TABLE OF CONTENTS目录

1.DOCUMENT SUMMARY文件摘要 (5)

2.CODES,STANDARDS&REFERENCES章程,标准和参考文献 (5)

2.1 Specifications规范 (5)

2.2 Drawings图纸 ........................................................................................................................... (5)

2.3 Australian Standards澳大利亚标准........................................................................................... (5)

2.4 Chinese Standards中国标准 (7)

2.5 Other Standards 其他标准.......................................................................................................... (7)

3.GEOTECHNICAL INVESTIGATION岩土工程勘测 (7)

4.MATERIALS OF CONSTRUCTION建筑材料 (8)

4.1 Concrete混凝土 (8)

4.2 Reinforcing Steel钢筋............................................................................................................. . 8

4.3 Steelwork钢骨架 (8)

5.DESIGN LOADS设计荷载 (10)

5.1 Test Loads荷载检测 (10)

5.2 Dead Loads 静荷载 (10)

5.3 Live Loads活荷载 (10)

5.4 Material Loads物质负荷 (12)

5.5 Conveyor Belt Material Loads传送带上的物料荷载 (12)

5.6 Conveyor Belt Tension Loads 传送带拉伸负荷 (12)

5.7 Equipment Loads设备荷载 (13)

5.8 Blocked Chutes and Overfilled Bins封闭的滑道和装得过满的储存箱 (13)

5.9 Thermal Loads热负荷. (13)

5.10 Crane Loads吊车荷载 (14)

5.10.1 Vertical Wheel Loads (Minimum) 垂直轮荷载(最小) (14)

5.10.2 Lateral Forces (Minimum) 侧力(最小) (14)

5.10.3 Longitudinal Forces纵向力 (14)

5.10.4 Crane Support Structure Design起重机支撑结构设计 (14)

5.11 Additional Machinery Dynamic Impact Loads额外的机械动力载荷 (14)

5.12 Wind Loads风力荷载 (15)

5.13 Earthquake Loadings地震荷载 (16)

5.14 Vibrating Loads振动荷载 (17)

5.15 Earth Loads土方荷载 (17)

5.16 Lateral Earth Pressure土方侧压力 (17)

5.17 Surcharge to Retaining Walls挡土墙的超载 (18)

5.18 Hydrostatic Loads流体静力荷载 (18)

5.19 Emergency Loads紧急荷载 (19)

5.20 Special Loads特殊载荷 (19)

5.21 Differential Settlement不均匀沉降 (19)

6.LOAD COMBINATIONS荷载组合 (19)

7.SERVICEABILITY DESIGN LIMITS有用性设计限定 (22)

7.1 General Structures一般构造 (22)

7.2 Crane Structures吊车构造 (22)

7.5 Low Level Conveyor Modules低水平运输单位 (23)

8.FOUNDATION DESIGN地基设计 (23)

8.1 Foundations: Major Structures of Process Plant地基:加工厂的主要构造 (23)

8.1.1 Foundations: Non Settlement-Sensitive Structures of Process Plant地基:加工厂不受结算

影响的构造 (24)

8.1.2 Footing: For the Construction Camp基础:营地建造 (24)

8.2 Stability of Footings地基的稳定性 (24)

9.STRUCTURAL ANALYSIS PROGRAMS构造分析程序 (24)

10.CORROSION CONSIDERATION腐蚀考虑 (25)

10.1 General.总则 (25)

10.2 Surface Treatment表面处理 (26)

11.GENERAL STRUCTURE DESIGN总体结构设计 (26)

11.1 Use of Standard Drawings使用标准图纸 (26)

11.2 Design Functionality 功能设计 (26)

11.3 Design of Steel Bunkers And Bins钢制料仓和料斗的设计 (26)

11.4 Crane and Monorail Structures起重机和轨道结构 (27)

11.5 Conveyor Gantries输送机门架 (27)

11.6 Low Level Conveyor Modules . 低水平输送机模量 (28)

11.7 Piles桩........................................................................................................................................

28

11.8 Building Design建筑物设计 (28)

11.9 Contractor Designed Structural Elements承包商设计的结构部件 (28)

11.10 Structural Steelwork 结构钢架 (29)

11.10.1 Connections 接点 (29)

11.10.2 Access Stairs 交通楼梯 (30)

11.10.3 Access Ladders检修楼梯 (30)

11.10.4 Guardrails护栏 (30)

11.11 Reinforced Concrete 钢筋混凝土 (30)

11.11.1 Slabs at Grade 平板等级 (30)

11.11.2 Shear Keys剪切键 (31)

11.11.3 Concrete Minimum strength and Minimum cover 混凝土的最小强度和极小覆盖 (31)

11.12 Notes on Drawings 图纸上的标示 (31)

12.STRUCTURES AND FOUNDATIONS SUPPORTING DYNAMIC LOADS结构和地基支撑动力载荷 (32)

12.1 Scope范围 (32)

12.2 Design Methodology设计方法 (32)

12.3 Validation of Data资料的有效性 (32)

12.4 Preliminary Structural Design of Dynamically Loaded Steelwork钢结构动力载荷的初始结构设

计 (33)

12.4.1 Over-tuned Structures构造调整过度 (33)

12.4.2 Low Tuned Structures构造调整不足 (33)

12.5 Detailed Dynamic Analysis of Steel Structures钢结构详细动态分析 (33)

12.5.1 Analysis分析 (34)

12.5.2 Bracing in Dynamically Loaded Systems动态负重系统中的支撑 (34)

12.5.3 Connections to Vibrating Structures震动结构的连接 (34)

12.5.4 Structures Supporting Conveyors输送机支撑部件 (35)

12.6 Supports for Vibrating Machines振动机械支架 (35)

12.7 Equipment on Isolated Foundation Blocks抗震地基上的设备 (35)

13.MISCELLANEOUS STRUCTURAL混合结构 (35)

13.3 Footings基础 (36)

13.3.1 Footings and retaining walls date. 基础和挡土墙的日期 (36)

13.3.2 Foundations Requirements基础要求......................................................... (37)

13.4 Vibrating Equipment Foundations震动设备基础..................................................................... (39)

13.4.1 Reciprocating Machinery 摆动式机器 (39)

13.4.2 Centrifugal Machinery 离心机器................................................................................ .. (39)

13.4.3 General总则............................................................................................................... . (40)

13.4.4 Foundations for Vibrating Machines震动机器的基础 (40)

13.5 Anchor Bolts 地脚螺栓 (40)

13.6 Grouting水泥浆 (41)

13.7 Conveyor Structures输送机结构 (41)

13.7.1 Notation标记 (41)

13.7.2 Conveyor Support Structures输送机支撑结构 (41)

13.7.3 Conveyor Gantries 输送机门架 (42)

13.7.4 Conveyor Gantry Connections to Buildings 与建筑物连接的输送机门架 (42)

13.7.5 Conveyor Trestle Design输送机支架设计 (42)

13.7.6 Conveyor Trestle Footing Design输送机支架基础设计 (42)

14.CIVIL WORK土建工程 (42)

14.1 Bulk Earthworks大量土方工程 (42)

14.2 Hard standing Areas & Car Parks 硬路面区域和停车场 (43)

14.3 Concrete Paving铺设混凝土路面 (43)

14.4 Access Roads 便道.................................................................................................................... .43

14.4.1 Intersections交叉 (43)

14.4.2 Unsealed Road Design未封闭道路设计 (44)

14.5 Site Drainage 工地排水 (44)

14.5.1 Hydrology .水文..................................................................................................................... (44)

14.5.2 Drainage排水 ............................................................................................................. (44)

15.CALCULATIONS预算 (45)

1. DOCUMENT SUMMARY文件摘要

THE Civil/Structure Design Criteria shall be used for the design of all civil works, foundations and structures for the Sino Iron Project. The prime purpose of this design criteria is to ensure that the design of civil and structural components produce a safe, economic and functional design.本土建设计标准适用于Sino铁矿项目的所有土建工程,基础和结构。最主要的目的是确保土建和结构部件安装安全,经济,有效的进行。

2. CODES, STANDARDS & REFERENCES章程,标准和参考文献

Government Statutory Requirements. 政府法律规定

Certification of Mining Plant.采矿设备认证

2.1 Specifications规范

The following project specifications shall apply to detailed design.

运用以下工程规范进行具体设计工作

DI-024725 DC-001 Site Information and General Plant现场情况及总平面图

DI-024737 ES-003 Grouting水泥浆

DI-024745 ES-11 Earthworks and Site Preparation土方工程和现场准备

DI-024746 ES-012 Geomembrane Liners土工布内衬

DI-024747 ES-013 Concrete Construction混凝土结构

DI-024748 ES-014 Steelwork Fabrication and Erection钢铁架的制作和拼装

DI-024749 ES-015 Roofing and Wall Cladding with Profiled Steel Sheeting用型钢板覆盖屋顶和墙壁DI-024750 ES-016 Road Pavement & Surfacing道路铺设和平整

2.2 Drawings图纸

Civil/Structural Standard Notes 土建工程标准

Slabs on Grade Standard Details平板等级标准细节

Embedded Steel Standard Details钢骨标准细节

Anchor Bolts Standard Details锚杆准则细节

Miscellaneous Standards Concrete Details混杂标准混凝土细节

Chainwire Mesh Security Fence/Gates Standard Details链条钢丝网安全围栏/门标准细节

Minor Underground Drain Lines Standard Details小型地下排水系准则细节

Beam Connections Standard Details横梁连接标准细节

Vertical Bracing Connections Standard Details垂直支撑连接标准的细节

Miscellaneous Bracing Connections Standard Details混杂支柱连接标准细节

Floor Plate and Grating Standard Details垫板和栅栏标准细节

Steelwork Fire Protection Standard Details Sheet 1钢铁架消防标准细节表1

Vertical Bracing Fire Protection Standard Details 2垂直支架消防标准细节2

Handrail Post Connections Standard Details 扶手栏杆连接标准细节

Staircase Connections Standard Details 楼梯连接标准细节

Ladder and Cage Standard Details梯子,笼子标准细节

Circular Platform Standard Details圆形平台标准细节

Vessel Ladder Standard Details容器梯标准细节

Standard Base Plate Details – Sheet 1 of 2标准底座细节表2-1

Standard Base Plate Details – Sheet 2 of 2标准底座细节表2-2

Beam to Column, Moment End Plate Connections Standard Details梁到柱的节点图

2.3 Australian Standards澳大利亚标准

All work associated with the project shall comply with the relevant Australian Standards. 项

目的所有相关工作都要遵循澳大利亚的有关标准。

The latest edition and amendments of Standards used on this project shall be applicable.用

于此项目的标准为最近版本和修订本。

DI-024766 Civil Structure Design Critera.doc Page 5 of 45

AS ISO 1000 The international system of units (SI system) and its application

国际单位体系(SI 体系)及其应用

AS 1012 Methods of testing of concrete混凝土检验方法

AS 1110 ISO metric precision hexagon bolts and screws ISO 米制精密六角螺拴、螺钉

AS 1111 ISO metric hexagon commercial bolts and screws ISO 米制六角商品螺拴、螺钉

AS 1112 ISO metric hexagon nuts, including thin nuts, slotted nuts and castle nuts

ISO 米制精密六角螺母,包括:薄螺母,沟槽螺母和槽型螺母

AS 1141 Methods of sampling and testing aggregates抽样方法和测试总量

AS 1152 Specification for test sieves试验筛规格

AS 1163 Structural steel hollow sections空心部分结构钢

AS/NZS 1170 Structural design actions结构设计

AS 1214 Hot-dip galvanised coatings on threaded fasteners (ISO metric coarse

thread series)热镀锌涂层的螺纹紧固件(ISO米制粗螺纹系列)

AS 1252 High strength steel bolts with associated nuts and washers for structural

engineering与螺母和垫圈相关的高强螺栓结构工程

AS 1275 Metric screw threads for fasteners米制螺纹扣件

AS 1289 Methods of testing soils for engineering purposes符合工程师要求的土壤检验方法

AS 1365 Tolerances for flat-rolled steel products热轧钢卷产品的偏差

AS 1379 The specification and manufacture of concrete混凝土的规格和生产

AS 1418 Cranes (Including Hoists & Winches) 起重机(包括吊笼及绞车)

AS 1478 Chemical admixtures for concrete混凝土化学外加剂

AS 1538 Cold formed steel structures冷轧型钢结构

AS /NZS 1554 Structural steel welding结构钢焊接

AS 1594 Hot-rolled steel flat products热轧钢板

AS1650 Hot-dipped galvanised coatings on ferrous articles钢铁制品的热镀锌涂层

AS1657 Code for fixed platforms, walkways, stairways and ladders休息平台,通道,楼梯和梯子

的技术规范

AS1755 Conveyors –Design Construction, Installation and Operation –Safety

Requirements输送带-设计施工,安装和操作-安全规定

AS 1761 Helical lock-seam corrugated steel pipes螺旋卷边接缝波纹钢管

AS 1762 Helical lock-seam corrugated steel pipes – Design and installation螺旋卷边接缝波纹钢管

的设计和安装

AS 2159 Piling code打桩技术规范

AS 2041 Buried corrugated metal structures埋地波纹金属结构

AS2312 Guide to the protection of iron & steel against exterior

atmospheric corrosion减少钢铁对外部大气腐蚀的规范

AS 2528 Bolts, studbolts and nuts for flanges and other high and low temperature

applications螺栓,柱螺栓和螺帽法兰及其他高低温应用

AS 2625 Rotating and reciprocating machinery - mechanical vibration Parts 1 to 4

旋转和摆动机械-机械振动第1至第4部分

AS 2758 Aggregate and rock for engineering purposes符合工程师要求的骨料和石块

AS 2870 Residential slabs and footings建筑板和基础

AS 3582 Supplementary cementitious material for use with portland cement波特兰水泥中混合胶凝材料的使用AS 3583 Method of test for supplementary cementitious materials for use with

Portland cement波特兰水泥中混合的胶凝材料的测试方法

AS 3600 Concrete structures混凝土结构

AS 3610 Formwork for concrete混凝土模板

AS/NZS 3678 Structural steel - Hot-rolled plates, floorplates and slabs结构钢-热轧板,波纹板和平板

AS/NZS 3679 Structural steel –ordinary weldable grades结构钢-普通焊等级

AS 3700 SAA masonry code SAA砖石建筑规范

AS 3703 Long-span corrugated steel structures大跨度波纹钢结构

AS 3735 Concrete structures retaining liquids混凝土结构保湿

AS 3750 Paints for steel structures钢结构涂层

AS 3774 Loads on bulk solids containers散装固体容器的载荷

AS 3799 Liquid membrane – forming curving compounds for concrete液态膜-混凝土形成弯化合物

AS 3905 Quality system guidelines质量体系准则

AS 3972 Portland and blended cements波特兰水泥和掺混合料的波特兰水泥

AS4100 Steel structures钢结构

AS4324 Mobile equipment for continuous handling of bulk materials移动设备对散装材料的连续处理

AS 4600 Cold formed steel structures冷弯型钢结构

AS/NZS 4671 Steel reinforcing materials钢骨架原料

2.4 Chinese Standards中国标准

GB 50017-2003 Code for design of steel structures钢结构设计规范

GB/T 1591-94 High strength low alloy structural steels低合金高强度结构钢

GB 50010-2002 Code for design of concrete structures混凝土结构设计规范

GB1499 Hot rolled ribbed steel bars for the reinforcement of concrete钢筋混凝土用带肋钢筋

GB13013 Hot rolled plain steel bars for the reinforcement of concrete钢筋混凝土用热轧光圆钢筋

GB13014 Remained heat treatment ribbed steel bars forthe reinforcement of concrete钢筋混凝土用余热处理钢筋

JGJ19 Prestressed Concrete with Cold Drawn Wire Design and Construction冷拔钢丝预应力混凝土构件设计与施工规程

JGJ/T114 Technical Specification for Concrete Structures Reinforced with Welded Steel

Fabric钢筋焊接网混凝土结构技术规程

GB 50018-2002 Technical code of cold-formed thin-wall steel structures冷弯薄壁型钢结构技术规范

2.5 Other Standards其他标准

CP 2012 British Standards Institute - Code of practice for

Foundations for Machinery英国标准协会-机械设备基础原理应用准则VDI 2056 Verein Deutscher Ingenieure –Criteria for assessing

mechanical vibrations of machines德国工程师协会――设备机械振动评估标准BHP Publication ‘Hot Roll ed and Structural Steel Prod ucts’ bhp

出版:带肋刚和结构刚生产

Australian Reinforced Concrete Design Handbook to AS 3600

澳大利亚的as3600钢筋混凝土设计手册

Australian Institute of Steel Construction: Design Capacity Tables For Structural Steel澳大利亚的钢结构协会:钢结构设计能力表

3. GEOTECHNICAL INVESTIGATION岩土工程勘测

A geotechnical investigation shall be undertaken to establish allowable bearing pressures before

commencement of final design. The foundation design shall be based on the Geotechnical Report (to be prepared) by Golder Associates Pty Ltd Consultants.设计完成之前,要进行岩土勘测确定容许承载压力。基础设计应该根据Golder Associates Pty Ltd提供的岩土报告开展。

Designers shall be responsible in ensuring that they make themselves familiar with all geotechnical information prior to commencing the design of foundations, retaining walls and buried structures like vaults and train un-loaders. They shall ensure that they obtain the latest reports before commencing design work. Any additional information when required should be obtained by the Lead Civil/ Structural Engineer.设计师有责任确保自己在地基,挡土墙,地下室和桥式卸车机等掩埋装置的设计工作开始之前熟悉所有的岩土信息。他们要确保开始设计工作之前获得的是最新的报告。土建/结构工程师要获取所需的任何补充说明。

Footing design for this project shall be based on allowable bearing pressures recommended by the Geotechnical Report.本项目的地基基础设计要根据岩土报告中推荐的容许支承压力来进行。

For load combinations, including seismic loadings, it shall be permissible to increase the allowable bearing capacity under footings by 50%. This recognises the transient nature of this type of loading.

For dynamic machines such as primary crushers and grinding mills, the allowable bearing pressures specified shall not be exceeded with the dynamic component of the applied load included. Refer to Section 14.5 for recommendations for foundations for vibrating machines.荷载组合包括地震荷载,要能够增加地下容许支承力的50%。这种类型的荷载是短暂的。

指定的容许支承力不能超过动力机械,如初步粉碎机和磨碎机的动态组件的使用负荷。参考14.5节对振荡机械基础的介绍。

For ultimate design, a Factor of Safety of 3, and a Capacity Reduction Factor of

0.45 shall be adopted, and the value above also need to be confirmed after the

MATERIALS OF CONSTRUCTION

The following standard materials shall be used on the project, non-Australian supply shall be approved equivalent or better.本项目应使用以下规格标准的材料,非澳大利亚供应的材料要确保与其相当或是更好的。

All characteristic compressive strength of concrete should be in accordance with AS Standards.所有混凝土特征耐压强度要符合澳方标准。

The strength of fabricated sections shall be established using mechanical tensile testing in according with AS3679.2 sections 8 and 9, test certificates shall be supplied prior to commencement of fabrication.制备的部件的强度要根据AS3679.2 第

8 ,9节的规定使用力学拉伸测试来确定。开始制备之前要获取此时结果。

4.1 Concrete混凝土

All concrete structures shall be designed in accordance with the requirements of AS 3600 and the relevant standards referred to therein.所有的混凝土结构的设计都要符合AS3600和其中的相关标准的要求。

Concrete characteristic strength (f’c) for the purposes of design shall be as follows:设计的混凝土的特征强度如下:

Blinding Concrete细石混凝土15MPa

Plain Mass Concrete素混凝土20MPa

Reinforced Concrete钢筋混凝土32MPa

Note: The concrete characteristic strength specified above shall be in accordance with AS 3600 and not GB 50010-2002. 注意:以上混凝土特征强度是根据AS3600的规定来指定

的而不是GB 50010-2002。

For all concrete work, except foundations greater than 1,000mm thick use cement type GP.除超过1000mm厚的地基外,其他的混凝土操作都要使用GP型号的水泥。

For footings greater than 1,000mm thick use low heat blended slag cement in accordance with the General Specification for Concrete DI-024747 ES-013 Concrete Construction对于厚度大于

1000mm的地脚要根据混凝土一般规格DI-024747 ES-013混凝土结构的规定使用低热矿渣水泥4.2 Reinforcing Steel钢筋

The following parameters shall be used for reinforcement design:钢筋设计要使用以下参数

AS Reinforcing Steel澳大利亚钢筋

bars 6mm & 10mm diameter hot rolled plain round bars grade R250N;直径为6mm & 10mm

的热轧光圆钢条,型号为R250N

bars 12mm diameter and greater hot rolled ribbed grade D500N;直径为12mm的热轧

带肋钢条,型号为D500N

cold drawn and ribbed wire grade R500L AND D500L respectively; and冷拔带肋钢丝,型号

分别为R500L 和D500L

welded wire fabric grade D500L.焊接钢丝网型号为D500L

Chinese Reinforcing Steel中国钢筋

bars 6mm & 10mm diameter hot rolled plain round bars grade HPB235; 直径为6mm &

10mm的热轧光圆钢条,型号为HPB235

bars 12mm diameter and greater hot rolled ribbed grade HRB335 or HRB400; 直径为

12mm的热轧带肋钢条,型号为HRB335 或者HRB400

cold drawn and ribbed wire grade HPB235; and冷拔带肋钢丝,型号为HPB235

welded wire fabric grade HRB400. 焊接钢丝网,型号为HRB400

Note: Engineer shall use design strength of reinforcing steel according to GB 50010-2002 Code to design of concrete structures if select Chinese Reinforcing Steel.

注意: 如果选用中国钢筋,工程师是应该根据GB 50010-2002法规使用钢筋的设计强度来设计混

凝土结构。

4.3

5. DESIGN LOADS设计荷载

5.1 Test Loads荷载检测

Test loads for tanks, equipment and piping etc shall be based on water testing.油罐,设备,管道等的荷载测试要用试水试验检测。

5.2 Dead Loads静荷载

Dead loads shall be calculated in accordance with AS 1170 or taken from Vendor data as applicable. References to the source of dead loads associated with mechanical, electrical and vendor supplied equipment that have been incorporated into the structural design shall be documented in the calculations.静荷载要根据AS1170来计算或者从Vendor数据库中提取。与静荷载计算有关的已编入结构设计的机械的,电力的以及由承包商提供的设备要备有文件说明。

Generally, the following loads shall be considered dead loads:总的来说,一下荷载应该算作静荷载 The self weight of buildings, structures, bins, chutes, tanks, foundations and other structural elements.建筑物,房屋,仓库,滑槽,油罐,地基和其他建筑装备的自重

All fixings including floor decking, cladding and insulation materials permanently attached to the structure.包括地板装饰,包层,和隔热材料等固定在建筑物上的装备。

Dead material in bins, chutes and rock boxes which will be retained under normal operation.储存性,滑槽和岩石箱内面,在正常工作状态下存在的枯枝落叶。

Additional dead load allowance should be applied as follows:附加静荷载量按如下所诉应用

Additional 0.6 kPa dead loading to cover for all floorplate, floorgrating, handrails and kickplates.所有的地板,地板光栅,栏杆和踢板算作0.6 kPa的附加荷载

0.2 kPa to 0.5 kPa dead loading for lighting and utility piping along all roofs所有顶部的电线和管线

算作0.2 kPa ~ 0.5 kPa

A minimum services allowance of 1.0 kPa for all floors unless assessed as greater

by the Structural Engineer.所有的地板的最小附加荷载为1.0 kPa,除非结构工程师有更高的估计。

Live and dead loads of major process pipes assuming full loads with maximum density of material as per piping layouts.主要工艺管道的活荷载和静荷载假定为每一最大物料密

度管道布置的全荷载。

Major electrical runs shall be assessed individually.主要的电线线路要分别估算

5.3 Live Loads活荷载

Minimum floor live loads shall be in accordance with AS 1170 or as follows:地板的最小活荷载按照

AS1170界定,或者按照如下规定界定

Floors/platforms: 5.0 kPa live loading on all or 4.5 kN point load whichever is worse.地板/平

台:全部的活荷载为5.0 kPa或者每一处都为4.5 kN点载荷

General Offices/Workrooms (light industrial) without storage -live loading 3 kPa over all or

3.5kN point load whichever is worse.一般的办公室/工作间(轻工业的)不带储存室——全为3

kPa的活荷载或者3.5kN的点荷载。

Roofs: live load (1.8/A +0.12) kPa with min of 0.25 kPa, where A =the plan projection of the surface area of roof supported by the member under analysis in m2For example for a rafter

spanning 8m and spaced at 6m A = 6m x 8m = 48m2

屋顶:活载荷为(1.8/A +0.12) kPa,但不能小于0.25 kPa 其中A =由会员根据分析计算屋顶表面的投影面积,结果使用平方米。例如:一个椽子跨度为8米,间距为6米,则A = 6m x 8m = 48m2

Stairs and landings: 4.0 kPa live loading or 1.4 kN point load楼梯和平台:4.0 kPa活载荷或者

1.4 kN的点载荷

Service Access Walkways: 2.5 kPa or 1.4 kN point load服务走道:2.5 kPa或者1.4 kN的点载

Conveyor Walkways

者2 kN的点载荷或者材料泄漏负荷

Workshop Floors: 5.0 kPa or 30 kN point load over .025m2 车间地板:超过.025m2 的平面上为

5.0 kPa or 30 kN的点荷载

Warehouse Floors: 2.4 kPa for each 1m of storage height (min 5.0 kPa)仓库地板:每一米存储高度为2.4 kPa(但是最小不得低于5.0 kPa)

Electrical Control Rooms: 10kPa or as calculated from detailed layouts配电室:10kPa或者根据详细(具体)布置计算

Crane and Hoist Loads: as per AS 1418 and section 5.10 of this document giving dynamic vertical and horizontal load factors. SWL to be clearly shown on all drawings and painted on crane runway beam or monorail.吊车荷载和提升荷载:按照AS 1418及本文件的5.10章节来确定动态垂直和水平荷载。所有的图纸上,以及起重机行车大梁或者铁轨上都要标明安全工作负荷。 Davit Loads: Vertical impact for 25% of lifted load. Horizontal impact force of 20% of weight of moving equipment ie davit plus attachments吊柱荷载:垂直方向上为起重荷载的25%,水平方向上为移动设备如吊柱加上附件的重量的20%

Pipe Bridge Loads 2.5 kPa or as calculated if greater.管桥荷载:2.5 kPa如果计算出的结果大于2.5 kPa,则以计算所得的结果为准。

Cable Ladder Loads: 2.5 kPa or 1 Kn电缆架荷载:2.5 kPa 或者1 Kn

Laydown areas: 12.0 kPa安装区域:12.0 kPa

Car Dumper Floors ( unless noted otherwise ) : 10.0 kPa翻车机底座(除非另行说明):10.0 kPa

Apron Feeder Slabs: 20.0 kPa板式给料机平板:20.0 kPa

Ground floors accessible to trucks (these loads are not to be used on light grating or thin checker plate trench or pit covers- for trucking areas provide suitable load carrying concrete or steel covers): AUSTROADS T-44靠近载重汽车的地层(光栅,薄地沟挡板,通行载重汽车的混凝土或钢铁坑盖不属于这种荷载)相当于澳大利亚的T-44的荷载。

For short spans less than 5 meters: AUSTROADS W7不超过5米的跨度:AUSTROADS W7 Ground floor areas not accessible to trucks: 20kPa or 9kN over 0.01m2不靠近载重汽车的地层:超过0.01m2为20kPa 或9kN

Engineering workshops and light vehicle workshops: AUSTROADS T-44工程现场和轻型车量车间:AUSTROADS T-44

Electrical switchgear areas: Concentrated moving load and equipment weight of 12kPa电器开关柜:集中移动荷载和设备重量为12kPa

Trench covers not for vehicle traffic 5.0kPa不通行车辆的沟盖:5.0kPa

Each structure shall have a minimum lateral resistance equivalent to 2.5% of (G + 0.6Q) for each level, applied simultaneously at each level for a given direction.

(Section 6.2.2

AS/NZS1170.0, ψc=0.6 TABLE 4.1 AS/NZS 1170.0 )每一个结构都要有相当于(G + 0.6Q)的2.5%的侧阻力,同时作用在每一层指定的方向上(AS/NZS1170.0第6.2.2节,AS/NZS 1170.0表4.1中标明ψc=0.6)

Connections shall be capable of transmitting lateral loads of 5% of the value of (G + 0.6Q) for the connection under consideration. (Section 6.2.3 AS1170.0)节点应该能为其他未连接的节点传导(G + 0.6Q)的5%的横向荷载。

The possibility of machinery parts being placed on the floor and equipment being skidded over the floor during maintenance or installation should be considered.应该充分考虑在维修和安装时放置在地面上的机械部件和在地面上滑动的设备。

Equipment in the unloaded condition may be considered as dead load.卸载下来的装备要算做静荷载。

Area live load reductions are not applicable to the design of floors but may be adopted for the design of columns supporting more than two floors. Maximum reduction shall not exceed 25%, reduction factors shall comply with AS/NZS 1170.1 3.4.2.活荷载减低不适用于地板设计,但可

5.4 Material Loads物质负荷

The ore material properties shall be in accordance with Process Design Criteria (DI-001682) an d Appendix A of AS 1170.1.铁矿石料的特性参照工艺流程设计标准(DI-001682)和AS 1170.1的附录A。

Bins and silos shall be sized to achieve the design volume using the minimum density of the material. Strength calculations shall be based on the maximum ore density and stress ranges for fatigue assessments shall be based on the average density. 使用最小密度的物料建造储存箱和地窖,其大小要达到设计容积。在估计强度是使用最大矿石密度,在估算疲劳范围时要使用平均密度。

Dynamic impact loads from ore streams shall be considered at transfer points for normal operation.

The impact load shall be calculated as follows:

Q(ML) {kN} = mass flow rate {t/s} x impact velocity {m/s}正常操作下,在转换点考虑矿石流的动力冲击负荷。这个冲击负荷按下面的公式计算

负荷(ML) {kN}=单位质量流速{t/s} x冲击速度{m/s}

The design shall account for build up of material through spillage at any material transfer point. The depth of built up material shall be taken as 0.5 m near the source of the spillage or 5 kPa whichever is the greater. This loading shall be applied as a stand alone load and it should not be considered as an addition to the normal live load for the area.设计中要说明任何物料转移点因溢出导致的物料堆积。物料堆积的深度要距离溢出点0.5米,任何大于0.5米的地方按5 kPa计算。这个荷载是独立荷载不能作为该区域正常活荷载的增加。

Chutes shall be considered full for maximum loads. Generally the normal operating material load shall have a value equal to 10% to 30% of the chute full load.应该考虑滑道的最大负荷。一般,正常工作物料负荷应该相当于滑道全负荷的10% 到30%。

5.5 Conveyor Belt Material Loads传送带上的物料荷载

Live loads carried on conveyor shall be determined in accordance with Appendix I of AS4324.1.传送的活荷载根据AS4324.1的附录I来确定。

The operating material loads on a conveyor belt shall be based on the maximum useable cross sectional area and not from the nominal tons/hour (TPH) conveyed., calculated in accordance with Appendix I 2 of AS 4324.1. This calculated value shall be compared to the rated maximum operating load and any marked variations shall be referred to the Project Manager for approval.传送带上的物料的工作荷载要根据可用的交叉截面面积而不是正常传送速度,根据AS 4324.1的附录2来计算。计算结果要和额定的最大工作负荷以及项目经理批准的任何变动比较。

The flooded belt material load shall be calculated using the Conveyor Equipment Manufacturer’s Association cross sectional areas. The CEMA flooded belt material load shall be increased by 50% for the first 10 metres pass any discharge point onto a conveyor to account for stacking of material with a greater material surcharge angle.满载的传送带的荷载要用美国CEMA交叉截面面积计算。CEMA满载传送带荷载在从卸载点转移到传送装置上后的第一个10米增加50%产生更大的超载角度来堆放物料。

5.6 Conveyor Belt Tension Loads传送带拉伸负荷

The design conveyor belt tensions shall be calculated by the Mechanical Engineer responsible for the design. Belt tensions shall be provided for non- operating, operating, starting and peak motor torque load cases. Maximum calculated belt start-up tensions shall be increased by 25% for structural design. The effects due to an increase of the counterweight mass by 20% shall also be considered. The effects of the increased counterweight mass have on the design belt tensions should be provided by the Mechanical Engineer. The peak motor torque tension shall be calculated as 3 times the operating belt tension.传动带拉伸负荷由机械工程师负责计算。分别计算传送带在非运行,运行,开始工作,达到工作顶峰使得马达转矩负荷。机构设计时,要把传送带的最大启动张力增加25%。也要考虑增加20%的平衡物的影响。机械工程师要在传送带张力设计中提供增加平衡物的影响的说明。高峰的转矩负荷要定为皮带工作张力的3倍。

5.7 Equipment Loads设备荷载

Equipment loads including crane loads shall be taken from vendor data. Vehicle For standard vehicle loads, refer to Austroads standards.设备的荷载包括起重机的荷载,应从供货方提供的数据中获得。运输工具的标准荷载参考Austroads标准。

The design documentation for a structure supporting major equipment shall not be issued for construction prior to completing a check against final equipment data received from the Vendor.主要设备的结构设计文件不能在和从供货方处获得的最终设备数据核对前发表。

5.8 Blocked Chutes and Overfilled Bins.封闭的滑道和装得过满的储存箱

The load from blocked chutes and overfilled bins shall be calculated using the maximum expected bulk density of the material and volume of the chute or bin. AS 3774 shall be used for the design of the chute or bin and to determine loads on belts or feeders below.封闭的滑道和装得过满的储存箱的荷载的计算要使用物料的期望容积密度和滑道和储存箱的容积。滑道或储存箱的设计以及其下的皮带或进料器的荷载的确定都要遵照AS3774。

The shear force developed during re-starting of a conveyor or feeder under a blocked chute condition will be transferred to the chute and supporting structure through the shear resistance of the material in the chute. The shear force shall be taken as the lesser of:重新启动输送装置或封闭滑道下的进料器时产生的剪切力会通过滑道内的物料的抗剪力转移到滑道和支承结构上。

The force developed by the conveyor or feeder under a motor peak torque condition.由输送装置或进料器在马达最大转距时产生的效力。

The shearing resistance of the material in the bin or chute based on taking the coefficient of friction as equal to tan (internal angle of friction).物料在储存斗或滑道中的抗剪力和容器具有相等的摩擦系数(内摩擦角)

5.9 Thermal Loads.热负荷

Forces caused by expansion or contraction due to changes in temperature shall be

considered. Such forces shall include those caused by:应该考虑因温度变化产生的膨胀和收缩导致的效力。这用的效力包括由以下因素引起的:

a) Partial or complete anchorage of piping or equipment.

管道或设备的部分或全部抛锚

b) Sliding or rolling friction of piping or equipment.管道或

设备的滑动或滚动摩擦

c) Expansion or contraction of the structure.结构的膨胀或收缩

Material surface temperatures when exposed to direct sun shall be as follows:

太阳直射时物料表面的温度规定如下:

Temperature C温度C

For steelwork and concrete surfaces shielded from direct sunlight, the maximum temperature is 50 degrees.避免阳光直射的钢铁架或混凝土表面的最大温度为50度。

Where sliding joints are used for piping or structures, the following coefficients of friction shall be used:使用滑动结头连接管道和设备时,要使用下列摩擦系数:

Teflon on steel聚四氟乙烯和钢铁0.05

Steel on steel钢铁和钢铁0.40

Steel on smooth concrete钢铁和光面混凝土0.55

DI-024766 Civil Structure Design Critera.doc Page 13 of 45

Crane Loads

The following impact factors shall be used when designing crane girders unless greater values are

required by AS1418 Cranes, Hoists & Winches.在设计起重机行车大梁是要使用以下影响因素,除非

AS1418起重机,起重器械和卷扬机中有更高要求。

5.10.1 Vertical Wheel Loads (Minimum)垂直轮荷载(最小)

The maximum static wheel load shall be increased as follows:最大静止轮载荷按以下方法增

for cab operated travelling cranes 25%汽化移动式起重机为25%

for pendant operated cranes 10%悬架式操作起重机为10%

5.10.2 Lateral Forces (Minimum)侧力(最小)

The lateral force on crane runways to allow for the effect of moving crane trolleys shall be

at least 20% of the sum of the weights of the lifted load and of the crane trolley (but

exclusive of other parts of the crane). The force shall be assumed to be applied at the top

of the rails, acting in either direction normal to the runway rails and shall be distributed

with due regard to the lateral stiffness of the structure supporting the rails.考虑了起重机

行车的移动影响的起重机行道上的侧力至少是起重荷载和起重机吊运车的总量的20%(不

考虑起重机的其他部件)。侧力被假定应用于轨道上方,作用于正常行轨的任何方向,应

该分散,注意支承轨道的结构的横向刚性。

5.10.3 Longitudinal Forces纵向力

The longitudinal force shall be taken as at least 10% of the maximum wheel loads of the

crane applied at the top of the rail.纵向里至少为起重机轨道上的最大轮荷载的10%。

5.10.4 Crane Support Structure Design起重机支撑结构设计

Either or both lateral and longitudinal forces shall be assumed to act in conjunction with the vertical loads when designing crane runway girders and supports.在设计起重机行

车大梁和支承设备时,一边或者两边的纵向力应该假设在作用于垂直载荷的连接。

Fatigue in the design of crane runway girders and connections shall be considered.

在设计起重机行车大梁和节点时要考虑它们的疲劳。

C ontinuous crane girders shall be used whenever possible.尽可能多的使用起重机连续吊车梁。

Where more than one crane can occupy the same runway, two fully loaded cranes

shall be considered, but for the computation of stresses caused by vertical loads,

factored impact loads shall be applied to only one of the two cranes.当同一轨道上

不止一辆起重机时,要考虑两辆满载的起重机,但是在估算垂直荷载和冲击负荷产

生的压力时就只能考虑一辆起重机。

Splices in continuous crane runway girders shall be made not closer to a column than 1/10 span. Splices shall be designed for the maximum bending moment and shear at

the section, but not less than 1/2 the capacity of the crane girder. Field splices of

girders shall be made with high strength 8.8/TF bolts or welds.连续起重机行车大梁的连

头于圆柱间的间距不能小于1/10跨度。结头要符合最大的弯矩和截面切割,但是不能小

于起重机行车大梁支承力的1/2。

Crane girder lateral strength shall be computed by using that portion of the member

above the neutral axis.起重机行车大梁的抗侧强度要用中性轴上的部分构件来计算。

Crane bumpers shall be designed for 1/2 the rated bridge speed and allowable

plunger travel as specified by the manufacturer. Plunger travel shall be 50mm or

greater.起重机减震器的速度应设计为车桥的额定速率的1/2,并且活塞的运作要根

据制造商的说明来进行。活塞有效作用长度应大于等于50mm.

5.11 Additional Machinery Dynamic Impact Loads额外的机械动力载荷

Dynamic loads shall include loads from vibrating machinery, centrifugal machinery and gyratory machinery which result in fluctuating sinusoidal dynamic loads over a range of

frequencies, for the purpose of loading combinations in the table. These fluctuating loads are

also subject to additional requirements as outlined below.动力荷载包括由振动机械,离心机

械,旋转机械为了在工作台上施加荷载组合在一定频率范围内正弦振动产生的动力荷载。

For the purpose of loading combinations in the table dynamic loads also include equivalent static loads from eccentric motor loads and impact forces from screens, crushers, feeders,

chutes, etc. Sources of impact loads may be from such things as rocks dropping at random

onto equipment.为了在工作台上产生荷载组合,动力荷载也包括由电动机偏心负载产生的相

当的静荷载,由过滤器,压碎机,进料机,滑道等产生的冲击力。这种冲击负荷可能是由于

during normal operation and machine operating speed shall be obtained from the equipment

vendors. Estimates of dynamic and static loads for similar equipment may be used for

preliminary design. However, the final design shall be checked using certified values provided

by the equipment vendors.静荷载,设备启动,正常工作是垂直和水平方向上的冲击力,以及机

械的工作速度可以从设备供应商处获取。初步设计时要估算相似设备的动力荷载和静荷载。但

是,最终设计时要与设备供应商提供的标准值对比审定。

Allowance for impact loads shall be as specified by the equipment vendors or as per Section

3.7 of AS 1170.1 as applicable. Also reference should be made to the Operating Procedures

for Impact Loading in determining dynamic factors and load combinations.冲击负荷的偏差要根

据设备供应商提供的数据或者按照AS1170.1第3.7节的相关内容来确定。也可以参照确定动力

因素和荷载组合的冲击荷载的操作程序。

In the absence of other design data, for structures carrying live loads which induce impact, the structural elements shall be designed to support the live load, increased in accordance with the

following.如果没有其他的设计数据,产生活荷载包括冲击荷载的结构部件要设计成能够支承活

荷载,并按以下规定增加:

Multiplying Factor倍加系数

Elevator lift supports升降机支架 2

Reciprocating machinery supports往复机械支护 1.5

Rotating machinery supports旋转机器支护 2

Hangers supporting floors and balconies楼层和阳台托架 1.33

Jib cranes and joists动臂起重机和托梁 1.25

Monorail beams轨道梁架 1.25

5.12 Wind Loads风力荷载

All wind loading is as per the requirements of AS/NZS 1170.2 and BCA with the following criteria unless advised otherwise:除非另有说明,所有风力荷载都要根据AS/NZS 1170.2或BCA的要求按照以下标准确定。

Wind Region –western Australia -Region D 风带-西澳大利亚-D区

The site wind speeds V sit,β=V R M d (M z,cat M s M t)现场风速V sit,β=V R M d (M z,cat M s M t)

Table 2. The

Dynamic Response Factor: Cdyn = 1.0 (unless detailed analysis of a tower or tall building or cantilever roofs show that the natural first mode fundamental frequencies of vibration is less than

1.0Hz) (Section

2.4.1 AS/NZS 1170.2)动态特性系数Cdyn = 1.0(除非对塔楼或高层建筑物或悬臂

屋顶的详细分析显示振动频率小于1.0Hz(AS/NZS 1170.2第2.4.1节)

Aerodynamic Shape Factor:空气动力形态因素

For rectangular buildings -internal and external pressure coefficients as per sections 5.2, 5.3,

5.4 & 5.5 of AS/NZS 1170.2矩形建筑物——按照AS/NZS 1170.2的5.2, 5.3,

5.4 和5.5章节来确定内外部压力系数

For circular bins -external pressure coefficient as per APPENDIX C5 of AS/NZS 1170.2圆形储存箱——按照AS/NZS 1170.2的附录c5来确定外部压力系数

Design Wind Pressure s: p = (0.5 ρa ir) [V des,θ]2Cfig Cdyn设计风压:p = (0.5 ρa ir) [V des,θ]2Cfig Cdyn

Wind loading shall be applied in a minimum of 4 directions for each structure (Section 2.5.2 AS/NZS 1170.2)要在建筑物的至少4个方向上应用风力荷载(AS/NZS 1170.2第2.5.2

章)

For open framed apply a Drag Coefficient to each and every member and shape (use C d=2.0) for rectangular shapes Cd=1.2 for circular shapes). (APPENDIX E Table E4 AS/NZS 1170.2)为开放式矩形外加框的每一个部件和其外形规定一个阻力系数(使用C d=2.0),圆形外加框的Cd=1.2 ,

Alternatively assume that the building is fully enclosed and use C p,e for

Windward and

Leeward faces. (Section 5.4.1 and APPENDIX C AS/NZS 1170.2)假定建筑物是全封闭的,用

C p,e代表迎风面和背风面。

The maximum wind velocity for full plant operation and maintenance is 20 m/s, above which it would be expected that the plant would close down. 20 m/s is known as the maximum operating wind speed. This is a working wind speed.设备运转和维修时的最大风速是20 m/s,风速大于这个数值是机械设备就会熄火。20 m/s是最大运转风速。这是工作风速。

For wind loads on plant structures, conveyor galleries and take-up structures, an acceptable method of assessing wind loads is to assume the structure is fully blocked and to use overall building drag coefficients from AS 1170.对于机械设备,运输器底座,拉线器的风力荷载而言,一种可行的估算方法是假定设备是全封闭式的,使用AS1170规定的综合建筑物阻力系数。

5.13 Earthquake Loadings地震荷载

As per the requirements of AS1170.4-2007summarized by the following: 按照AS1170.4-

2007的要求总结如下:

和EDC II都用第五条

EARTHQUAKE DESIGN CATEGORY I (EDC I): (Section 5.3 AS 1170.4-2007)地震设计类

型(EDC I)(AS 1170.4-2007的5.3节)

Equivalent static forces applied laterally to the centre of mass of the part or component being considered, or to the centers of mass of the levels of

the structure等效静止力应用于从所考虑部分或部件,或者构件水平的边缘到质心(参看

表5.2

(see Figure 5.2), in combination with gravity loads (see combination [G, Eu, ψcQ] in

AS/NZS 1170.0) : Fi = 0.1Wi结合重力荷载(参看AS/NZS 1170.0种的[G, Eu, ψcQ]组合。

Vertical earthquake actions and pounding need not be considered, except where vertical actions apply to parts and components.垂直地震活动和重击是不需要考

虑的,除了垂直活动作用于部件。

EARTHQUAKE DESIGN CATEGORY II (EDC II): (Section 5.4 AS 1170.4-2007)地震设计

类型II (EDC II)(AS 1170.4-2007 5.4节)

use Clause 5.4 for Static analysis用5.4条进行静态分析

Earthquake forces shall be calculated using the equivalent static method, in accordance with Section 6 for structures exceeding 15 m地震力要用等效

的静态分析方法根据第6节针对高于15米的建筑物的规定来计量。

Non-structural parts and components shall be designed in accordance with Section 8 for importance level 2 and 3 structures exceeding 15 m非结构性部件要根据第8节中这

对重要性水平为2和3建筑物高于15米的规定来设计。

5.14 Vibrating Loads振动荷载

See Section 12: Structures and Foundations Supporting Dynamic Loads参看12 节:动力荷载的构成和基本原理

5.15 Earth Loads土方荷载

Earth loads shall be determined from the geotechnical reports available for the project.土方荷载根据本项目的可行性岩土报告来确定。

Design of earth retaining structures shall be in accordance with AS 4678 and the criteria set out

below.对土工防护建筑物的设计要根据AS 4678和下面的标准来进行

5.16 Lateral Earth Pressure土方侧压力

Active pressures shall be used to design flexible structures, such as cantilever retaining walls. Minor retaining walls can be designed using the following parameters for well graded free draining compacted granular material where more detailed information is not available.在设计柔性结构如悬臂挡土墙时要使用积极压力。在没有更多详细信息的情况下,使用下面的分级好了的自由穿流压实颗粒材料的参数来设计较小的挡土墙。

Density密度18Kn/m3

Apparent Cohesion表面凝聚力

At rest pressures shall be used to design rigid structures, such as tied retaining walls and concrete tunnels. The at rest pressure coefficient shall be taken as not less than K0= 0.5. At rest pressure coefficients for major structures shall be determined in conjunction with the Geotechnical Engineer.刚性结构如固定挡土墙和混凝土隧道要使用静止压力来设计。静止压力系数不能小于K0=

0.5。主结构的静止压力系数要由岩土工程师确定。

Lateral earth pressure coefficients on retaining structures subjected to repeated traffic loads shall take into consideration the resulting long term compaction. K in this case shall be developed in conjunction with the Geotechnical Engineer. It shall be taken as K0where no other information is available.应该考虑承担重复运输荷载的防护结构的土方侧压力系数,作为长期压实的结果。这种情况下压力系数K由岩土工程师确定。如果没有更详尽信息就使用K0。

Earth pressures on deep structures are to be determined in conjunction with the Geotechnical Engineer based upon the selected backfill material, compaction methods and proposed construction method.深层结构的土方压力由岩土工程师根据所选回填材料,压实方法和计划建造方法来确定。

5.17 Surcharge to Retaining Walls挡土墙的超载

All retaining walls shall be designed for the actual surcharges applied, or the effect of either (?), (??) or (???) below whichever gives the worst effect for design.挡土墙的设计要考虑实际超载,或者以下(?), (??)或(???)中的任一种会导致最坏效果设计的影响。

(?) Minimum Surcharge最小超载

The minimum surcharge for which a retaining structure shall be designed is 10kPa.挡土墙的最小超载应设计为10kPa。

(??) Normal Road Traffic正常公路交通

Where the edge of a road is within a horizontal distance from the top of a retaining structure equal to one half of its clear height, the wall shall be designed for a road vertical surcharge of 22 kPa in addition to normal earth pressures. (reference: NAASRA Bridge Design Section

2.11 –Earth Pressure. Live load surcharge = 1.2m of soil.)路的边缘距离挡土墙的水平距离为其

净高的一半时,墙要设计能承受22 kPa的道路垂直超载外加上正常土方压力。(参考:NAASRA桥梁设计第2.11节-土方压力。活荷载超载=1.2米土壤

Horizontal loads shall include the induced pressure effects of compaction (refer AS 4678 Appendix J9 and Figure J5). Design drawings associated with pits and retaining walls should note that only 125kg plate compaction equipment shall be used for the back-filling operation (unless the design has allowed for larger induced pressure).水平荷载应包括压实的人工压力作用(参考AS4678附录J9和表J5)。坑道和挡土墙的设计图上要标明只能用125Kg板作为回填操作的压实设备。(除非设计允许更大的人工压力)

(???) Abnormal Axle or Point Load异常的轴荷载或点荷载

Where high axle load vehicles or other items are able to apply point surcharge loads to retaining structures the effect of this load shall be calculated specifically. Guidance on this is given in

“ Reinforced Concrete Design Handbook” 9th Edition by Reynolds, published by the Cement and Concrete Association UK.高轴荷载交通工具或其他车辆能对防护结构施加点超荷载时,这种作用效果要特别计算。有关参考条目已在“钢筋混凝土设计手册”第9版中给出,该手册由Reynolds编写,英国水泥和混凝土协会出版。

5.18 Hydrostatic Loads流体静力负荷

Fluid loads in tanks, sumps etc shall be calculated using the maximum possible liquid density assuming that the containment structure is overtopping. Fluid surge forces, pumping pressures etc shall be considered applicable.油箱,水坑等的流体荷载要用最大液体密度来计算,并且假定容器是越顶结构。流体冲力和水泵抽吸压力等到要尽可能的考虑进去。

Hydrostatic pressure from ground water shall be determined by taking the maximum density of

water. The density of seawater or saline groundwater shall be taken as 1050kg/m3.

Open-topped structures shall be checked for the minimum loads induced by

(a) taking the expected maximum level of water with a limit state factor of 1.5 or

(b); water overtopping the structure with a limit state factor of 1.2.

地下水的流体静压力要根据水的最大密度来确定。海水或含盐地下水为1050kg/m3。检查因下面原因导致的开顶设备的最小荷载:

(a)使用1.5的政府极限参数时的最大预期水位或者

(b)政府极限参数为1.2下的从顶端灌入设备的水

5.19 Emergency Loads紧急荷载

Emergency loads are defined as those which are considered rare, extreme, limited events

and/or where it is considered satisfactory for structural materials to approach their elastic limit.

Examples include impact from the maximum rock size on a bin stiffener and vehicle impact to a

wall or bollard. Generally, these loads shall apply for local design of non-critical members or

where failure of a member will not lead to overall failure of a structure.紧急荷载是那些罕见,稀

少,有限的事件或者结构物质恰好接近他们的弹性极限时产生的。料斗加固物上的最大尺寸石料的

碰撞和交通工具对墙和护柱的冲击都属于这类荷载。一般情况下,这种荷载应用于无标准部件或不

会导致整体结构失稳的坏部件的设计。

An emergency load shall be factored by 1.05 for limit state design.紧急荷载应该用1.05的政府极限参数。

The decision as to whether a load may be considered as an emergency load is to be agreed

with the Lead Civil/Structural Engineer.由土木/结构工程师决定一项荷载是否是紧急荷载。

5.20 Special Loads特殊载荷

Equipment loads, vessel loads, pipe loads, etc shall be obtained from relevant source (such as the Mechanical Engineer, Piping Engineer or Vendor Data) as applicable.

要从相应的地方(比如机械工程师,管道工程师,供货商数据)获得设备荷载,容器荷载,管道荷载等的可行性数据

Bundle pull for exchanger shall be calculated as 150% of bundle weight, where tube bundles shall be pulled from shell and tube equipment. The bundle pull force shall be applied to the fixed-end pedestal of the exchanger. If there are several exchangers on the structure, only the most unfavorable one has to be considered. If a loosening device is provided the force may be reduced

to 30% of bundle weight.在将管束从框架和管道装置上拉下时,交换器的管束拉力应该为管束质量的150%。管束拉力要施加在交换器底座的固定端。如果设备上有多个交换器,只考虑最不利的那个。

如果使用了松动设备,拉力将减少相当于管束质量的30%

5.21 Differential Settlement 不均匀沉降

In the design of all structures, account shall be taken of the possibility of differential settlements occurring within the structure.设计所有的结构都要说明结构内可能出现的差异沉降。

6. LOAD COMBINATIONS荷载组合

The following tables is presented as a guide to the primary loads and load combinations to be considered for strength and stability design of general structures. It is not intended to be a definitive list and the Designer must consider what additional load cases may be applicable. Load factors may also be varied where cases are considered unreasonable but any modifications shall be agreed with the Lead Civil/Structural Engineer.

Refer table on following page:下表显示了一般结构强度和稳定度设计是要考虑的主荷载和荷载组合。但它不是固定的,设计者必须考虑要增加的附加荷载。荷载系数也随着考虑的因素变化而不同,但是任何修改都要经过土木/结构工程师的同意。参考表格在下一页:

Loads -Primary Cases

Loads -Combined Cases

Loads that oppose each other should not be considered simultaneously where it is reasonable to assume one may be absent. i.e. F (EP) and F (H) should be considered independently in the case of buried structures containing fluids.假如充分猜测到有一个不在场时,则彼此相对的载重不应该同时考虑。也就是说在掩埋构造中包含有液体时,F (EP)和F (H)须分开单独考虑。

Thermal and differential settlement loads should be applied to any combination where they may be significant. They may be applied simultaneously. 如果热量和结算差别载重都可能是重要的,则它们可以适用于任何组合,也可以同时适用。

Live load on platforms will be ignored during extreme wind events (i.e. no people are present).

在极端的风荷载中站台的活负载须忽略(也就是没有人在场)

Wind (Vu) and earthquake loads are considered as limit state therefore load factors are unity.

风力(Vu)和地震负载须作为极端状态进行考虑,所以载重因素是一致的。

Load reversal is to be considered. 反向负载也须考虑在内。

Wind (Vu) or earthquake loads must be considered as coming from any direction. 风力(Vu)和地震负载须根据来自的方向进行考虑。

建筑结构抗震设计课后习题答案

武汉理工大学《建筑结构抗震设计》复试 第1章绪论 1、震级和烈度有什么区别和联系? 震级是表示地震大小的一种度量,只跟地震释放能量的多少有关,而烈度则表示某一区域的地表和建筑物受一次地震影响的平均强烈的程度。烈度不仅跟震级有关,同时还跟震源深度、距离震中的远近以及地震波通过的介质条件等多种因素有关。一次地震只有一个震级,但不同的地点有不同的烈度。 2.如何考虑不同类型建筑的抗震设防? 规范将建筑物按其用途分为四类: 甲类(特殊设防类)、乙类(重点设防类)、丙类(标准设防类)、丁类(适度设防类)。 1 )标准设防类,应按本地区抗震设防烈度确定其抗震措施和地震作用,达到在遭遇高于当地抗震设防烈度的预估罕遇地震影响时不致倒塌或发生危及生命安全的严重破坏的抗震设防目标。 2 )重点设防类,应按高于本地区抗震设防烈度一度的要求加强其抗震措施;但抗震设防烈度为9度时应按比9度更高的要求采取抗震措施;地基基础的抗震措施,应符合有关规定。同时,应按本地区抗震设防烈度确定其地震作用。 3 )特殊设防类,应按高于本地区抗震设防烈度提高一度的要求加强其抗震措施;但抗震设防烈度为9度时应按比9度更高的要求采取抗震措施。同时,应按批准的地震安全性评价的结果且高于本地区抗震设防烈度的要求确定其地震作用。 4 )适度设防类,允许比本地区抗震设防烈度的要求适当降低其抗震措施,但抗震设防烈度为6度时不应降低。一般情况下,仍应按本地区抗震设防烈度确定其地震作用。 3.怎样理解小震、中震与大震? 小震就是发生机会较多的地震,50年年限,被超越概率为63.2%; 中震,10%;大震是罕遇的地震,2%。 4、概念设计、抗震计算、构造措施三者之间的关系? 建筑抗震设计包括三个层次:概念设计、抗震计算、构造措施。概念设计在总体上把握抗震设计的基本原则;抗震计算为建筑抗震设计提供定量手段;构造措施则可以在保证结构整体性、加强局部薄弱环节等意义上保证抗震计算结果的有效性。他们是一个不可割裂的整体。 5.试讨论结构延性与结构抗震的内在联系。 延性设计:通过适当控制结构物的刚度与强度,使结构构件在强烈地震时进入非弹性状态后仍具有较大的延性,从而可以通过塑性变形吸收更多地震输入能量,使结构物至少保证至少“坏而不倒”。延性越好,抗震越好.在设计中,可以通过构造措施和耗能手段来增强结构与构件的延性,提高抗震性能。 第2章场地与地基 1、场地土的固有周期和地震动的卓越周期有何区别和联系? 由于地震动的周期成分很多,而仅与场地固有周期T接近的周期成分被较大的放大,因此场地固有周期T也将是地面运动的主要周期,称之为地震动的卓越周期。 2、为什么地基的抗震承载力大于静承载力? 地震作用下只考虑地基土的弹性变形而不考虑永久变形。地震作用仅是附加于原有静荷载上

建筑抗震设计规范

《建筑抗震设计规范》(GB 500011-2001) 《建筑抗震设计规范》 Code for seismic design of buildings GB 50011-2001 主编部门:中华人民共和国建设部 批准部门:中华人民共和国建设部 施行日期:2002年1月1日 关于发布国家标准《建筑抗震设计规范》的通知 建标[2001] 156 号 根据我部《关于印发1997 年工程建设标准制订修订计划的通知》(建标[1997] 108 号)的要求,由建设部会同有关部门共同修订的《建筑抗震设计规范》,经有关部门会审,批准为国家标准,编号为GB50011-2001,自2002 年 1 月1 日起施行。其中,1.0.2、1.0.4、3.1.1、3.1.3 3.3.1、3.3.2、3.4.1、3.5.2、3.7.1、3.8.1、3.9.1、3.9.2、4.1.6、4.1.9、4.2.2、4.3.2、4.4.5、5.1.1、5.1.3、5.1.4、5.1.6、5..5、5.4.1、5.4.2、6.1.2、6.3.3、6.3.8、6.4.3、7.1.2、7.1.5、7.1.8、7..4、7.2.7、7.3.1、7.3.3、7.3.5、7.4.1、7.4.4、7.5.3、7.5.4、8.1.3、8.3.1、8.3.6、8.4.2、8.5.1、10.1.3、10.2.5、10.3.3、12.1.2、12.1.5、12.2.1、12.2.9 为强制性条文,必须严格执行。原《建筑抗震设计规范》GBJ11-89 以及《工程建设国家标准局部修订公告》(第1 号)于2002 年12 月31 日废止。 本标准由建设部负责管理,中国建筑科学研究院负责具体解释工作,建设部标准定额研究所组织中国建筑工业出版社出版发行。 中华人民共和国建设部 2002 年1 月10 日 前言 本规范是根据建设部[1997]建标第108 号文的要求,由中国建筑科学研究院会同有关的设计、勘察、研究和教学单位对《建筑抗震设计规范》GBJ11-89 进行修订而成。 修订过程中,开展了专题研究和部分试验研究,调查总结了近年来国内外大

建筑结构抗震设计基本知识

单元21 建筑结构抗震设计基本知识 学习目标】 1、能够对抗震的基本概念、抗震设防目标和抗震设计的基本要求知识点掌握。 2、能够具备砌体结构房屋和钢筋混凝土框架房屋、框架剪力墙结构、剪力墙结构房屋的抗 震设计要点,从而为识读平法03G101-1混凝土结构施工图中抗震部分打下基础。 【知识点】 构造地震;地震波;震级;烈度;抗震设防;抗震设计的基本要求;钢筋混凝土框架房屋的抗震规定。 【工作任务】 任务1 建筑结构抗震设计基本知识 【教学设计】通过带领学生观看地震灾害照片,让学生对抗震设计的必要性有一个清楚的认识,从而为识读平法03G101-1混凝土结构施工图中抗震部分打下基础,为今后识读结构 施工图、胜任施工员岗位打下基础。 21.1地震基本知识 21.1.1 地震 21.1.1.1构造地震 地震是由于某种原因引起的地面强烈运动(见图21-1)。是一种自然现象,依其成因,可分为三种类型:火山地震、塌陷地震、构造地震。由于火山爆发,地下岩浆迅猛冲出地面时引起的地面运动,称为火山地震。此类地震释放能量小,相对而言,影响围和造成的破坏程度均比较小;

由于石灰岩层地下溶洞或古旧矿坑的大规模崩塌引起的地面震动,称为塌陷地震。此类地震不仅能量小,数量也小,震源极浅,影响围和造成的破坏程度均较小;由于地壳构造运动推挤岩层,使某处地下岩层的薄弱部位突然发生断裂、错动而引起地面运动,称为构造地震;构造地震的破坏性强影响面广,而且频繁发生,约占破坏性地震总量度的95%以上。因此,在建筑抗震设计中,仅限于讨论在构造地震作用下建筑的设防问题(见图21-2)。 地壳深处发生岩层断裂、错动的部位称为震源(见图21-3)。这个部位不是一个点,而是有一定深度和围的体。震源正上方的地面位置叫震中。震中附近地面震动最厉害,也是破坏最严重的地区,称为震中区。地面某处至震中的水平距离称为震中距。把地面上破坏程度相似的点连成的曲线叫做等震线。震中至震源的垂直距离称为震源深度。 根据震源深度不同,可将构造地震分为浅源地震(震源深度不大于60km),中源地震(震源深度60~300km),深源地震(震源深度大于300km)三种。我国发生的绝大部分(地震都属于浅源地震,一般深度为5~40km)。浅源地震造成的危害最大。如大地震的断裂岩层深约1lkm,属于浅源地震,发震构造裂缝带总长8km多,展布围30m,穿过市区东南部,这里就是震中,市铁路两侧47km的区域属于极震区。 21.1.1.2 地震波 当地球的岩层突然断裂时,岩层积累的变形能突然释放,这种地震能量一部分转化为热能,一部分以波的形式向四周传播。这种传播地震能量的波就是地震波。总之,地震波的传播以纵波最快,横波次之,面波最慢。在离震中较远的地方,一般先出现纵波造成房屋的上下颠簸,然

建筑结构抗震设计要点

建筑结构抗震设计的要点分析 提要:本文主要针对建筑结构抗震设计的要点展开了分析,对建筑混凝土框架结构抗震薄弱的部位作了详细的概述,并给出了一系列提高混凝土框架结构抗震性能的措施,以期能为有关方面的需要提供有益的参考借鉴。 近年来,随着我国地震灾害的频繁发生,建筑抗震设计成为了我国建筑结构设计一个新的重要发展方向。但是由于实际操作经验缺乏经验,建筑抗震设计存在着一定的薄弱环节,是需要相关的工作人员给予足够的重视,并采取有效措施提高建筑抗震的性能,以减轻地震灾害对建筑的破坏。 1 混凝土框架结构抗震薄弱部位 1.1 从震害中找出结构薄弱部位 某次地震中,多层混凝土框架教学楼的倒塌,使我们对混凝土框架结构的抗震性能有了进一步的认识。根据地震现场的调查,混凝土框架结构的震害大致如下:6、7度区,底层柱上下端出现斜裂缝,并且柱头比柱脚更厉害。8、9度区,底层柱上下端保护层混凝土脱落,箍筋拉脱,柱心混凝土被压碎,纵筋压成灯笼状。二层柱端及底层梁端也出现不同程度的开裂。在地震中倒塌的框架结构,估计也是底层柱上下端先出现斜裂缝,最后被折断的,只不过整个过程时间很短。不难判断:框架结构薄弱层在底层,底层柱是薄弱构件,底层柱的上下端是最薄弱的部位。震害同时表明:在底层柱中存在某些比较薄弱的柱,地震作用下,这些柱的柱端首先出现斜裂缝,最先形成塑

性铰,使整个结构内力重新分布,导致底层柱逐根被击破,引起连续倒塌。 1.2 从结构分析中确定结构薄弱部位 混凝土框架结构抗震有其特性,与带有剪力墙的其他混凝土结构相比,框架结构侧向刚度小,变形能力强。对抗震有利的是吸收地震总能量少,不利的是抗侧力能力差。框架唯一的竖向构件——柱的侧向刚度比剪力墙的墙肢小得多,比梁板组成的楼层平面刚度也小很多。地震通过地层土晃动框架楼房,刚度大而且质量集中的各楼层就会前后左右来回移动,产生楼层水平地震剪力,这些力由梁传给柱。结构的整体变形主要是各楼层按一定的振型和周期往复侧移。柱本身刚度较小,其竖向变形被动地随各楼层。梁属于楼层的一部分,变形较小。框架的水平地震力和侧移变形主要来自梁板,而抗侧力和侧移主要靠柱。在结构分析中,若忽视板对梁刚度的影响是不现实的,尤其是一起现浇的梁板。相对于梁来说,柱是薄弱构件。因此,“强柱弱梁”便成为框架结构抗震设计的基本原则之一。 框架结构底层柱托起整栋楼房,除了承受整栋楼全部垂直力外,还要承受地震产生的水平力。结构分析显示:底层任何一根柱的轴力、剪力及弯矩都比上层柱大,底层柱比上层柱更容易被破坏。底层柱上下端弯矩最大,成为整个框架结构内力最大的部位,也就是最薄弱的部位。不难理解:为什么地震时,首先出现裂缝的总是底层柱上下端。各楼层抗剪承载力分析结果表明,底层抗剪承载力最小,验证了底层是抗震薄弱层。底层柱既是框架结构抗震的“中流砥柱”,又是薄弱

建筑抗震设计规范

修订说明 本次局部修订系根据住房和城乡建设部《关于印发2014年工程建设标准规范制订修订计划的通知》(建标[2013]169号)的要求,由中国建筑科学研究院会同有关的设计、勘察、研究和教学单位对《建筑抗震设计规范》GB 50011-2010进行局部修订而成。 此次局部修订的主要内容包括两个方面: 1 根据《中国地震动参数区划图》GB18306-2015和《中华人民共和国行政区划简册2015》以及民政部发布2015年行政区划变更公报,修订《建筑抗震设计规范》GB50011-2010附录A“我国主要城镇抗震设防烈度、设计基本地震加速度和设计地震分组”。 2 根据《建筑抗震设计规范》GB50011-2010实施以来各方反馈的意见和建议,对部分条款进行文字性调整。修订过程中广泛征求了各方面的意见,对具体修订内容进行了反复的讨论和修改,与相关标准进行协调,最后经审查定稿。 此次局部修订,共涉及一个附录和10条条文的修改,分别为附录A和第3.4.3条、第3.4.4条、第4.4.1条、第6.4.5条、第7.1.7条、第8.2.7条、第8.2.8条、第9.2.16条、第14.3.1条、第14.3.2条。 本规范条文下划线部分为修改的内容;用黑体字表示的条文为强制性条文,必须严格执行。 本次局部修订的主编单位: 本次局部修订的参编单位: 主要起草人员: 主要审查人员: 3.4.3建筑形体及其构件布置的平面、竖向不规则性,应按下列要求划分:

1 混凝土房屋、钢结构房屋和钢-混凝土混合结构房屋存在表3.4.3-1所列举的某项平面不规则类型或表3.4.3-2所列举的某项竖向不规则类型以及类似的不规则类型,应属于不规则的建筑: 表3.4.3-1 平面不规则的主要类型 表3.4.3-2 竖向不规则的主要类型 2 砌体房屋、单层工业厂房、单层空旷房屋、大跨屋盖建筑和地下建筑的平面和竖向不规则性的划分,应符合本规范有关章节的规定。 3当存在多项不规则或某项不规则超过规定的参考指标较多时,应属于特别不规则的建筑。 3.4.4 建筑形体及其构件布置不规则时,应按下列要求进行地震作用计算和内力调整,并应对薄弱部位采取有效的抗震构造措施: 1平面不规则而竖向规则的建筑,应采用空间结构计算模型,并应符合下列要求: 1)扭转不规则时,应计入扭转影响,且在具有偶然偏心的规定水平力作用下,楼层竖向 两端抗侧力构件最大的弹性水平位移或和层间位移的最大值与平均值的比值不宜大于1.5分别不宜大于楼层两端弹性水平位移和层间位移平均值的1.5 倍,当最大层间位移远小于规范限值时,可适当放宽; 2)凹凸不规则或楼板局部不连续时,应采用符合楼板平面内实际刚度变化的计算模型; 高烈度或不规则程度较大时,宜计入楼板局部变形的影响; 3) 平面不对称且凹凸不规则或局部不连续,可根据实际情况分块计算扭转位移比,对扭 转较大的部位应采用局部的内力增大系数。 2平面规则而竖向不规则的建筑,应采用空间结构计算模型,刚度小的楼层的地震剪力应乘以不小于1.15的增大系数,其薄弱层应按本规范有关规定进行弹塑性变形分析,并应符合下列要求: 1)竖向抗侧力构件不连续时,该构件传递给水平转换构件的地震内力应根据烈度高低和 水平转换构件的类型、受力情况、几何尺寸等,乘以1.25~2.0的增大系数; 2)侧向刚度不规则时,相邻层的侧向刚度比应依据其结构类型符合本规范相关章节的规 定;

我国建筑结构的抗震设计思路

我国建筑结构的抗震设计思路 摘要:本文综述了我国建筑结构的抗震设计方法的发展过程,通过与国外规范 的比较指出我国规范对抗震设计存在的问题。 关键词:结构设计抗震 0 引言 随着建筑结构抗震相关理论研究的不断发展,结构抗震设计思路也经历了一 系列的变化。最初,在未考虑结构弹性动力特征,也无详细的地震作用记录统计 资料的条件下,经验性的取一个地震水平作用(0.1倍自重)用于结构设计。结 构抗震设计思路经历了从弹性到非线性,从基于经验到基于非线性理论,从单纯 保证结构承载能力的“抗”到允许结构屈服,并赋予结构一定的非弹性变形性能力 的“耗”的一系列转变。 1 现代抗震设计思路及关系 在当前抗震理论下形成的现代抗震设计思路,其主要内容是: 1.1 合理选择确定结构屈服水准的地震作用。一般先以一具有统计意义的地面峰值加速度作为该地区地震强弱标志值(即中震的),再以不同的R(地震力降 低系数)得到不同的设计用地面运动加速度(即小震的)来进行结构的强度设计,从而确定了结构的屈服水准。 1.2 制定有效的抗震措施使结构确实具备设计时采用的R所对应的延性能力。其中主要包括内力调整措施(强柱弱梁、强剪弱弯)和抗震构造措施。 现代抗震设计理念是基于对结构非弹性性能的研究上建立起来的,其核心 是关系,主要指在不同滞回规律和地面运动特征下,结构的屈服水准与自振周 期以及最大非弹性动力反应间的关系。其中R为弹塑性反应地震力降低系数,简 称地震力降低系数;而μ为最大非弹性反应位移与屈服位移之比,称为位移延性 系数。 随着对地震作用规律认识的深入,这一规律已被各国规范所接受。在抗震设 计时,对在同一烈度区的同一类结构,可以根据情况取用不同的R,也就是不同 的用于强度设计的地震作用。当R取值较大,即用于设计的地震作用较小时,对 结构的延性要求就越严;反之,当R取值较小,即用于设计的地震作用较大时, 对结构的延性要求就可放松。 2 保证结构延性能力的抗震措施 合理选择了结构的屈服水准和延性要求后,就需要通过抗震措施来保证结构 确实具有所需的延性能力,从而保证结构在中震、大震下实现抗震设防目标。系 统的抗震措施包括以下几个方面内容: 2.1 “强柱弱梁”:人为增大柱相对于梁的抗弯能力,使钢筋混凝土框架在大震下,梁端塑性铰出现较早,在达到最大非线性位移时塑性转动较大;而柱端塑性 铰出现较晚,在达到最大非线性位移时塑性转动较小,甚至根本不出现塑性铰。 从而保证框架具有一个较为稳定的塑性耗能机构和较大的塑性耗能能力。 2.2 “强剪弱弯”:剪切破坏基本上没有延性,一旦某部位发生剪切破坏,该部 位就将彻底退出结构抗震能力,对于柱端的剪切破坏还可能导致结构的局部或整 体倒塌。因此可以人为增大柱端、梁端、节点的组合剪力值,使结构能在大震下 的交替非弹性变形中其任何构件都不会先发生剪切破坏。 2.3 抗震构造措施:通过抗震构造措施来保证形成塑性铰的部位具有足够的塑性变形能力和塑性耗能能力,同时保证结构的整体性。

建筑结构抗震设计复习资料(完美篇)

《建筑结构抗震设计》总复习 (武汉理工配套) 考试的具体题型和形式可能会有变化,但知识点应该均在以下内容中。复习不要死记硬背,而应侧重理解。 第一章:绪论 1.什么是地震动和近场地震动?P3 由地震波传播所引发的地面振动,叫地震动。其中,在震中区附近的地震动称为近场地震动。 2. 什么是地震动的三要素?P3 地震动的峰值(振幅)、频谱和持续时间称作地震动的三要素。 3. 地震按其成因分为哪几类?其中影响最大的是那一类?答: 地震按其成因可分为构造地震、火山地震、陷落地震和诱发地震等几类,其中影响最大的是构造地震。 4. 什么是构造地震、震源、震中、震中距、震源深度?P1 答: 由于地壳构造运动使深部岩石的应变超过容许值,岩层发生断裂、错动而引起的地面震动,这种地震称为构造地震,一般简称地震。地壳深处发生岩层断裂、错动的地方称为震源。震源至地面的距离称为震源深度。一般震源深度小于60km的地震称为浅源地震;60~300km的称为中源地震;大于300km的称为深源地震;我国绝大部分发生的地震属于浅源地震,一般深度为5~40km。震源正上方的地面称为震中,震中邻近地区称为震中区,地面上某点至震中的距离称为震中距。 5. 地震波分哪几类?各引起地面什么方向的振动?P1-3 答: 地震波按其在地壳传播的位置不同可分为体波和面波。在地球内部传播的波称为体波,体波又分为纵波(P波)和横波(S波)。纵波引起地面垂直方向的震动,横波引起地面水平方向震动。在地球表面传播的波称为面波。地震曲线图中,纵波首先到达,横波次之,面波最后到达。分析纵波和横波到达的时间差,可以确定震源的深度。 6. 什么是震级和地震烈度?几级以上是破坏性地震?我国地震烈度表分多少度?P4答: 震级:指一次地震释放能量大小的等级,是地震本身大小的尺度。(1)m=2~4的地震为有感地震。(2)m>5的地震,对建筑物有不同程度的破坏。(3)m>7的地震,称为强烈地震或大地震。 地震烈度:是指某一区域内的地表和各类建筑物遭受一次地震影响的平均强弱程度。 M(地震震级)大于5的地震,对建筑物就要引起不同程度的破坏,统称为破坏性地震。我国地震烈度表分为十二度,用罗马数字表示。 7. 什么是基本烈度和设防烈度?什么是设计基本地震加速度?P5答: 基本烈度是指一个地区在一定时期(我国取50年)内在一般场地条件下按一定概率(我国取10%)可能遭遇到的最大地震烈度。它是一个地区抗震设防依据的地震烈度。 抗震设防烈度是指按国家规定的权限批准作为一个地区抗震设防依据的地震烈度。 设计基本地震加速度指50年设计基准期内超越概率为10%的地震加速度的取值:7度--0.10g(0.15g); 8度--0.20g(0.30g);9度--0.40g 8. 不同震中距的地震对建筑物的影响有什么不同?设计规范如何考虑这种影响? 答:宏观地震烈度相同的两个地区,由于它们与震中的距离远近不同,则震害程度明显不同。处于大震级,远震中距下的高柔结构,其震害远大于同样烈度的中小震级、近震中距的建筑物,且反映谱特性不同。 ?为了区别同样烈度下不同震级和震中距的地震对建筑物的破坏作用,89《规范》将地震影响分为近震和远震两种情况。01《规范》进一步引入了设计基本地震加速度和设计地震分组。

建筑抗震设计规范GB50011-2001

建筑抗震设计规范GB 50011-2001 主编部门:中华人民共和国建设部 批准部门:中华人民共和国建设部 施行日期: 2002年1月1日 关于发布国家标准《建筑抗震设计规范》的通知 建标[2001]156 号 根据我部《关于印发1997 年工程建设标准制订修订计划的通知》(建标[1997]108号)的要求,由建设部会同有关部门共同修订的《建筑抗震设计规范》,经有关部门会审,批准为国家标准,编号为GB50011-2001,自2002 年1 月1 日起施行。其中,1.0.2、1.0.4、3.1.1、3.1.3 3.3.1、3.3.2、3.4.1、3.5.2、3.7.1、3.8.1、3.9.1、3.9.2、4.1.6、4.1.9、4.2.2、4.3.2、4.4.5、5.1.1、5.1.3、5.1.4、5.1.6、5..5、 5.4.1、5.4.2、 6.1.2、6.3.3、6.3.8、6.4.3、 7.1.2、7.1.5、7.1.8、7..4、7.2.7、7.3.1、7.3.3、7.3.5、7.4.1、7.4.4、7.5.3、 7.5.4、 8.1.3、8.3.1、8.3.6、8.4.2、8.5.1、10.1.3、10.2.5、10.3.3、12.1.2、12.1.5、12.2.1、12.2.9为强制性条文,必须严格执行。原《建筑抗震设计规范》GBJ11-89以及《工程建设国家标准局部修订公告》(第1 号)于2002 年12 月31 日废止。 本标准由建设部负责管理,中国建筑科学研究院负责具体解释工作,建设部标准定额研究所组织中国建筑工业出版社出版发行。 中华人民共和国建设部 2001年7月20日 前言 本规范是根据建设部[1997]建标第108 号文的要求,由中国建筑科学研究院会同有关的设计、勘察、研究和教学单位对《建筑抗震设计规范》GBJ11-89 进行修订而成。 修订过程中,开展了专题研究和部分试验研究,调查总结了近年来国内外大地震的经验教训,采纳了地震工程的新科研成果,考虑了我国的经济条件和工程实践,并在全国范围内广泛征求了有关设计、勘察、科研教学单位及抗震管理部门的意见,经反复讨论、修改、充实和试设计,最后经审查定稿。 本次修订后共有13章11个附录,主要修订内容是:调整了建筑的抗震设防分类,提出了按设计基本地震加速度进行抗震设计的要求,将原规范的设计近、远震改为设计特征周期分区;修改了建筑场地划分、液化判别、地震影响系数和扭转效应计算的规定;增补了不规则建筑结构的概念设计、结构抗震分析、楼层地震剪力控制和抗震变形验算的要求;改进了砌体结构、混凝土结构、底部框架房屋的抗震措施;增加了有关发震断裂、桩基、混凝土筒体结构、钢结构房屋、配筋砌块房屋、非结构等抗震设计的内容以及房屋隔震、消能减震设计的规定。还取消了有关单排柱内框架房屋、中型砌块房屋及烟囱、水塔等构筑物的抗震设计规定。 本规范将来可能需要进行局部修订,有关局部修订的信息和条文内容将刊登在《工程建设标准化》杂志上。 本规范以黑体字标志的条文为强制性条文,必须严格执行。 本规范的具体解释由中国建筑科学研究院工程抗震研究所负责。在执行过程中,请各单位结合工程实践,认真总结经验,并将意见和建议寄交北京市北三环东路30号中国建筑科学研究院国家标准《建筑抗震设计规范》管理组(邮编:100013, E-mail:ieecabr@https://www.doczj.com/doc/6f8866648.html,) 本规范的主编单位:中国建筑科学研究院 参加单位:中国地震局工程力学研究所、中国建筑技术研究院、冶金工业部建筑研究总院、建设部建筑设计院、机械工业部设计研究院、 中国轻工国际工程设计院(中国轻工业北京设计院)、北京市建筑设计研究院、上海建筑设计研究院、中南建筑设计院、中国建 筑西北设计研究院、新疆自治区建筑设计研究院、广东省建筑设计研究院、云南省设计

建筑结构抗震设计的研究

建筑结构抗震设计的研究 发表时间:2018-09-18T16:24:34.330Z 来源:《基层建设》2018年第23期作者:张智民 [导读] 摘要:近年来我国地震频发,强烈的地震造成人身伤亡和财产的巨大损伤,所以建筑结构的抗震设计也越来越受人们所关注。 广州地铁集团有限公司 摘要:近年来我国地震频发,强烈的地震造成人身伤亡和财产的巨大损伤,所以建筑结构的抗震设计也越来越受人们所关注。目前,建筑结构抗震设计研究已成为土木工程行业中的研究前沿,随着近年来新型建筑材料不断涌现,在建筑结构设计方法与应用上出现了很多新思路,新方法,并在传统的抗震设计基础上引入了一些新理念,设计了很多刚度大、耗能能力强的结构体系和结构构件。本文就当前一些最新的研究作一些简述。 关键词:建筑结构;新型建筑材料;抗震设计;刚度;耗能 1 引言 建筑结构在地震作用下会产生振动,过大的结构振动现象不仅会影响到结构物的正常使用,还会造成主体结构的破坏、甚至倒塌。有时虽然主体结构未破坏,但由于建筑饰面、装修或非结构配件、室内昂贵仪器、设备的破坏而导致严重的损失。为了保护人类生命财产的安全,减轻地震灾害,全国地震工程科技人员致力于提高建筑抗震能力的研究,已经形成一套较为完整的抗震设计理论。这种抗震设计理论建立在传统抵御地震灾害思想的基础上,主要是通过增加结构本身的强度、刚度或延性的办法,使所设计的建筑达到“小震不坏、中震可修、大震不倒”的抗震设防目的。传统的抗震理论虽然在很多情况下非常有效,但仍然存在较大的局限性[1]。 2 结构抗震设计应注意的问题 2.1选择有利的抗震场地 选择对建筑抗震有利的场地。首先人们常常看到在具有不同工程地质条件的场地上,建筑物在地震中的破坏程度是明显不同的。地震造成建筑物的破坏,除地震动直接引起的结构破坏外,场地条件也是一个重要的原因。因此,应选择对建筑抗震有利的地段,应避开对抗震不利地段,如软弱场地土,易液化土,条件突出的山嘴,高耸孤立的山丘,非岩质陡坡、采空区、河岸和边坡边缘,场地土在平面分布上的成因、岩性、状态明显不均匀等地段;当无法避开时,应采取适当的抗震加强措施,应根据抗震设防类别、地基液化等级,分别采取加强地基和上部结构整体性和刚度、部分消除或全部消除地基液化沉陷的措施。 2.2 抗震的建筑平面和立面布置的选择 (1)建筑形状力求简单规则,平立面不出现凹角的结构。体型简单和规则的建筑,受力性能明确,设计时容易分析结构在地震作用下的实际反应及其内力分析,且结构细部的构造也易于处理。所以这类结构遭遇地震后其震害相对都较轻。反之,建筑体型不规则,平面上曲出凹进,立面上高低错落。易于形成刚度和强度上的突变,引起应力集中或变形集中,也容易形成薄弱环节,往往造成比较严重的危害。 (2)建筑的平、立面刚度和质量分布力求对称。因为不对称结构由于地震作用引起的扭转作用十分明显,在设计时应采取加强措施;周边构件的强度和刚度不对称,布置时应在总体上减小刚度偏心,计算时要充分估计薄弱侧的较大位移及构件的内力和变形。 (3)建筑的质量和刚度变化要均匀。建筑的质量和刚度沿竖向分布往往是不均匀的。 2.3 合理的抗震结构体系选择 合理的抗震结构体系,首先应根据建筑的重要性、设防烈度、房屋高度、场地、地基、材料和施工等因素,结合技术、经济条件综合考虑抗震结构体系。其次,还应该设计多道抗震防线。避免因部分结构或构件破坏而导致整个体系丧失抗震能力或对重力的承载能力。一个抗震结构体系应由若干个延性较好的分体系组成,并由延性较好的结构构件连接起来协同丁作。一般情况下,应优先选择不负担重力荷载的竖向支撑或填充墙,或选用轴压比不太大、延性较好的抗震墙等构件,作为第一道抗震防线的抗侧力构件。框架—抗震墙结构体系中的抗震墙、处于第一道防线,当抗震墙在一定强度的地震作用下遭受可允许的损坏,刚度降低而部分退出工作并吸收相当的地震能量后,框架部分起到第二道防线的作用。这种体系的设计既考虑到抗震墙承受大部分的地震力。对于强栓弱梁型的延性框架。另外,该抗震体系还要具备必要的强度,良好的变形能力和耗能能力以及合理的刚度和强度分布,避免因局部削弱或突变形成薄弱部位。最后,要选择合适的材料,减轻结构自重。 2.4 合理的建筑结构参数设计 结构主要靠延性来抵抗较大地震作用下的非弹性变形,因此,地震作用下,结构的延性与结构的强度具有同等重要的意义。为了使钢筋混凝土结构在地震引起的动力反应过程中表现出必要的延性,就必须使塑性变形更多地集中在比较容易保证良好延性性能或者具有一定延性能力的构件上参数设计是进行地震作用和房屋各构件的地震响应计算,包括各墙柱梁板承载力和变形计算。开始计算前,应根据高层结构的实际工作状况,建立正确的计算模型,根据概念设计做必要的简化计算与处理。 3结构构件的抗震优化设计 在结构延性设计中应保证结构关键构件的延性优于整个结构以保证结构的整体延性性能的要求,因此,在抗震设计中需要对一些延性要求高的部位的结构构件进行优化设计,以保证其良好的延性性能。以下是几种常用的构件的优化设计方案: 3.1框架梁塑性铰外移 传统钢筋混凝土框架梁的塑性铰出现在始于柱面的梁端。将塑性铰从柱面移开一定距离,可以避免梁端钢筋屈服,从而不仅可以避免钢筋屈服后向节点核心区发展,引起粘结破坏,还能改善核心区的性能。如图1所示

建筑结构抗震设计(第三版)习题解答1-5章

第一章的习题答案 1.震级是衡量一次地震强弱程度(即所释放能量的大小)的指标。地震烈 度是衡量一次地震时某地区地面震动强弱程度的尺度。震级大时,烈度就高;但某地区地震烈度同时还受震中距和地质条件的影响。 2.参见教材第10面。 3.大烈度地震是小概率事件,小烈度地震发生概率较高,可根据地震烈度 的超越概率确定小、中、大烈度地震;由统计关系:小震烈度=基本烈度-1.55度;大震烈度=基本烈度+1.00度。 4.概念设计为结构抗震设计提出应注意的基本原则,具有指导性的意义; 抗震计算为结构或构件达到抗震目的提供具体数据和要求;构造措施从结构的整体性、锚固连接等方面保证抗震计算结果的有效性以及弥补部分情况无法进行正确、简洁计算的缺陷。 5.结构延性好意味可容许结构产生一定的弹塑性变形,通过结构一定程度 的弹塑性变形耗散地震能量,从而减小截面尺寸,降低造价;同时可避免产生结构的倒塌。 第二章的习题答案 1.地震波中与土层固有周期相一致或相近的波传至地面时,其振幅被放 大;与土层固有周期相差较大的波传至地面时,其振幅被衰减甚至完全过滤掉了。因此土层固有周期与地震动的卓越周期相近, 2.考虑材料的动力下的承载力大于静力下的承载力;材料在地震下地基承 载力的安全储备可低于一般情况下的安全储备,因此地基的抗震承载力高于静力承载力。 3.土层的地质年代;土体中的粘粒含量;地下水位;上覆非液化土层厚度; 地震的烈度和作用时间。 4.a 中软场地上的建筑物抗震性能比中硬场地上的建筑物抗震性能要差 (建筑物条件均同)。 b. 粉土中粘粒含量百分率愈大,则愈容易液化. c.液化指数越小,地震时地面喷水冒砂现象越轻微。 d.地基的抗震承载力为承受竖向荷载的能力。

建筑抗震设计规范

建筑抗震设计规范(GB50011-2010)学习体会 2010抗震规范已经到货,抽空学习了一下,与去年注册工程师继续教育课时学的送审稿略有改动,以下简要记述认为对自己设计工作影响较多的修改,钢结构、砌体结构等本人接触不多的内 容就不赘述了。 一、第3章新增3.10节建筑抗震性能化设计的内容,3.10.3明确给出了中震(即设防烈度)计算的αmax值(送审稿是放在表 5.1.4-1处的,正式版本不知为何又改到了这里): 6度——0.12;7度(0.10g)——0.23;7度(0.15g)——0.34;8度(0.20g)——0.45;8度(0.30g)——0.68。对于平时设计来说,主要用于超限审查做的中震不屈服或中震弹性设计,一 般的结构计算也没必要做。 二、4.1.6条,将场地类别中的I类细化为I0和I1两个亚类。修订原因是考虑到剪切波速为500-800m/s的场地还不是很坚硬,将此种场地定为I1类,硬质岩石场地定为I0类。相应地,表5.1.4-2提供了这两种场地类别的特征周期值,其中I1类的特征周期值与2001规范中I类场地的周期值相同。 三、5.1.4条: 1. 增加了6度罕遇地震的αmax值。

2. 计算罕遇地震作用时,特征周期应增加0.05s。01规范只是在计算8度、9度的罕遇地震才有此要求,现要求扩大至各种地震烈度。此条对超限审查的罕遇地震弹塑性分析等有影响。四、5.1.6条,修改了地震影响系数曲线。曲线的表达式表面上没有变化,但其中曲线下降段的衰减指数γ、直线下降段的下降斜率调整系数η1及阻尼调整系数η2的公式均有变化。五、5.2.5条,增加了6度地震计算的结构任一楼层的水平地震 剪力要求,01规范只对7-9度有要求。 六、6.1.1条,现浇钢筋混凝土房屋适用的最大高度有所调整。 1. 注4明确表中的框架结构不包括异形柱框架结构,异形柱结 构的适用高度应以异形柱规范为准。 2. 8度地震的适用高度分为0.2g和0.3g两种要求。 3. 框架结构适用高度有所降低。 4. 板柱-剪力墙结构的适用高度增大较多。 七、6.1.2条抗震等级,增加了24m作为抗震等级划分的高度分界。但编委们对条文细节的把握上依然令人失望,如抗震墙结构,H≤24m为四级抗震,H为25-80m为三级抗震,那24.5m应该按几级抗震,这不是又要让俺们和审查的老爷们扯皮吗?搞笑的是框架结构的划分——H≤24m为三级抗震,H为>24m为三级抗震就没有问题,难道结构抗震等级的划分还是一个委员确定一类结构?这种低级错误在02版高规也是俯拾即是,比如长厚比为5-8为短肢剪力墙,≥8以上为一般剪力墙,小于3为柱,长厚比为

关于对建筑结构抗震设计分析84

关于对建筑结构抗震设计分析 摘要:我国是地震多发国,破坏性地震造成建筑结构、桥梁结构的损坏,人员 的伤亡及经济损失都是巨大的。随着社会的不断向前发展,各门学科的交叉发展,使得隔震、消能减震等抗震技术的运用走上一个新的阶段。任何结构所受的载荷 都具有不同程度的动载荷性质,有不少结构主要在振动环境下工作。通过对隔震 装置的动力学分析,发现自振振动在结构的地震反应中经常占有主导地位,不能 够忽略。建筑结构抗震设计中的概念设计是对建筑抗震设计的宏观控制。本文根 据地震的特点,从建筑物的场地选择、平立面形式、结构布置、延性等方面论述 了建筑结构设计中概念设计的内容。 关键词:建筑结构;抗震;设计 一、建筑结构抗震概念设计概述 我国结构计算理论经历了经验估算、容许应力法、破损阶段计算、极限状态 计算,到目前普遍采用的概率极限状态理论等阶段。现行的《建筑结构可靠度设 计统一标准》(GB50068-2001)则采用以概率理论为基础的结构极限状态设计准则,以使建筑结构的设计得以符合技术先进、经济合理、安全适用的原则。概率 极限状态设计法更科学、更合理,但该法在运算过程中还带有一定程度近似,只 能视作近似概率法,并且仅凭极限状态设计也很难估算建筑物的真正承载力。事 实上,建筑物是一个空间结构,各种构件以相当复杂的方式共同工作,并非是脱 离结构体系的单独构件。 地震具有随机性、不确定性和复杂性,要准确预测建筑物所遭遇地震的特性 和参数,目前是很难做到的。而建筑物本身又是一个庞大复杂的系统,在遭受地 震作用后其破坏机理和破坏过程十分复杂。且在结构分析方面,由于未能充分考 虑结构的空间作用、非弹性性质、材料时效、阻尼变化等多种因素,也存在着不 确定性。因此,结构工程抗震问题不能完全依赖“计算设计”解决。应立足于工程 抗震基本理论及长期工程抗震经验总结的工程抗震基本概念,从“概念设计”的角 度着眼于结构的总体地震反应,按照结构的破坏过程,灵活运用抗震设计准则, 全面合理地解决结构设计中的基本问题,既注意总体布置上的大原则,又顾及到 关键部位的细节构造,从根本上提高结构的抗震能力。 二、抗震概念设计的基本原则与要求 1.选择有利场地。 造成建筑物震害的原因是多方面的,场地条件是其中之一。由于场地因素引 起的震害往往特别严重,而且有些情况仅仅依靠工程措施来弥补是很困难的。因此,选择工程场址时,应进行详细勘察,搞清地形、地质情况,挑选对建筑抗震 有利的地段,尽可能避开对建筑抗震不利的地段,任何情况下均不得在抗震危险 地段上建造可能引起人员伤亡或较大经济损失的建筑物。 对建筑抗震有利的地段,一般是指位于开阔平坦地带的坚硬场地土或密实均 匀中硬场地土。建造于这类场地上的建筑一般不会发生由于地基失效导致的震害,从而可从根本上减轻地震对建筑物的影响。对建筑抗震不利的地段,就地形而言,一般是指条状突出的山嘴、孤立的山包和山梁的顶部、高差较大的台地边缘、非 岩质的陡坡、河岸和边坡的边缘;就场地土质而言,一般是指软弱土、易液化土、故河道、断层破碎带、暗埋塘浜沟谷或半挖半填地基等,以及在平面分布上成因、岩性、状态明显不均匀的地段。 2.采用合理的建筑平立面。

建筑结构抗震设计(高起专)

河南工程学院 2017年秋《建筑结构抗震》期末试题 批次专业:2016年春季-建筑工程技术(高起专)课程:建筑结构抗震 设计(高起专)总时长:180分钟 1. ( 单选题 ) 下列哪种不属于地震波的传播方式()(本题 2.5分) A、P波 B、S波 C、L波 D、M波 学生答案: 标准答案:D 解析: 得分:0 2. ( 单选题 ) 罕遇烈度50年的超越概率为(本题2.5分) A、2-3% B、20% C、10% D、5% 学生答案: 标准答案:A 解析:

得分:0 3. ( 单选题 ) 震级相差一级,能量就要相差()倍之多(本题2.5分) A、 2 B、10 C、32 D、100 学生答案: 标准答案:C 解析: 得分:0 4. ( 单选题 ) 下面哪个不属于影响土的液化的因素?()(本题2.5分) A、土中黏粒含量 B、上覆非液化土层厚度和地下水位深度 C、土的密实程度 D、地震烈度和震级 学生答案: 标准答案:D 解析: 得分:0 5. ( 单选题 ) 抗震设计原则不包括:()(本题2.5分)

A、小震不坏 B、中震可修 C、大震不倒 D、强震不倒 学生答案: 标准答案:D 解析: 得分:0 6. ( 单选题 ) 框架结构中布置填充墙后,结构的基本自振周期将(本题2.5分) A、增大 B、减小 C、不变 D、说不清 学生答案: 标准答案:B 解析: 得分:0 7. ( 单选题 ) 钢筋混凝土房屋的抗震等级应根据那些因素查表确定()(本题2.5分) A、抗震设防烈度、结构类型和房屋层数 B、抗震设防烈度、结构类型和房屋高度

C、抗震设防烈度、场地类型和房屋层数 D、抗震设防烈度、场地类型和房屋高度 学生答案: 标准答案:B 解析: 得分:0 8. ( 单选题 ) 下列哪项不属于地震动的三要素(本题2.5分) A、震幅 B、震级 C、频谱 D、持时 学生答案: 标准答案:B 解析: 得分:0 9. ( 单选题 ) 体波可以在地球内部和外部传播。()(本题2.5分) A、 B、 学生答案: 标准答案:B 解析: 得分:0 10. ( 单选题 ) 钢筋混凝土构造柱可以先浇柱,后砌墙。()(本题2.5分)

钢筋混凝土结构抗震设计规范

钢筋混凝土结构抗震设计规范 导读:我根据大家的需要整理了一份关于《钢筋混凝土结构抗震设计规范》的内容,具体内容:钢筋混凝土结构具有坚固、耐用、防火性好等优点,在全世界范围内都得到了认可,那么你想知道是什么吗?以下是我为你整理推荐,希望你喜欢。1 结构设计地震力的确定1.1... 钢筋混凝土结构具有坚固、耐用、防火性好等优点,在全世界范围内都得到了认可,那么你想知道是什么吗?以下是我为你整理推荐,希望你喜欢。 1 结构设计地震力的确定 1.1 低地震力取值的可行性 到二十世纪八十年代,各国设计规范都承认这样一个事实,就是在地震作用下,结构在真正失效前,有一个较大的塑性变形能力(结构延性),即结构在一个较小的地震下可能达到或者接近屈服状态;而在较大的地震下,结构的若干部位将陆续进入屈服后的非弹性变形状态,并且随着地震力的增大,结构中进入弹塑性变形的部位增多,先进入屈服的部位弹塑性变形也增大。结构通过这种变形耗散较多的地震传来的能量,将其转换成热能。 对于"设计地震力-延性"联合法则,我们可以从地震力和结构相互关系上进行理解:一方面设计地震力低的结构,通过更大的非弹性变形,耗散掉更多的地震能量;另一方面结构非弹性变形越大,刚度降低越严重,阻尼增大,周期比高设计地震力的结构增长越多,结构受到的总地震力也降

低也越多。这就使得我们在设计过程中,在不降低构件竖向承载力、保证结构延性的前提下,可以取用一个小于设防烈度地震反应水准,作为设计中取用的地震作用。反过来讲,若采用的设计地震力越低,结构屈服部位在屈服后,水平和竖向承载力不降低的前提下需要达到的非弹性变形就越大,也就需要结构有更好的延性性能。 这样,我们就需要解决如下两个问题: A、如何在设防烈度地震作用与设计地震力取值之间建立恰当的联系; B、如何在设计地震力与所要求的结构延性建立对应关系。 对于问题A,以N.M.Newmark为代表的众多学者认为,将设防烈度地震加速度通过地震力降低系数R(中,美等国)或结构性能系数q(欧共体,新西兰等)折减为结构设计加速度,相当于赋予结构一个较小的屈服承载力,结构在竖向承载力不降低的情况下,通过屈服后的非弹性变形来经受更大的地震,实现"大震不倒"的目标。因而,采用低设计地震力的关键在于保证结构及构件在大震下达到所需的延性。对于地震力降低系数R或结构性能系数q,各国设计规范存在略为不同的处理手法,不过总体而言,R或q 均为设防烈度地震作用与结构截面设计所用的地震作用的比值。 R或q越大,则要求结构达到的延性能力越大,R或q越小,则结构需要达到的延性能力越小。这样均能实现"大震不倒"。 对于问题B,国外一般有如下三种设计方案: (1)较高地震力——较低延性方案; (2)中等地震力——中等延性方案; (3)较低地震力——较高延性方案。

(完整版)建筑结构抗震设计整理

《建筑结构抗震设计》期末考试复习题 一、名词解释 (1)地震波:地震引起的振动以波的形式从震源向各个方向传播并释放能量; (2)地震震级:表示地震本身大小的尺度,是按一次地震本身强弱程度而定的等级; (3)地震烈度:表示地震时一定地点地面振动强弱程度的尺度; (4)震中:震源在地表的投影; (5)震中距:地面某处至震中的水平距离; (6)震源:发生地震的地方; (7)震源深度:震源至地面的垂直距离; (8)极震区:震中附近的地面振动最剧烈,也是破坏最严重的地区; (9)等震线:地面上破坏程度相同或相近的点连成的曲线; (10)建筑场地:建造建筑物的地方,大体相当于一个厂区、居民小区或自然村; (11)沙土液化:处于地下水位以下的饱和砂土和粉土在地震时有变密的趋势,使孔隙水的压 力急剧上升,造成土颗粒局部或全部将处于悬浮状态,形成了犹如“液化”的现象,即称为 场地土达到液化状态; (12)结构的地震反应:地震引起的结构运动; (13)结构的地震作用效应:由地震动引起的结构瞬时内力、应力应变、位移变形及运动加速 度、速度等;(14)地震系数:地面运动最大加速度与重力加速度的比值; (15)动力系数:单质点体系最大绝对加速度与地面运动最大加速度的比值; (16)地震影响系数:地震系数与动力系数的乘积; (17)振型分解法:以结构的各阶振型为广义坐标分别求出对应的结构地震反应,然后将对应 于各阶振型的结构反应相组合,以确定结构地震内力和变形的方法,又称振型叠加法; (18)基本烈度:在设计基准期(我国取50年)内在一般场地条件下,可能遭遇超越概率(10%)的地震烈度。 (19)设防烈度:按国家规定权限批准的作为一个地区抗震设防依据的地震烈度。 (20)罕遇烈度:50年期限内相应的超越概率2%~3%,即大震烈度的地震。 (21)设防烈度 (22)多道抗震防线:一个抗震结构体系,有若干个延性较好的分体系组成,并由延性较好的 结构构件连接起来协同作用; (24)鞭梢效应; (25)楼层屈服强度系数; (26)重力荷载代表值:建筑抗震设计用的重力性质的荷载,为结构构件的永久荷载(包括自 重)标准值和各种竖向可变荷载组合值之和; (27)等效总重力荷载代表值:单质点时为总重力荷载代表值,多质点时为总重力荷载代表值 的85%; (28)轴压比:名义轴向应力与混凝土抗压强度之比; (29)强柱弱梁:使框架结构塑性铰出现在梁端的设计要求;(30)非结构部件:指在结构分析 中不考虑承受重力荷载以及风、地震等侧向力的部件 二、简答题 1.抗震设防的目标是什么?实现此目标的设计方法是什么? 答:目标是对建筑结构应具有的抗震安全性能的总要求。我国《抗震规范》提出了三水准的

相关主题
文本预览
相关文档 最新文档