当前位置:文档之家› 浅谈低压无功补偿的选择

浅谈低压无功补偿的选择

浅谈低压无功补偿的选择
浅谈低压无功补偿的选择

浅谈低压无功补偿的选择

浅谈低压无功补偿的选择

摘要:电力系统大多为感性负载,会产生无功功率。无功功率越大,要保持有功功率不变,势必提高电流而增加线路损耗。在电力系统运行中,为减少能量损耗,提高供电设备利用率,合理的选择利用低压无功补偿装置,可以取得很好的效果。

关键字:无功补偿;低压

Abstract:Power system is mostly inductive load, it will produce reactive power. When reactive power is greater, want to keep the active power,we will increase the current .It will increasing the circuit power loss. In order to reduce energy loss, improve the utilization rate of power supply equipment, reasonable choice a using low voltage reactive power compensation device, it can be achieved very good results.

Key words: reactive power compensation;low voltage

中图分类号:TM642+.2文献标识码:A文章编号:

2095-2104(2013)

电力系统的负载大多为感性负载,会产生无功功率,使得负载电流相位滞后于电压,相角差越大,无功功率需求越大,要供给固定的有功功率,势必提高电流而增加线路损耗。同时,电力网络中的用电设备消耗的无功功率也必须从网络中某个地方获得,如这些无功功率都要由发电机提供并经过长距离传送是不合理的,通常也是不可能的。因此在配电系统里几乎都使用电容器来补偿负载所需的无功功率,来改善功率因数。在电力系统运行中,为减少能量损耗,提高供电设备利用率,使用无功功率补偿装置,可以取得很好的效果。合理的选择补偿装置,可以做到最大限度的减少网络的损耗,使电网质量提高。反之,如选择或使用不当,可能造成供电系统,电压波动,谐波增大等诸多因素。通常无功功率补偿装置会选择装在低压侧或是高压侧,这里仅对低压无功补偿的选择进行探讨。

1、低压无功补偿的一般方式及原理

低压无功补偿一般可分为两种:静态补偿及动态补偿。

1.1 静态补偿

"静态"补偿是依靠接触器的动作来投切电容,使用的是具有抑制电容的涌流作用专门用于投切电容的接触器。"静态"补偿的目的在于防止接触器过于频繁的动作时造成电容器的损坏,更重要的是防备电容不停的投切导致供电系统振荡。当使用电动机、电焊机等负载电网的负荷呈感性时,电网的电流滞带后电压一个角度,当负荷呈容性时,电网的电流超前于电压的一个角度。功率因数超前或滞后就是指电流与电压的相位关系。通过补偿装置的控制器检测供电系统的物理量,来决定电容器的投切,这个物理量可以是功率因数或无功电流或无功功率。

以功率因数型为例。如要求0.950.98,即呈容性载荷时,那么控制器就逐一切除电容器组。要遵循的原则就是:先投先切。如果把延时时间整定为100s,而这套补偿装置有六路电容器组,那么全部投入的时间就为10分钟,切除也如此。在这段时间内无功损失补偿只能是逐步到位。如果将延时时间整定的很短,或没有设定延时时间,就可能会出现当控制器监测到cosΦ〈0.95,迅速将电容器组逐一投入,而在投入期间,此时电网可能已是容性负载即过补偿了,控制器则控制电容器组逐一切除,形成振荡,导致系统崩溃。为防止系统崩溃,要在保证系统安全的情况下,再考虑补偿效果。

1.2 动态补偿

"动态"补偿是半导体电力器件与数字技术综合的技术结晶,实际就是一套快速随动系统,控制器一般能在半个周波至1个周波内完成采样、计算,在2个周期到来时,控制器已经发出控制信号了。通过脉冲信号使晶闸管导通,投切电容器组大约20-30毫秒内就完成一个全部动作,这种控制方式是机械动作的接触器类无法实现的。动态补偿方式作为新一代的补偿装置有着广泛的应用前景。

动态补偿的线路方式

(1)LC串接法原理如图1所示

这种方式采用电感与电容的串联接法,调节电抗以达到补偿无

功损耗的目的。从原理上分析,这种方式响应速度快,闭环使用时,可做到无差调节,使无功损耗降为零。从元件的选择上来说,根据补偿量选择1组电容器即可,不需要再分成多路。既然有这么多的优点,应该是非常理想的补偿装置了。但由于要求选用的电感量值大,要在很大的动态范围内调节,所以体积也相对较大,价格也要高一些,再加一些技术的原因,这项技术到目前来说还没有被广泛采用或使用者很少。

(2)采用电力半导体器件作为电容器组的投切开关。作为补偿装置所采用的半导体器件一般都采用晶闸管,其优点是选材方便,电路成熟又很经济。其不足之处是元件本身不能快速关断,在意外情况下容易烧毁,所以保护措施要完善。当解决了保护问题,作为电容器组投切开关应该是较理想的器件。动态补偿的补偿效果还要看控制器是否有较高的性能及参数。很重要的一项就是要求控制器要有良好的动态响应时间,准确的投切功率,还要有较高的自识别能力,这样才能达到最佳的补偿效果。

简单的说动态补偿,就是实时跟踪负荷的功率因数的变化,极快的跟踪补偿,反映速度在1/20个周波之内。现在的产品,理论上都不是动态补偿,而是快速补偿。动态补偿和快速补偿,必须采用晶闸管等大功率电子器件,不能采用接触器和复合开关等。

2 低压无功补偿的选择

2.1控制器的选择

在低压无功补偿柜的制造中控制器的选择很重要。无功功率补偿控制器有三种采样方式,功率因数型、无功功率型、无功电流型。选择那一种物理控制方式实际上就是对无功功率补偿控制器的选择。控制器是无功补偿装置的指挥系统,采样、运算、发出投切信号,参数设定、测量、元件保护等功能均由补偿控制器完成。就国内的总体状况,由于市场的需求量很大,生产厂家也很多,其性能及内在质量差异很大,在选用时需认真对待。在选用时需要注意的是国内生产的控制器其名称均为"XXX无功功率补偿控制器",名称里出现的"无功功率"的含义并不是这台控制器的采样物理量。采样物理量取决于产品的型号,而不是产品的名称。我们现在一般选用无功功率和功率因数

复合控制的自动补偿控制器。这种控制器操作简单可自动也可手动。还可调节投切滞后时间。反应较快对于静态和动态无功补偿都可以使用。

2.2电容器的选择

电容器在原理上相当于产生容性无功电流的发电机。将它连接到需要无功的补偿装置或设备上,变压器和输出线的负荷降低,从而输出有功能力增加。在输出一定有功功率的情况下,供电系统的损耗降低。比较起来电容器是减轻变压器、供电系统和工业配电负荷的最简便、最经济的方法。以前,低压侧的无功补偿,采用油浸纸介电容器。这种电容器体积大、损耗高、成本高,而且爆炸、鼓肚、漏油现象严重,已远远不能适应电网发展的要求。近些年来自愈式低压并联电力电容器已取代油浸纸介电容器。自愈式低压并联电力电容器是以电工级的聚丙烯膜为介质,单面蒸镀一层金属膜为极板,采用无感卷绕法形成元件,在其两端面喷涂金属,将极板引出作为电极。元件是电容器的主体,也是其关键。根据容量的要求,将一定数量的元件用导线组合起来,经过绝缘处理,加装防爆装置后,置于一个壳体中,再经过一定的工艺加工就成为单台的电容器。电容器应当有放电器件,当电容器从电源脱开后,它能在规定的时间内把电容器上剩余电压降低到零,以保证维护人员的人身安全和防止重复投切时电压叠加造成电容器过电压。自愈式低压并联电力电容器尽管有自愈功能,比较安全可靠,但仍存在自愈失败的情况,造成元件绝缘水平降低,甚至短接,产生鼓肚、爆裂等个别情况。为解决这一现象,不同厂家采用了不同的防爆措施。如压差防爆装置,安全膜,温度电流型保险等。电容器的阻抗是和频率成反比。随着频率的增高,损耗也增大。对于电路中的谐波和涌流要采取措施加以限制。电容器总是要产生热量的,要特别注意通风冷却。

2.3低压无功补偿方式的选择

选择使用静态补偿还是动态补偿主要还是看负载使用的状况,工作场所,性价比几个方面。从经济方面考虑,在负载条件比较好的场所一般选用静态补偿,其制作费用比较低,损坏时更换的元器件比较容易采购。动态补偿相对于静态补偿其制作费用昂贵,维护成本相对

较高适用于用电波动大,谐波大的场合。

近年来还出现了一种集成式的智能无功补偿装置即智能电容器。智能电容器是集成现代测控、电力电子、网络通讯、自动化控制、电力电容器等先进技术为一体的智能无功补偿装置。智能无功补偿电容器改变了传统无功补偿装置落后的控制技术和落后的机械式接触器或机电一体化开关作为投切电容器的投切技术,改变了传统无功补偿装置体积庞大和笨重的结构模式,从而使新一代低压无功补偿设备具有补偿效果更好,体积更小,功耗更低,价格更廉,节约成本更多,使用更加灵活,维护更加方便,使用寿命更长,可靠性更高的特点,适应了现代电网对无功补偿的更高要求。使用智能电容器的低压补偿柜制作成本介于传统的静态补偿柜与动态补偿柜之间,其补偿效果比一般的静态补偿要好很多且保护功能多,维护更换很便捷在小区民用电中得到了广泛应用。

3总结

综上所述,在低压无功补偿柜中,动补适用于用电波动大,谐波大的场合,但是补偿设备的造价高昂。由于工作中没有接触器投切的声音,故早些时候,机械部的专家把它叫静止补偿。静态补偿,是传统的接触器控制补偿电容的方式,其反映速度极慢,少的十几秒,多的几十分钟才能反映,只适用于用电相对较稳定的场合。动态补与静补,关键看反映速度。在实际生产时根据现场环境及要求,采用静补的地方还是比较多的,但近些年来工业上动态补偿的使用越来越多。在无功功率补偿的应用方面,选择那一种补偿方式,还要依电网的状况而定,首先对所补偿的线路要有所了解,对于负荷较大且变化较快的工况,电焊机、电动机的线路采用动态补偿,节能效果明显。对于负荷相对平稳的线路应采用静态补偿方式。

参考文献

[1]诸俊伟.电力系统分析[M].北京:水利电力出版社,1995.

[2]余建明.供电技术[M].北京:机械工业出版社,1998.

[3]刘华云.对电网无功功率补偿的探讨[A].科学之友(B版),2007,09-0003-02

作者简介:周洁(1979-),女,工程师,主要从事电控配电成套

设计制作。

------------最新【精品】范文

低压无功补偿在配电台区中的应用

低压无功补偿在配电台区中的应用 发表时间:2018-08-22T10:34:27.173Z 来源:《电力设备》2018年第14期作者:惠三军 [导读] 摘要:在我国电力系统的发展道路中低压无功补偿技术在配电台区中的应用范围越来越广,但是在部分地区还存在着低压配电台区使用的线路不符合标准、线路损耗过大以及电压过低等具体问题。本文主要针对线路损耗的问题使用低压无功补偿技术进行合理地改进,进而对功率低以及质量差等电力方面的问题提出改进措施,为防止电能的过度消耗提供保障,最后对低压无功补偿技术在应用效果进行分析。 (国网山东省电力公司诸城市供电公司山东潍坊 262200) 摘要:在我国电力系统的发展道路中低压无功补偿技术在配电台区中的应用范围越来越广,但是在部分地区还存在着低压配电台区使用的线路不符合标准、线路损耗过大以及电压过低等具体问题。本文主要针对线路损耗的问题使用低压无功补偿技术进行合理地改进,进而对功率低以及质量差等电力方面的问题提出改进措施,为防止电能的过度消耗提供保障,最后对低压无功补偿技术在应用效果进行分析。 关键词:低压无功;智能配电台区;电压质量;电能损耗 无功补偿为电网的安全运行提供了必要的保障,并且在电网供电的质量以及产生的经济效益方面也占据了重要的地位。近些年来我国已经社会各方面对高压无功补偿的关注程度逐渐提高,但是由于低压配网的构造比较繁琐导致人们对其的重视程度不够,再加上较大功率电器的大规模使用,造成了配电网的电力负担明显加重而无法保证电力供应的效率和质量,因此在配电台区中使用低压无功补偿的装置对于电网的建设有着极其重要的意义。 一、装置介绍 (一)装置简介 一般的补偿装置的容量可以分为从二级到四级不等,由于分组较少并且每一级之间的跳跃程度过于明显,造成运行期间的安全性能得不到保障,容易出现不平衡的情况,因此有必要对传统的补偿装置进行合理地调整。 低压无功补偿装置的构造如图1所示,主要由负荷开关、智能时间继电器、熔断器以及交流接触器等部件组成。最新研发的补偿装置的容量可以分为36级,如图2所示,电容器部件可以在每两根相线之间进行补偿,极大程度地提升了装置的便捷程度[1]。 (二)运行原理 在低压无功补偿装置的运行过程中,电容可以在每两根相线之间进行转移有功并且能够在相线之间与零线中连接数量不等的电容器,不仅能够把其功率因数补偿到0.94或者高于0.94并且能够原本负荷不平衡的电流调整至其额定电流的使用范围之内,能够在较大程度上解决传统负荷不均衡的状况。 (三)新型补偿装置的收益概算 假设配电台区在一年的使用中以大容量运行时间t1大约为3个月,小容量t2运行时间大约为9个月,而低压无功补偿的容量按照配变容量p的百分之三十来计算,在无功经济的当量依照a=0.09并且补偿的投入b按照百分之五十进行计算,以配电台区使用频率最广的c=200kVA 来计算年节能大约为: N=c×p×b×a×(t1+t2)×360d×[t1/(t1+t2)+t2/(t1+t2)]=11664kW?h 图3为试验区域台区某天的补偿投入容量对比图,可以看出相电压和相电流对补偿方式的影响。 二、现阶段配电网存在的问题以及改善的方向 (一)存在问题 虽然我国在大力推行城镇化建设使农村居民的生活水平得到较大的改善,但是由于农村数量基数过大导致现阶段还有较大数量的农村没有发展成为现代化的城镇,再加上我国城镇与农村的发展不平衡,这就会造成农村的用电设施老化问题一直得不到缓解。用电或者供电设备老化以及供电线路过度损耗一直是农村最主要的用电安全隐患之一,除此之外还有电压过低的现象经常出现,农民为解决这个问题大

低压无功补偿技术规范

Q/…… 吉林省电力有限公司企业标准 0.4kV低压无功补偿装置 技术规范 2006-9-17发布 2006-9-17实施 吉林省电力有限公司发布

目次 前言 (Ⅱ) 1.范围 (1) 2. 规范性引用文件 (1) 3 使用条件 (1) 3.1 环境条件 (1) 3.2 运行条件 (1) 3.3 系统条件 (1) 4 技术要求 (1) 5 装置功能 (2) 6 试验 (2) 7 技术服务 (2) 8在卖方工厂的检验、监造 (3) 9包装、运输和贮存 (3)

前言 为规范吉林省电力有限公司配电网设备、材料的技术要求,保证入网产品的先进、可靠、安全,依据国家及行业有关规定、规程、标准等,结合吉林省电力有限公司设备运行经验,特制定本标准。 本标准由吉林省电力有限公司提出并归口。 本标准主要起草单位:吉林省电力有限公司生产部 本标准主要起草人:张树东、陈学宇、马卫平、陈文义、谷明远、岳建国、杨万成、郑金鹏、任有学、宋庆秋、徐晓丰、孙静

0.4kV低压无功补偿装置技术规范 1范围 本标准规定了吉林省电力有限公司0.4kV低压无功补偿装置使用条件、主要技术参数和要求、试验、运输等。 本标准适用于吉林省电力有限公司0.4kV低压无功补偿装置的招标通用订货,是相关设备通用订货合同的技术条款。 2规范性引用文件 GB/T15576-1995 低压无功功率静态补偿装置总技术条件 DL599-1996 城市中低压配电网改造技术导则 JB7113-1993 低压并联电容器装置 3使用条件 3.1环境条件 3.1.1海拔高度:≤1000m 3.1.2空气温度 最高温度:+40℃ 最低温度:-40℃ 最大日温差: 25K 3.1.3最大风速: 35m/s 3.1.4最大覆冰厚度:10mm 3.1.5月相对湿度平均值:≤90% ;日相对湿度平均值:≤95% 3.1.6日照强度:≤1.1kW/m2 3.1.7抗震能力:8度(地面水平加速度0.3g,垂直加速度0.15g,两种加速度同时作用。分析计算的安全系数不小于1.67)。 3.1.8污秽等级:级 a)Ⅲ级 b)Ⅳ级 3.2运行条件 安装方式:户内/户外 3.3系统条件 3.3.1系统额定电压:0.4kV 3.3.2系统额定频率:50Hz 4主要技术参数和要求 4.1名称:配电监测与动态无功补偿箱 4.2外形尺寸:600(宽)×400(深)×600(高) 4.2.1地角尺寸:按深度方向打长孔320-340mm,ф14孔。 4.2.2柜体颜色:灰白色 4.3主要订货参数: 4.3.1输入电压:0.4kV(安装点电压) 4.3.2负荷特性:较重

浅谈无功补偿原理及无功补偿率

浅谈无功补偿原理及无功补偿率 无功补偿原理 电网中的电力负荷如电动机、变压器等,大部分属于感性负荷,在运行过程中需向这些设备提供相应的无功功率。在电网中安装并联电容器等无功补偿设备以后,可以提供感性负载所消耗的无功功率,减少了电网电源向感性负荷提供、由线路输送的无功功率,由于减少了无功功率在电网中的流动,因此可以降低线路和变压器因输送无功功率造成的电能损耗,这就是无功补偿。 简介编辑 无功补偿原理 当电网电压的波形为正弦波,且电压与电流同相位时,电阻性电气设备如白炽灯、电热器等从电网上获得的功率P等于电压U和电流I的乘积,即:P=U×I。 电感性电气设备如电动机和变压器等由于在运行时需要建立磁场,此时所消耗的能量不能转化为有功功率,故被称为无功功率Q。此时电流滞后电压一个角度φ。在选择变配电设备时所根据的是视在功率S,即有功功率和无功功率的矢量和:  无功功率为: 有功功率与视在功率的比值为功率因数: cosf=P/S 无功功率的传输加重了电网负荷,使电网损耗增加,系统电压下降。故需对其进行就近和就地补偿。并联电容器可补偿或平衡电气设备的感性无功功率。当容性无功功率QC等于感性无功功率QL时,电网只传输有功功率P。根据国家有关规定,高压用户的功率因数应达到0.9以上,低压用户的功率因数应达到0.85以上。 如果选择电容器功率为Qc,则功率因数为: cosφ= P/ (P2 + (QL-Qc)2)1/2 在实际工程中首先应根据负荷情况和供电部门的要求确定补偿后所需达到的功率因数值,然后再计算电容器的安装容量: Qc = P(tanf1 - tanf2)=P〔(1/cos2f1-1)1/2-(1/cos2f2-1)1/2〕 式中:

JKWNA-9低压无功补偿控制器使用说明书(2015总线版、.

JKWNA-9 低压无功补偿控制器 使用说明书江苏南自通华电力自动化有限公司 1产品简介 1.1概述 JKWNA-9低压无功补偿控制器和NA系列智能集成式电力电容补偿装置配套使用,具备采集并显示电测量数据,监测和显示智能电容器运行工况、投切状态,以及根据无功功率与目标功率因数自动控制投切电容器等功能。 1.2产品特点 JKWNA-9低压无功补偿控制器通过通信总线连接NA系列智能集成式电力电容补偿装置;控制器采集电网电测数据,在显示智能电容器组运行情况的同时,可以直接根据当前的电测数据,对电容器组进行智能投切控制,以达到无功补偿的效果。 1.3外观尺寸 2技术参数

显示分辨率128×64,显示12点阵汉字输入测量RJ45方式接入智能电容器网络 电源 工作范围AC380V±30% 功耗≤2W 工作条件 -10~55℃,相对湿度≤93% 无腐蚀气体场所,海拔≤2000m 隔离耐压电源>2500V 绝缘电阻≥2MΩ 尺寸 面框尺寸:120mm×120mm 开孔尺寸: 3使用说明 JKWNA-9低压无功补偿控制器面板由产品名称及公司信息、液晶显示屏、操作按键组成。下面对液晶显示屏显示内容和主要功能作简单说明: 3.1主菜单 液晶屏第1行从左到右依次显示:联网电容器数量、当前投切控制方式(自控/手控和软件版本号;

当前所有联网电容器的投切状态以图形的方式直观显示在液晶屏上,同时显示投入到电网中总的补偿容量,显示界面如下: 注:表示分补表示共补表示投入表示切除 当前电容柜补偿电流界面如下: 3.2运行工况 显示开关故障、过压保护、过流保护、过温保护、过谐波保护的电容器信息。 使用和切换界面查看各种保护与故障,按 键返回主菜单。 3.3设置参数 设置参数 CT变比(比值:0000 目标功率因数:0.99 无功算法时间:040 设置现场的电流互感器变比,无功控制的目标功率因数和无功算法时间。

用电企业无功功率补偿的作用、目的和意义

用电企业无功功率补偿的作用、目的和意义 电网中的许多用电设备是根据电磁感应原理工作的。它们在能量转换过程中建立交变磁场,在一个周期内吸收的功率和释放的功率相等,这种功率叫无功功率。电力系统中,不但有功功率平衡,无功功率也要平衡。 有功功率、无功功率、视在功率之间的关系如图1所示 式中 S——视在功率,kVA P——有功功率,kW Q——无功功率,kvar φ角为功率因数角,它的余弦(cosφ)是有功功率与视在功率之比即cosφ=P/S称作功率因数。 由功率三角形可以看出,在一定的有功功率下,用电企业功率因数cosφ越小,则所需的无功功率越大。如果无功功率不是由电容器提供,则必须由输电系统供给,为满足用电的要求,供电线路和变压器的容量需增大。这样,不仅增加供电投资、降低设备利用率,也将增加线路损耗。为此,国家供用电规则规定:无功电力应就地平衡,用户应在提高用电自然功率因数的基础上,设计和装置无功补偿设备,并做到随其负荷和电压变动及时投入或切除,防止。还规定用户的功率因数应达到相应的标准,否则供电部门可以拒绝供电。因此,无论对供电部门还是用电部门,对无功功率进行自动补偿以提高功率因数,防止无功倒送,从而节约电能,提高运行质量都具有非常重要的意义。 无功补偿的基本原理是:把具有容性功率负荷的装置与感性功率负荷并联接在同一电路,能量在两种负荷之间相互交换。这样,感性负荷所需要的无功功率可由容性负荷输出的无功功率补偿。 当前,国内外广泛采用并联电容器作为无功补偿装置。这种方法安装方便、建设周期短、造价低、运行维护简便、自身损耗小。 采用并联电容器进行无功补偿的主要作用: 1、提高功率因数 如图2所示图中

配电网无功补偿方式

配电网无功补偿方式 合理的无功补偿点的选择以及补偿容量的确定,能够有效地维持系统的电压水平,提高系统的电压稳定性,避免大量无功的远距离传输,从而降低有功网损。而且由于我国配电网长期以来无功缺乏,造成的网损相当大,因此无功功率补偿是降损措施中投资少回收高的有效方案。配电网无功补偿方式常用的有:变电站集中补偿方式、低压集中补偿方式、杆上无功补偿方式和用户终端分散补偿方式。 配电网无功补偿方案 1 变电站集中补偿方式 针对输电网的无功平衡,在变电站进行集中补偿(如图1的方式1),补偿装置包括并联电容器、同步调相机、静止补偿器等,主要目的是改善输电网的功率因数、提高终端变电所的电压和补偿主变的无功损耗。这些补偿装置一般连接在变电站的10kV母线上,因此具有管理容易、维护方便等优点。 为了实现变电站的电压控制,通常采用无功补偿装置(一般是并联电容器组)结合变压器有载调压共同调节。通过两者的协调来进行电压/无功控制在国内已经积累了丰富的经验,九区图便是一种变电站电压/无功控制的有效方法。然而操作上还是较为麻烦的,因为由于限值需要随不同运行方式进行相应的调整,甚至在某些区上会产生振荡现象;而且由于实际操作中变压器有载分接头的调节和电容器组的投切次数是有限的,而在九区图没有相应的判断。因此,现行九区图的调节效果还有待进一步改善。 2 低压集中补偿方式 在配电网中,目前国内较普遍采用的无功补偿方式是在配电变压器380V侧进行集中补偿(如图1的方式2),通常采用微机控制的低压并联电容器柜,容量在几十至几百千乏左右,根据用户负荷水平的波动投入相应数量的电容器进行跟踪补偿。它主要目的是提高专用变用户的功率因数,实现无功补偿的就地平衡,对配电网和配电变的降损有积极作用,同时也有助于保证该用户的电压水平。这种补偿方式的投资及维护均由专用变用户承担。目前国内各厂家生产的自动补偿装置通常是根据功率因数来进行电容器的自动投切。就这种方案而言,虽然有助于保证用户的电能质量,但对电力系统并不可取。虽然线路电压的波动主要由无功量变化引起,但线路的电压水平往往是由系统情况决定的。当线路电压基准值偏高或偏低时,无功的投切量可能与实际需求相去甚远,易出现无功过补偿或欠补偿。 对配电系统来说,除了专用变之外,还有许多公用变。而面向广大家庭用户及其他小型用户的公用变,由于其通常安装在户外的杆架上,实现低压无功集中补偿则是不现实的:难于维护、控制和管理,且容易造成生产安全隐患。这样,配电网的无功补偿受到了很大地限制。 3 杆上补偿方式 由于配电网中大量存在的公用变压器没有进行低压补偿,使得补偿度受到限制。由此造成很大的无功缺口需要由变电站或发电厂来填,大量的无功沿线传输使得配电网网损仍然居高难下。因此可以采用10kV户外并联电容器安装在架空线路的杆塔上(或另行架杆)进行无功补偿(如图1的方式3),以提高配电网功率因数,达到降损升压的目的。但由于杆上安装的并联电容器远离变电站,容易出现保护不易配置、控制成本高、维护工作量大、受安装环境和空间等客观条件限制等问题。因此,杆上无功优化补偿必须结合以下实际工程要求来进行: (1)补偿点宜少,建议一条配电线路上宜采用单点补偿,不宜采用多点补偿; (2)控制方式从简。建议杆上补偿不设分组投切; (3)建议补偿容量不宜过大。补偿容量太大将会导致配电线路在轻载时出现过电压和过补偿现象;另外杆上空间有限,太多数电容器同杆架设,既不安全,也不利于电容器散热; (4)建议保护方式应简化。主要采用熔断器和氧化锌避雷器作简单保护。 显然,杆上无功补偿主要是针对10kV馈线上的公用变所需无功进行补偿,因其具有投资小,回收快,补偿效率较高,便于管理和维护等优点,适合于功率因数较低且负荷较重的

低压无功补偿系统硬件设计Word版

摘要 本文主要介绍低压无功补偿装置的基本原理、控制方案以及硬件方面的选型和设计。 该补偿系统采用TI公司的定点TMS320LF2812系列DSP和MCU的双控制器进行控制,TMS320LF2812为补偿装置的总控制器,具有自动采样计算、无功自动调节、故障保护、数据存储等功能。同时具备指令运算速度快(约100MIP)、运算量大的优点,同时MCU 与外部设备进行通讯,互不干扰,更好的满足了实时性和精确性的要求。采用晶闸管控制投切电容器、数字液晶实时显示系统补偿情况,可以实现快速、无弧、无冲击的电容器投切。为了更详细的介绍该系统,在论文第四章设计了比较完整的各功能模块的硬件电路图,其中包括电源模块、信号变换及调理模块、AD采样模块、锁相同步采样模块、通讯模块等。 关键字:低压无功补偿;晶闸管投切电容器;DSP

Abstract This paper mainly introduces the basic principle of low-voltage reactive power compensation device, control scheme and hardware selection and design. The compensation system by TI company's fixed-point tms320lf2812 series DSP and MCU dual controller control, tms320lf2812 compensation device controller with automatic sample calculation, automatic reactive power regulation, fault protection, data storage and other functions. At the same time with the instruction operation speed (about 100MIP), the advantages of large amount of computation. At the same time, MCU and peripheral equipment communication and do not interfere with each other, better meet the requirements of real-time and accurate. The use of thyristor controlled switched capacitor, digital LCD display real-time compensation system situation can achieve fast, no arc , without the impact of the capacitor switching. In order to more detailed introduction to the system. In the fourth chapter of the thesis design the hardware circuit diagram of each function module of relatively complete, including power module, signal transformation and conditioning module, AD sampling module, phase locking synchronous sampling module, communication module block and so on. Key Words:Low voltage reactive power compensation;Thyristor switched capacitor; DSP

浅析无功补偿在电力电网中的应用

浅析无功补偿在电力电网中的应用 发表时间:2017-11-01T11:42:22.800Z 来源:《电力设备》2017年第18期作者:马静 [导读] 摘要:在现代供电行业内部,功率因数是考核电网运行的重要指标之一,为了确保功率因数达到考核指标,保证电网供电的政策运行,无功补偿就显得尤为重要。本文就无功补偿的原因和策略进行了探讨,以期给电网企业一些借鉴价值。 (国网吴忠供电公司宁夏回族自治区吴忠市 751100) 摘要:在现代供电行业内部,功率因数是考核电网运行的重要指标之一,为了确保功率因数达到考核指标,保证电网供电的政策运行,无功补偿就显得尤为重要。本文就无功补偿的原因和策略进行了探讨,以期给电网企业一些借鉴价值。 关键词:无功补偿;电力电网;应用 电力系统中先天性地存在着大量的无功负荷,这些无功负荷来自电力线路、电力变压器以及客户的用电设备。系统运行中大量的无功功率将降低系统的功率因数,增大线路电压损失和电能损失,严重地影响着电力企业的经济效益,解决这些问题的一个行之有效的方法就是进行无功补偿。为了起到节能降损的作用,改善电能的质量,提高输变电设备的有功出力,使电气设备处在最佳经济状态下运行,使有限的电力能更好地为社会主义建设服务,做好无功补偿工作势在必行。 1 电力电网中无功补偿的原因 随着国民经济的快速发展,国内的工业用电和生活用电不断增加,需求的增加对供电系统提出了更高的要求,无功补偿的运用,可以有效的降低电力电网的有功损耗,提高电力电网运行的科学性、经济性。无功补偿设备可以有效的降低电网中的功率耗损,根据公式I=P/Ucos可知,其中电流与cos成反比,因此,按装无功补偿设备之后可以有效的提高功率因数,线路中的负荷电流降低,进而使有功功率的损耗有所降低,同时还可以减少电网中电压的损失,提高电压的质量,减少客户的电费费用,减少设备投资。由于无功补偿可以减少无功功率在电网中的流动,降低线路和变压器因为输送无功功率而造成电能损失,安装无功补偿设备可以有效的降低电力网的损耗。而且无功补偿可以提高功率因数,相对其他节能措施而言,是一项收效快、投资少的降损节能措施,它可以使电力系统少送无功功率,多送有功功率,而且可以在电力系统无功功率不足时,迅速提供无功功率。 2 电力电网中无功补偿的使用 一般无功补偿设备是在用户的负载点或者配电室进行补偿,供电部门会与用户进行协商,鼓励用户在在用电处安装无功补偿设备,减少电费支出,进而提高功率因数,使功率因数符合考核标准。相关资料表明,无功功率约有40%在消耗在变压器和电线线路,剩余的则消耗在客户的用电设备中。为此,供电部门要与用户加强沟通,共同做好无功补偿设备的配置,保证电力资源的高效合理使用,减少能源浪费。 2.1无功补偿设备的选定 无功补偿设备的选定要按照合理布局、就地平衡、全面规划的原则,保证电力电网的无功补偿取得最佳的经济效益和社会效益。合理的无功补偿设备容量设定是决定其是否能够实现节能降耗的重要因素,在实际工作中,电力企业首先要根据不同的负荷情况,以及供电部门的要求确定无功补偿后应该达到的功率因数,然后计算无功补偿设备应具有的实际容量大小。 2.2并联电容器的无功补偿 提高功率因数最常用的办法就是与电感性负载并联静电电容器,并联补偿的电力电容器,根据电压高低的不同内部接线也不同,高压电容器组一般宜接成中性点不接地星形;低压变压器组一般接成三角形。目前我国使用的补偿方式有单独就地补偿、低压集中补偿、高压集中补偿三种。 2.2.1单独就地补偿 相比其他两种补偿方式,单独就地补偿的补偿范围最大,补偿效果也最好,电力企业一般优先采用这种方式进行补偿。单独就地补偿的电容器组是使用电设备自身的绕组电阻来放电,它是将并联补偿电容器组装在需要进行补偿的用电设备附近,它可以直接补偿安装部位的变压器和所有高低压电线线路的无功功率。单独就地补偿需要的投资费用较大,利用率较低,一般而言,当被补偿的用电设备停止作业时,单独就地补偿的电容器组也会被切除,导致资源浪费。为此,它适用于一些经常运转,负荷较平稳而且容量又大的设备,如,高频电炉、感应电动机等等,以及一些虽然容量较小,但是数量多,长期稳定运行的机械设备,如荧光灯等。 2.2.2低压集中补偿 低压集中补偿主要用于补偿高压配电线路、电力系统以及车间变电所低压母线前车间变电所的无功功率,可以使用专门的放电电阻或者白炽灯的灯丝进行放电,使用成本较低,运行和维修也比较方便安全,同时,它可以依据用户的用电负荷水平的波动,投入相应的电容器,进行跟踪补偿。低压集中补偿的目的在于提高专用变压器用户的功率因数,投资费用和后期维护都是由专用变压器用户自己承担。 2.2.3高压集中补偿 高压集中补偿是将高压电容器组集中装设在工厂变电所的6~10kV母线上,因此,这种补偿方式只能补偿6~10kV母线前的所有线路的无功功率,而母线后的电线线路的无功功率得不到有效补偿。但是相对而言,这种补偿方式的投资较小,而且便于工厂进行集中管理和控制,同时对于工厂高压的无功功率进行有效的补偿,比较适用于大中型的工厂。 3 无功补偿设备的使用管理 在进行无功补偿设备配置和管理的过程中,坚持集中补偿与分散补偿相结合,以分散补偿为主。对分散补偿的配置要从实际出发,确保无功补偿之后可以达到功率因数的审核标准,对于供电公司而言,无功补偿设备过于分散,导致企业的设备维护量大,工作难度较大,为此,大多采用变电站集中补偿和配变就地分散补偿相结合的方式。另外,在无功补偿过程中要坚持调压与降损相结合,同时以降损为主,因为无功补偿产生的最大的经济效益和社会价值是降损,在一定程度上调整电压只是为了保证电压质量。特别是对于很多轻载运行的电线线路,由于电压偏高,会导致配电变压器的铁损占线损的70%以上,这种情况下,就不宜再安装电容,否则在线路电压升高过快时,配电变压器的损坏程度会进一步增加,使线损程度增大,为此,投切无功补偿设备,使电网中的电力功率因数提高,减低电网的损耗。能源建设是我国国民经济建设的战略重点之一,在进行能源建设的过程中,我国坚持贯彻实施科学发展观,要求相关部门在加强能源开发的过程中,不断提高资源的使用效率,使有限的能源发挥尽可能多的经济效益,同时减少在使用过程中的能源浪费。为此,在电力电网内出现大负荷欠补偿时,供电企业、发电企业和用电企业要协同合作,共同把无功补偿工作搞好。电力电网通过无功补偿节约电能,不仅可以降低工厂的生产成本,而且可以为国家积累更多的财富,促进国

低压无功补偿的应用与效益分析

低压无功补偿的应用与效益分析 发表时间:2017-09-19T09:30:56.460Z 来源:《电力设备》2017年第13期作者:王玺[导读] 甚至会导致部分区域无功严重不足,电压作用往往很低,一旦系统遭遇到较大程度的干扰,在电压稳定性薄弱区域使得电压崩溃。 (国网河北省电力公司任丘市供电分公司河北任丘 062550)摘要:随着国民经济的不断快速发展及人们生活质量水平的日益提高,人们对于电力资源服务、供电的可靠性与质量也相应地提出了更高的要求,由于负荷的反复增加变化与电源的全面涨幅,不仅从行为上改变了当前电力体系的网络组织,也改变了电力系统中的电源布置,致使系统无功分布并不科学,有时,甚至会导致部分区域无功严重不足,电压作用往往很低,一旦系统遭遇到较大程度的干扰,在电 压稳定性薄弱区域使得电压崩溃。无功补偿能提高系统电压水平,增强电网稳定裕度,降低线损,并由此产生经济效益。为了确保功率因数达到考核指标,保证电网供电的政策运行,无功补偿就显得尤为重要。 关键词:低压无功补偿;应用;效益分析 1电力电网中无功补偿的原因 随着国民经济的快速发展,国内的工业用电和生活用电不断增加,需求的增加对供电系统提出了更高的要求,无功补偿的运用,可以有效地降低电力电网的有功损耗,提高电力电网运行的科学性、经济性。 无功补偿设备可以有效地降低电网中的功率耗损,根据公式I=P/Ucos可知,其中电流与cos成反比,因此,安装无功补偿设备之后可以有效地提高功率因数,线路中的负荷电流降低,进而使有功功率的损耗有所降低,同时还可以减少电网中电压的损失,提高电压的质量,减少客户的电费费用,减少设备投资。 由于无功补偿可以减少无功功率在电网中的流动,降低线路和变压器因为输送无功功率而造成电能损失,安装无功补偿设备可以有效地降低电力网的损耗。而且无功补偿可以提高功率因数,相对其他节能措施而言,是一项收效快、投资少的降损节能措施,它可以使电力系统少送无功功率,多送有功功率,而且可以在电力系统无功功率不足时,迅速提供无功功率。 2电力电网中无功补偿的使用 ―般无功补偿设备是在用户的负载点或者配电室进行补偿,供电部门会与用户进行协商,鼓励用户在用电处安装无功补偿设备,减少电费支出,进而提高功率因数,使功率因数符合考核标准。相关资料表明,无功功率约有40%是消耗在变压器和电线线路,剩余的则消耗在客户的用电设备中。为此,供电部门要与用户加强沟通,共同做好无功补偿设备的配置,保证电力资源的高效合理使用,减少能源浪费。 2.1无功补偿设备的选定 无功补偿设备的选定要按照合理布局、就地平衡、全面规划的原则。保证电力电网的无功补偿取得最佳的经济效益和社会效益。合理的无功补偿设备容量设定是决定其是否能够实现节能降耗的重要因素,在实际工作中,电力企业首先要根据不同的负荷隋况,以及供电部门的要求确定无功补偿后应该达到的功率因数,然后计算无功补偿设备应具有的实际容量大小。 2.2并联电容器的无功补偿 (1)单独就地补偿 相比其他两种补偿方式,单独就地补偿的补偿范围最大,补偿效果也最好,电力企业一般优先采用这种方式进行补偿。单独就地补偿的电容器组是使用电设备自身的绕组电阻来放电,它是将并联补偿电容器组装在需要进行补偿的用电设备附近,它可以直接补偿安装部位的变压器和所有高低压电线线路的无功功率。 (2)低压集中补偿 低压集中补偿主要用于补偿高压配电线路、电力系统以及车间变电所低压母线前车间变电所的无功功率,可以使用专门的放电电阻或者白炽灯的灯丝进行放电,使用成本较低,运行和维修也比较方便安全。 (3)高压集中补偿 高压集中补偿是将高压电容器组集中装设在工厂变电所的6~10kV母线上,因此,这种补偿方式只能补偿6~10kV母线前的所有线路的无功功率,而母线后的电线线路的无功功率得不到有效补偿。 3无功补偿的效益分析 在现代用电企业中,在数量众多、容量大小不等的感性设备连接与电力系统中,以致电网传输功率除有功功率外,还需无功功率。如自然平均功率因数在0.70~0.85之间。企业消耗电网的无功功率约占消耗有功功率的60%~90%,如果把功率因数提高到0.95左右,则无功消耗只占有功消耗的30%左右。由于减少了电网无功功率的输入,会给用电企业带来效益。 3.1节省企业电费开支 提高功率因数对企业的直接经济效益是明显的,因为在国家电价制度中,从合理利用有限电能触发,对不同企业的功率因数规定了要求达到的不同数值,低于规定的数值,需要多收电费,高于规定数值,可相应地减少电费。可见,提高功率因数对企业有着重要的经济意义。 3.2提高设备的利用率 对于原有供电设备来讲,在同样有功功率下,因功率因数的提高,负荷电流减少,因此向负荷传送功率所经过的变压器、开关和导线等供配电设备都增加了功率储备,从而满足了符合增长的需要;如果原网络已趋于过载,由于功率因数的提高,输送无功电流的减少,使系统不至于过载运行,从而发挥原有设备的潜力;对尚处于设计阶段的新建企业来说则能降低设备容量,减少投资费用,在一定条件下,改善后的功率因数可以使所选变压器容量降低。因此,使用无功补偿不但减少初次投资费用,而且减少了运行后的基本电费。工业用户合理配置无功补偿,可提高功率因数,提高设备的出力率,降低电费的支出,获得可观的经济效益,同时也能改善电网的功率因数和电压质量,提高电力系统的供电稳定性。 在进行无功补偿设备配置和管理的过程中,坚持集中补偿与分散补偿相结合,以分散补偿为主,对分散补偿的配置要从实际出发,确保无功补偿之后可以达到功率因数的审核标准。对于供电公司而言,无功补偿设备过于分散,导致企业的设备维护量大,工作难度较大,为此,大多采用变电站集中补偿和配变就地分散补偿相结合的方式。

配电网无功补偿方式的优化选择

配电网无功补偿方式的优化选择 发表时间:2011-12-31T10:12:35.030Z 来源:《时代报告》2011年11月下期供稿作者:邹雪莲 [导读] 电力系统无功分布是否合理,关系到电能质量的优劣,还影响电网运行的安全性和经济性。 邹雪莲 (重庆工贸职业技术学院,重庆 408000) 中图分类号:TM769 文献标识码:A 文章编号:1003-2738(2011)11-0278-01 摘要:本文根据目前配电网中无功补偿的实际情况,简要分析了配电网中无功补偿装置在调节电压、降低电能损耗中所起的作用,提出了配电网中几种无功补偿方式,进行了经济技术优化比较,提出了相应的优化选择方式。 关键词:配电网;无功补偿;优化选择 一、概述 随着国民经济的高速发展和人民生活水平的提高,人们对电力的需求日益增长,电网负荷的不断增加,改变了网络结构和电源分布,造成无功分布的不合理,甚至出现局部地区无功严重不足、电压水平普遍较低的情况。电力系统无功分布是否合理,关系到电能质量的优劣,还影响电网运行的安全性和经济性。合理的无功补偿点的选择以及补偿方式的选择,能够有效地维持系统的电压水平,提高系统的电压稳定性,降低有功网损。因此,解决好配电网络无功补偿的问题,对电网的运行安全和降损节能有着重要的意义。 二、无功补偿的原则 无功补偿的原则:全面规划,合理布局,分级补偿,就地平衡。 1.总体平衡与局部平衡相结合:既要满足全网的总无功平衡,又要满足分线、分站的无功平衡。 2.集中补偿与分散补偿相结合:要求既要在变电站进行大容量集中补偿,又要在配电线路、配电变压器和用电设备处进行分散补偿,目的是做到无功就地平衡,减少其长距离输送。 3.高压补偿与低压补偿相结合:以低压补偿为主,这和分散补偿相辅相成。 4.降损与调压相结合针对线路长,分支多,负荷分散,功率因数低的线路。这种线路最显著的特点是:负荷率低,线路损失大,若对此线路补偿,可明显提高线路的供电能力。 5.供电部门的无功补偿与用户补偿相结合:由于无功消耗大约60%在配电变压器中,其余的消耗在用户的用电设备中,若两者不能很好地配合,可能造成轻载或空载时过补偿,满负荷时欠补偿,使补偿失去了它的实际意义,得不到理想的效果。 三、无功补偿装置在调节电压、降低电能损耗中所起的作用 无功补偿的作用主要有以下几点:提高系统及负载的功率因数,降低设备容量,减少功率损耗,稳定受电端及电网的电压,提高供电质量。 1.功率因数补偿,提高电压质量。 工农业生产的用电设备多为电磁结构,功率因数较低,一般都会低于0.7以下,导致电网电压降低。加装并联电容器补偿装置就近供给用户或配电网所需要的滞相无功功率,减少在配电网中流失的无功功率,降低网损,从而改善电压质量; 2.无功补偿调压,提高电压质量。 变电站10KV母线无功集中补偿,主要是平衡输电网的无功功率,提高系统终端变电站的母线电压,补偿主变和高压线路的无功损耗。变电站10KV母线无功集中补偿容量和投切控制方式应考虑到满足主变自身的无功损耗和就近向配电线路前端输送无功,为主变有载调压维持系统电压稳定提供保障。 四、配电网无功补偿方案及其经济技术优化比较 1.变电站集中补偿方式 针对输电网的无功平衡,在变电站进行集中补偿,补偿装置包括并联电容器、同步调相机、静止补偿器等,这些补偿装置一般连接在变电站的10kV母线上,因此具有管理容易、维护方便等优点。 为了实现变电站的电压控制,通常采用并联电容器组结合变压器有载调压共同调节。利用九区图配合调节来进行电压无功控制,是一种变电站电压无功控制的有效方法。然而操作上较为麻烦,因为由于限值需要随不同运行方式进行相应的调整,会在某些区上产生振荡现象;而且由于实际操作中变压器有载分接头的调节和电容器组的投切次数是有限的,而九区图没有相应的判断。因此,现行九区图的调节效果还有待进一步改善。 2.低压集中补偿方式。 在配电网中,目前国内较普遍采用的无功补偿方式是在配电变压器380V侧进行集中补偿,通常采用微机控制的低压并联电容器柜,根据用户负荷水平的波动投入相应数量的电容器进行跟踪补偿,实现无功补偿的就地平衡,对配电网和配电变的降损有积极作用,同时也有助于保证该用户的电压水平。 3.杆上补偿方式。 采用 10kV户外并联电容器安装在架空线路的杆塔上进行无功补偿,以提高配电网功率因数,达到降损升压的目的。由于杆上安装的并联电容器远离变电站,容易出现保护不易配置、控制成本高、维护工作量大、受安装环境和空间等客观条件限制等问题。因此,杆上无功优化补偿必须结合以下实际工程要求来进行:补偿点宜少、杆上补偿不设分组投切、补偿容量不宜过大、保护方式应简化。 杆上无功补偿主要是针对10kV馈线上的公用变所需无功进行补偿,因其具有投资小,回收快,补偿效率较高,便于管理和维护等优点,适合于功率因数较低且负荷较重的长配电线路,但是因负荷经常波动而该补偿方式是长期固定补偿,故其适应能力较差,应积极开发应用电容器组能自动投切的杆上无功补偿技术。 4.用户终端分散补偿方式。 直接对用户末端进行无功补偿,将最恰当地降低配电网的损耗和维持配电网的电压水平的有效措施。对于企业和厂矿中的电动机,应

无功补偿技术发展及其应用研究学士学位论文

提供全套毕业论文图纸,欢迎咨询 编号(学号):13894049 毕业设计 (2013届本科) 题目:无功补偿技术的发展及其应用研究 学院:信息与电气工程学院 专业: 电气工程及其自动化专业 姓名: 指导教师: 完成日期:2013年06月13 日

毕业论文(设计)任务书 论文(设计) 题目无功补偿技术的发展及其应用研究 下发任务 日期 2013.03.01 学生姓名张晟指导教师栗庆吉讲师一.论文(设计)主要内容 本文研究的是电力系统无功补偿技术的发展以及在现代工业领域的应用。随着国民经济的迅速发展,用电量的增加,电网的经济运行日益受到重视。为了做好降损节能,改善电能质量,提高电气设备的有功出力,使电气设备在最佳经济状态下运行,无功功率补偿工作势在必行。本文揭示无功功率补偿发展根本并介绍无功功率补偿的应用,意在突出无功补偿技术与现代科技发展的有机结合。

二.论文(设计)的基本要求 1.有关资料的收集: 要求尽量收集第一手资料,资料要真实、可靠、有代表性。 2 资料的整理与分析: 要求条理清晰,数据分析详尽。 3 查阅相关文献: 要求贴近主题,有参考价值。 4 认真撰写论文,字数在10000字以上。 三.论文(设计)工作进度安排 阶段论文(设计)各阶段名称日期 1 现场观察无功补偿装置2013. 3. 2—2013. 3.10 2 参数进行分析与处理2013.3.11—2013.3.20 3 查阅相关文献2013.3.21—2013.4.10 4 撰写论文初稿2013.4.11—2013. 5.21 5 论文修改2013. 5. 21—2013. 6.2 6 论文完成2013. 6.3

低压无功补偿的几个问题

低压无功补偿的几个问题 1、补偿柜有那些标准?电容器有那些标准? 2、为什么要在系统安装电力电容补偿装置? 3、用于补偿的电力电容器现行的标准是什么? 4、为什么电容器的保护控制电器和导线要求按照电容器额定电流的1.5倍来选择? 5、补偿柜中熔断器为何不能用微型断路器来代替? 6、补偿柜中热继电器何种情况下可省略? 7、XD1电抗器与滤波电抗器一样吗? 低压无功补偿的几个问题 1、补偿柜有那些标准?电容器有那些标准? (a)机械部相关标准: JB7115-1993低压无功就地补偿装置 JB7113-1993低压并联电容器装置 (b)电力部相关标准: DL/T 597—1996低压无功补偿控制器订货技术条件-有效版本 (c)国标 GB 12747.2-200410KV及以下交流电力系统用自愈式并联电容器第2部分:老化试验、自愈性试验和破坏试验-有效版本 GBT 12747.1-2004标称电压1kV及以下交流电力系统用自愈式并联电容器第1部分:总则-有效版本 2、为什么要在系统安装电力电容补偿装置? 工业生产广泛使用的交流异步电动机、电焊机、电磁炉等设备都是感性负载,这些感性的负载在进行能量转换过程中,使加在其上的电压超前电流一个角度,这个角度的余弦cosΦ叫做功率因数。当功率因数即无功功率很大时,会有以下危害: (1)增大线路电流,使线路损耗加大,浪费电能; (2)因线路电流增大,一旦输电线路较远,线路上的电压降就大,电压过低就可能影响设备正常使用; (3)对变压器或者发电机而言,无功功率大,变压器或者发电机输出的电流也大,往往是输出电流已达额定值,这时负荷若再增加就需要加多一台变压器或者发电机组,浪费资源;补偿了电容后,同样负荷下变压器或者发电机输出电流大大降低,再增加负荷机组也能承受,无需再加一台变压器或者发电机,可节省资源。 (4)月平均功率因数工业用户低于0.92、普通用户低于0.9要被供电管理部门处于不同额度的罚款。 增加并联电容补偿柜是补偿功率因数的方法之一(另外还有采用过激磁的同步电动机、调相机、异步电动机同步化等方法)。 3、用于补偿的电力电容器现行的标准是什么? 现行的两个标准是: GB 12747.2-200410KV及以下交流电力系统用自愈式并联电容器第2部分:老化试验、自愈性试验和破坏试验-有效版本 GBT 12747.1-2004标称电压1kV及以下交流电力系统用自愈式并联电容器第1部分:总则-有效版本

无功补偿的意义

第1章绪论 1.1 无功补偿的意义 国民经济的高速发展和人民生活水平的不断提高带来了电力负荷的高速增长。尤其是近两、三年来,由于电力负荷增长迅猛,而发电装机容量和输配电能力不足,造成全国近20个省市电力供应紧张,部分省市出现限电拉闸[1]。与此同时,随着电力市场的开放,电力用户对电能质量的要求也在提高;电力生产与供应企业也比以往任何时候都重视电力系统运行的经济性。 电力系统运行的经济性和电能质量与无功功率有重大的关系。无功功率是电力系统一种不可缺少的功率。大量的感性负荷和电网中的无功功率损耗,要求系统提供足够的无功功率,否则电网电压将下降,电能质量得不到保证。同时,无功功率的不合理分配,也将造成线损增加,降低电力系统运行的经济性。 无功功率从何而来?显然,发电机提供的无功功率相对负荷和网络对无功功率的需求来说只是“杯水车薪”,仅仅依靠发电机提供无功功率也是极不经济的。无功功率最主要的来源是利用各种无功功率补偿(以下简称无功补偿)设备在电力系统的各个环节进行无功补偿。因此,无功补偿是电力系统的重要组成部分,它是保证电能质量和实现电力系统经济运行的基本手段。 低压电力用户量大面广,其负荷的功率因数又大都比较低,因此在低压电网中进行无功功率的就地补偿是整个电力系统无功补偿的重要环节。 低压电网的无功补偿主要采用并联电容器进行,它包括固定电容器(FC)补偿和自动投切电容器的动态补偿以及两者混合补偿等方式。 电力负荷是随时变化的,所需要的无功功率也是随时变化的,为了维持无功平衡,要求无功补偿设备实行动态补偿,即要根据无功负荷的变化及时投切电容器。以往的低压动态无功补偿设备以机械开关(接触器)作为电容器的投切开关,机械开关不仅动作速度慢,而且会产生诸如涌流冲击、过电压、电弧重燃等现象,开关本身和电容器都容易损坏。据调查,我国过去使用的自动投切电容器无功补偿装置在使用3年后损坏率达75%[2]。 随着电力电子技术和微机控制技术的迅速发展和广泛应用,出现了智能型的动态无功补偿装置。这种以电力电子器件作为无功器件(电容器、电抗器)的控制或开关器件的动态无功补偿装置被称为静止无功补偿装置(SVC:Static V ar Compensator)。 SVC是动态无功补偿技术的发展方向,它正成为传统无功补偿装置的更新换代产