4Connection
Assembly
?2-channel isolated barrier ?24 V DC supply (Power Rail)
?TC, RTD, potentiometer or voltage input ?Current output 0/4mA...20mA ?Sink or source mode
?Configurable by PACT ware ]TM
?Line fault (LFD) and sensor burnout detection ?
Up to SIL2 acc.to IEC 61508/IEC 61511
Function
This isolated barrier is used for intrinsic safety applications. It is designed to connect RTDs, thermocouples, or potentiometers in the hazardous area, and provide a proportional 0/4mA ...20mA signal to the safe area.The barrier offers 3-port isolation between input, output, and power supply.
A removable terminal block K-CJC-** is available for
thermocouples when internal cold junction compensation is desired.
A fault is indicated by a red flashing LED per NAMUR NE44 and user-configured fault outputs.
The unit is easily programmed with the PACT ware ? configuration software.
A collective error messaging feature is available when used with the Power Rail system.
For additional information, refer to the manual and https://www.doczj.com/doc/d89683168.html,.
Features
2
12-09-17 12:03
D a t e o f i s s u e 2012-09-17
223819_e n g .x m
l
General specifications Signal type Analog input
Supply Connection terminals 14+, 15- or power feed module/Power Rail Rated voltage 20 ... 30 V DC
Ripple
within the supply tolerance Power loss/power consumption ≤ 1.5 W / 1.5 W Input Connection terminals 1, 2, 3; 4, 5, 6
RTD
type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)type Cu10, Cu50, Cu100 (P50353-92)type Ni100 (DIN 43760)Measuring current approx. 200 μA with RTD Types of measuring 2-, 3-wire connection Lead resistance
≤ 50 ? per lead
Measuring circuit monitoring sensor burnout, sensor short-circuit Thermocouples
type B, E, J, K, N, R, S, T (IEC 584-1:1995)type L (DIN 43710:1985)
type TXK, TXKH, TXA (P8.585-2001)Cold junction compensation external and internal Measuring circuit monitoring sensor burnout
Voltage selectable within the range -100 ... 100 mV
Potentiometer 0 ... 20 k ? (2-wire connection), 0.8 ... 20 k ? (3-wire connection)Input resistance ≥ 1 M ? (-100 ... 100 mV)
Output Connection output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-)Output I, II Analog current output Current range 0 ... 20 mA or 4 ... 20 mA
Fault signal downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)Source load 0 ... 550 ?
open-circuit voltage ≤ 18 V
Sink
Voltage across terminals 5 ... 30V. If the current is supplied from a source > 16.5V,series resistance of ≥ (V - 16.5)/0.0215 ? is needed, where V is the source voltage.The maximum value of the resistance is (V - 5)/0.0215 ?.Transfer characteristics Deviation
After calibration
Pt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection))
thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1 K (1.2 K for types R and S)) this includes ± 0.8 K error of the cold junction compensation mV: ± (50 μV + 0.1 % of span)
potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes errors due to lead resistance))Influence of ambient temperature
deviation of CJC included:
Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ?T amb *)
thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ?T amb *) mV: ± (0.01 % of measurement value + 0.006 % of span)/K ?T amb *)potentiometer: ± 0.006 % of span/K ?T amb *) *) ?T
amb = ambient temperature change referenced to 23 °C (296 K)Influence of supply voltage < 0.01 % of span
Influence of load ≤ 0.001 % of output value per 100 ?
Reaction time
sensor burnout and sensor short circuit selected where appropriate
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s Electrical isolation
Output/supply, programming input
functional insulation acc. to IEC 62103, rated insulation voltage 50 V eff
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.Directive conformity Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006Conformity
Insulation coordination UL 61010-1Electromagnetic compatibility NE 21:2006Protection degree IEC 60529:2001
12-09-17 12:03D a t e o f i s s u e 2012-09-17223819_e n g .x m
l
Protection degree IP20
Mass approx. 130 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2Mounting
on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with Ex-areas
EC-Type Examination Certificate CESI 04 ATEX 143 , for additional certificates see https://www.doczj.com/doc/d89683168.html,
Group, category, type of protection ? II (1)GD, I (M1), [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ T amb ≤ 60 °C) [circuit(s) in zone 0/1/2]Input Ex ia IIC
Inputs terminals 1, 2, 3, 4, 5, 6 (for passive equipment)
Voltage U o 9
V Current I o
22 mA Power
P o 50 mW
Analog outputs, power supply, collective error
Maximum safe voltage U m 250 V (Attention! This is not the rated voltage.)Interface
Maximum safe voltage U m
250 V (Attention! The rated voltage is lower.), RS 232Statement of conformity
TüV 02 ATEX 1797 X , observe statement of conformity Group, category, type of protection, temperature class ? II 3G Ex nA II T4 [device in zone 2]Electrical isolation
Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V Directive conformity
Directive 94/9/EC EN 60079-0:2006, EN 60079-11:2007, EN 60079-15:2005, EN 60079-26:2007, EN 61241-0:2006, EN 61241-11:2006International approvals UL approval Control drawing 116-0316CSA approval
Control drawing 366-024CS-12 (cCSAus)IECEx approval IECEx TUN 07.0003
Approved for [Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I
General information Supplementary information
EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see https://www.doczj.com/doc/d89683168.html,.
12-09-17 12:03D a t e o f i s s u e 2012-09-17223819_e n g .x m
l
Power feed module KFD2-EB2
The power feed module is used to supply the devices with 24V DC via the Power Rail. The fuse-protected power feed module can supply up to 100 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical contact uses the Power Rail to transmit collective error messages.Power Rail UPR-03
The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35mm x 15mm. To make electrical contact, the devices are simply engaged.Profile Rail K-DUCT with Power Rail
The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables. Due to this assembly no additional cable guides are necessary.
Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
K-CJC-**
This removable terminal block with integrated temperature measurement sensor is needed for internal cold junction compensation for thermocouples. One K-CJC-** is needed for each channel.PACT ware ?
Device-specific drivers (DTM)Adapter K-ADP1
Programming adapter for parameterisation via the serial RS 232 interface of a PC/Notebook
For programming, please use the new version of adapter K-ADP1 (part no.181953, connector length 14mm). When using the previous version K-ADP1 (connector length 18 mm) the plug is exposed by approx.3 mm. The function is not affected.Adapter K-ADP-USB
Programming adapter for parameterisation via the serial USB interface of a PC/Notebook
Accessories