 3.6卫生间的设计…………………………………………………………( 10 ) 4.其他作品欣赏…………………………………………………………………( 10)结论……………………………………………………………………………( 11 )致谢……………………………………………………………………………( 12 ) 参考文献………………………………………………………………………( 13 ) 图录……………………………………………………………………………( 14 )

青岛市某大楼中央空调设计说明

目录 (1) 第一章工程概述与设计依据 (3) 1.1 工程概述 (4) 1.2 设计依据 (4) 1.2.1 围护结构热工指标 (4) 1.2.2 室外设计参数 (4) 1.2.3 室设计参数 (5) 1.2.4 体力活动性质 (5) 第二章负荷计算 (6) 2.1 夏季冷负荷的计算 (7) 2.1.1 夏季冷负荷的组成 (7) 2.1.2空调冷负荷计算方法 (7) 2.2 湿负荷的计算 (9) 2.2.1 湿负荷的组成 (9) 2.2.2 湿负荷的计算方法 (10) 2.3 冬季热负荷的计算 (10) 2.3.1 围护结构传热耗热量 (10) 第三章空调方案的确定 (11) 3.1 空调系统的确定 (11) 3.1.1 全空气系统方案的确定 (11) 3.1.2 风机盘管加新风方式的确定 (12) 3.2 空气处理过程设计 (12) 3.2.1 全空气系统设计计算 (12) 3.2.2 风机盘管加独立新风系统设计 (14) 第四章风系统的设计 (16) 4.1 风管材料和形状的确定 (16) 4.2 送、回风管的布置 (16) 4.3 气流组织设计 (17) 4.3.1 全空气系统 (17) 4.3.2 风机盘管加新风系统 (17)

4.4 风管设计 (17) 4.4.1 风道水力计算步骤 (17) 4.4.2新风机组的选型 (18) 第五章水系统的设计 (19) 5.1 水系统方案的确定 (19) 5.1.1 两管制水系统的特点 (19) 5.1.2 闭式系统的特点 (19) 5.1.3 同程和异程系统的选择 (20) 5.1.4 一次泵变流量系统的选择依据 (20) 5.1.5 水系统方案的确定 (20) 5.2 冷冻水管路设计计算步骤 (21) 5.3 冷冻水泵的选型 (22) 5.3.1 冷冻水泵设计规 (22) 5.3.2 冷冻水泵的选型 (23) 5.3 冷凝水排放系统设计 (23) 第六章空调冷热源的确定 (24) 第七章通风与防排烟设计 (25) 7.1 防排烟的方式 (25) 7.2 空调建筑的防火防烟措施 (26) 7.3 通风、防排烟设计 (26) 第八章管道保温设计的考虑 (28) 8.1 管道保温的一般原则 (28) 8.2 管道保温层厚度的确定 (28) 第九章空调系统消声减振的设计方案 (29) 9.1 空调系统消声设计 (29) 9.2 空调系统减振设计 (30) 总结 (30) 参考文献 (31) 致32 附录 (33)

国祥空调说明书

国祥空调说明书 国祥?空调说明书 ?篇一:? 国祥?风冷模块安装使用说明?书 ?篇二: ? 空调控制?板维修中央空调控制?维修关键词电子膨?胀阀故障检测及修理方?法富田螺杆机组配置?广州大麦空调控制器?格力中央空调外置电?子膨胀阀结构降膜螺?杆机组如何控制西?臣仕中央空调系统电?脑控制汇中地源热泵?空调说明书克莱门特?中央冷暖空调控制电路?sink空调空气?处理机组线路板海润?空调风冷模块机组安?装图纸水源热泵监控?系统枫叶能源空调水?机组故障代码热泵电?子膨胀阀故障聊城麦?克维尔地源热泵奇威?特中央空调空调电子?膨胀阀维修指引奇威?特控制器模块机通用?电路板电子膨胀阀接?线图电子膨胀阀原理?空调板式换热器冻坏?中央空调空调FER?D LIS 约克YCA?E-BC使用说明中?央空调通用控制器空?调风冷模块通用电脑板?蒋立天加天加?蒋立螺杆水冷空调液?晶线路板空调电路板?接线中央空调市场占?有率空调监控 GP?R S模块空调遥控器?维修中央空调压缩机?保养图片格力201?X上半年销售额富田?中央空调主板汇中中?央空调喷液压缩机?麦克维尔热泵控制板?伯瑞斯B-8空调天?津开利螺杆冷水机组?主板谷轮压缩机内?部结构天加空调蒋立?中央空调接线图空?调开关电源的原理欧?科中央空调简介麦克?维尔风冷模块机组报压?缩机过载电子膨胀阀?原理图中央空调PL?C系统中央空调因电?造成故障空调使用年?限规定电子膨胀阀门?的原理模块机万能控?制板伯瑞斯空调格?力201X年上半年销?售额约克空调机型?C00 2.MC?B.P:00 ? 3. 中央空调?电脑远程控制器空气?处理机组电路板地源?热泵空调品牌空调变?频通用板 carel?easytls编程?软件下载 eurkl?i mat 空

建环毕设说明书 中央空调系统设计

摘要 摘要 本次毕业设计的主要内容是对天津市某酒店进行中央空调系统设计。该建筑位于天津市,共5层,总制冷负荷约为900KW,室内采用风机盘管系统为主。本次设计涉及到空调系统的划分,冷热负荷的计算,空调设备的选型,风管的水力计算和布置,管道的消声,防震,冷冻机房的设计,水系统的划分,水管的水力计算及水管布置,水泵和通风机的选择,通风系统的自动控制等。 关键词:中央空调、通风设计、设备选择、水力计算、冷冻机房

Abstract the main content of this graduation design is a four-star hotel in Tianjin for central air conditioning system design. The building is located in Tianjin, a total of 5 layers, total cooling load is 900KW, indoor fan coil system. This design involves the division of the air conditioning system, cooling and heat load calculation, the selection of air conditioning equipment, duct hydraulic calculation and arrangement of pipeline of noise elimination, shockproof, the design of the cooling room, the division of water system, the hydraulic calculation of pipe and pipe arrangement, the choice of the pump and fan, ventilation system, such as automatic control

设计方案说明(格力空调)

第一部分:设计方案说明 格力小型中央空调系统设计方案 一、工程概况 本方案中住宅的建筑室内面积约为多m2空调使用面积约为m2。设有客厅、餐厅、主卧室、次卧、 书房。 本工程设计:主机采用格力数码多联家用中央空调机组。 1.电控系统:由主机电控部分、末端内机电控部分、主机与室内机联网控制部分组成。 2.控制方式:各房间室内机就地独立自动控制,主机在电脑控制下自动运行,全部室内机末端可 与主机联动。 二、设计参数 (一) 室外气象参数: 夏季空调室外计算干球温度 T=36.5℃ 夏季空调室外计算湿球温度 Ts=27.3℃ 冬季干球温度 T=2.0℃ 冬季空调室外计算相对湿度Ф=82% 大气压力夏季 991.2hPa 冬季 973.2hPa (二)室内设计参数: 夏季室内温度冬季室内温度 24-28℃18-22℃ 三、设计依据 (一)设计采用规范 1.《采暖通风与空气调节设计规范》。GBJ19-87(2001年版) 2.《户用和类似用途冷水热泵机组》国家标准(GB/T18430.2-200119-87) 3.《家用中央空调实用技术手册》(交通出版社) (二)业主要求 1.业主单位提供的建筑平面图; 2.主机与室内机均采用格力产品 3.空调主机按全负荷的计算。 4.空调内外机连接采用紫铜管,冷凝水管采用蓝色UPVC管。 四、设计思想 (一)优化系统设计,确保运行稳定可靠。 (二)室内温度可在一定范围内随意调控,控制器为格力标配的液晶显示智能温控器,其特点为:1.超小型外观设计,大液晶数字显示室内温度。

2.室内自动恒温控制,24小时定时开/关功能。 (三)系统噪音最小化。 (四)尽量提高安装高度,融入装饰之中 (五)降低初投资和运行费用 五、主机、末端选型 楼层房间功能面积(m2) 冷指标(W/m2)冷负荷(W)室内机型号 一楼客厅20 220 4400 GMV-R50P/HL 餐厅11 220 2420 GMV-R25P/HL 书房12 200 2400 GMV-R25P/HL 二楼 主卧室19 220 4180 GMV-R50P/HL 次卧11 200 2420 GMV-R25P/HL 合计73 15.82KW 17.5KW 经计算总冷负荷为17.5KW,根据使用功能分配要求,考虑到空调区域的使用功能不同,不具有同 时使用负荷高峰的可能性(如客厅与卧室一般使用会交替)。总负荷峰值按总末端负荷70%计算.故主机负荷为12kw. 制冷机的选型采用珠海格力空调设备有限公司生产的数码多联家用中央空调一台,型号为GMV-R120W/H,总制冷/制热量为12KW/13KW,制冷/制热用电功率为 3.5KW/3.6KW。主机电源为220V、50Hz。脑板的控制下根据负荷变化,自动无级工作保证空调区域温度稳定。 六、空调氟系统及气流组织设计 1.铜管系统 (1)铜管系统: 空调内外机连接采用铜管,闭式循环系统;其管路走向由设计人员、施工人员根据现场具体情况 与业主、装修及各施工单位共同协商确定、详见空调平面布置图。 (2)冷凝水系统 空调冷凝水依就近排入卫生间旁通地漏的原则,其管路布置根据现场具体情况与业主、装修单位共同确定。凝结水管路必须保证顺水流方向的斜度1/100,以保证凝结水能自然流畅。 (3)保温材料 冷(热)水路系统管道保温密闭,采用材料为橡塑福乐斯,外缠扎带。 2.气流组织 气流组织决定房间空调效果,本设计采用侧送下回风方式(详见空调方案设计图)。由施工人员根据现场具体情况与业主、装修单位共同确定,其开口及表面美饰由装修单位处理。 七、施工说明与其它注意事项 (一)在工程施工过程中,施工人员应多协调业主、装修及各工种,及时解决工程问题,做到 气流组织合理,装修美观,空调安装方便,达到业主与设计要求;并保质、保量,按期完成工程内容。 (二)空调铜管系统管道保温连接处不能有缝隙,保温材料无破损。 (三)冷凝水管路必须保证凝结水自流畅通。

相关主题
文本预览
相关文档 最新文档