当前位置:文档之家› 办公楼弱电工程设计方案

办公楼弱电工程设计方案

目录

第一部分

1综合布线系统 ................................................................................................................................ 2

1.1系统总体设计原则 ................................................................................................................ 2

1.2设计依据 ................................................................................................................................ 2

1.3总体考虑 ................................................................................................................................ 2

1.4子系统设计 ............................................................................................................................ 31.5 设备间接地系统 .................................................................................................................... 4

1.6产品选择 ................................................................................................................................ 52视频监控系统 ................................................................................................................................ 8

2.1项目概况及需求分析 ............................................................................................................ 8

2.2设计依据: ............................................................................................................................ 8

2.3验收标准: ............................................................................................................................ 8

2.4前端设计 ................................................................................................................................ 8

2.5传输设计 ................................................................................................................................ 9

2.6终端设计 ................................................................................................................................ 9

2.7电源设计 ............................................................................................................................ 10

2.8接地系统 ............................................................................................................................ 10

2.9设备选型 ............................................................................................................................ 103防盗报警系统 ............................................................................................................................ 18

3.1设计依据: ........................................................................................................................ 18

3.2验收标准: ........................................................................................................................ 18

3.3系统设计方案 .................................................................................................................... 18

3.4传输设计 ............................................................................................................................ 26

3.5终端设计 ............................................................................................................................ 264LED显示屏系统 ......................................................................................................................... 27

4.1概述 .................................................................................................................................... 27

4.2LED发光元器件介绍 ......................................................................................................... 30

4.3小型LED电子显示系统 .................................................................................................... 32

4.4大型LED电子显示系统 .................................................................................................... 34

4.5本项目介绍 ........................................................................................................................ 36

4.6显示屏框架结构 ................................................................................................................ 39

1综合布线系统

1.1系统总体设计原则

本综合布线系统实施的目标是办公楼内计算机网络、通讯网络的统一布线和计算机资源的共享,,有力支持各种业务的开展。同时,提供多种信息需求并且保证整个网络的扩展升级,以适应未来更先进系统的应用。

本系统的物理拓扑结构为星型拓扑结构。

在本结构化综合布线系统方案设计中,我们将根据大楼的具体情况,全面考虑实际应用需求和未来的发展,系统结构上应能根据业务发展变化的需要灵活调整和扩展,易于维护管理;系统技术上以最新的国际标准为依据,充分考虑技术的先进性以支持未来高速网络应用的发展;遵循“多、快、好、省”的指导思想,提供智能大楼内部通信系统发展应用的坚实基础。

1.2设计依据

根据甲方提供的平面图并依据以下标准设计本方案。

目前综合布线系统惯用标准——CECS 92∶97和美国电子工业协会、美国电信工业协会的EIA/TIA为综合布线系统制定的一系列标准。

这些标准主要有下列几种:

? JGJ/T16-92——民用建筑电气设计规范

? GB/T50311-2000--建筑与建筑群综合布线系统工程设计规范

? GB/T50312-2000--建筑与建筑群综合布线系统工程验收规范

1.3总体考虑

网络中心和电话机房设在大楼第三层。根据滨海市水利基建管理处新办公楼弱电工程项目综合布线系统设计要求,综合布线系统将支持大楼内部计算机联网、办公自动化及内部电话网络。

水平语音、数据布线均采用超五类线(C5E UTP)传输数据和语音信号,可提供国际标准要求的100MHZ 的传输带宽;模块采用统一的RJ45标准接口(兼容RJ11);配线间设有19”标准机柜,所有线缆管理器件都为19”,方便管理。

本布线系统除地下一层外所有信息点汇集到三层电话机房,主要由工作区子系统、水平布线子系统和设备间子系统几个部分组成(具体参见下文介绍)。

信息点的布置原则为:

初期信息点的使用率按70%设计,在满足目前使用要求的基础上,充分考虑了将来的扩展性。

●办公室设置4组信息点(4个语音点和4个数据点),对于较大的办公室适当增加信息点数;

●会议室按6-8组信息点考虑,即使将来变为办公室也可提供充足的信息接入点。

●档案室考虑将来电子存档系统的发展,设置12组信息点,方便多人查询。

●其他房屋适当考虑设置1-2组信息点。

1.4子系统设计

由配线间到信息点全部采用超五类非屏蔽双绞线,且长度在90M范围之内。按照甲方要求地下室预留2根6芯光缆和1条25对大对数电缆,此处配线架安装于挂墙式机柜内,再经过交换机(未包含在本系统内)上联到中心机房。

1.4.1工作区子系统

工作区子系统由安装在各办公区的国际标准信息插座及其配套的86面板组成。

工作区子系统信息插座安装位置参见平面点位图,全部采用RJ45超五类非屏蔽模块(C5E)端接,每个工作区设置1组,即1个数据点和1个语音点。并统一安装在双口标准86面板上;信息出口遵循

EIA/TIA568A的连接标准。考虑到美观方便我们在每个处长室布置一个地插座,在一楼大堂服务台布置2个地插座。

1.4.2水平布线子系统

为保证网络的先进性、灵活互换性,水平子系统全部(数据、语音)采用能够确保高速数据传输的超五类非屏蔽双绞线。

水平线缆可从配线间引出,经金属线槽、铁管走线至各工作区。配线架与信息插座之间均为点到点端接,任何改变系统的操作(如增减用户,用户位置改变等)都不影响整个系统的工作,为系统线路故障检修提供极大方便。

1.4.3设备间子系统

设备间子系统设于大楼的电话机房,总配线架(包括语音总配线架、数据总配线架)、电信设备和计算机网络设备应集中放置于此。

设备间子系统所有配线架均安装在3个国产19”标准落地机柜中,并留有足够的空间,用以安装用户

网络集线器设备。该机柜正面安装玻璃门,使管理人员能够在不打开机柜的时候就可以看清面板上的跳线情况,看到网络设备的工作状态。由于机柜为全封闭型,使所有线缆(大对数双绞线和跳线)均被封闭在机柜内,无关人员不可能接触到布线系统,使系统的可靠性得到了极大的提高。数据水平线缆端接在24口快接式跳线盘上,由跳线跳接到交换机等网络设备;语音部分端接于110型配线架上,通过跳线与程控交换机连接。

设备间是整个配线系统的中心单元,它的环境条件的考虑是否恰当都直接影响到将来信息系统的正常运行及维护使用的灵活性。建议其室内照明不低于150Lux,并应提供UPS电源配电盘以保证网络设备运行及维护的供电。

设备间的环境条件建议如下:

1、将服务电梯安排在设备间附近,以便装笨重的设备。

2、室温应保持在18℃至27℃之间,相对温度保持在30%─55%。

3、保持室内无尘或少尘,通风良好,亮度至少达30英尺烛光。

4、安装合适的消防系统(如采用湿型系统,不要把喷头直接对准电气设备)。

5、使用防火门,至少能耐火1小时的防火墙和阻燃漆。

6、提供合适的门锁,至少要有一扇窗口留作安全出口。

7、设备间应注意避免电磁干扰和雷击,安装小于1Ω的接地装置;尽量远离存放危险物品的场所、强电和电磁干扰源(如发射机和电动机)。

8、设备间的地板负重能力至少应为500KG/平方米。

9、根据结构化布线系统的要求,在配线间安装布线硬件的墙壁上须覆盖涂有阻燃漆的3/4英寸(合1.9CM)厚的木板。

在配线间内应至少留有二个为本系统专用的,符合和办公照明要求的220V电压,电流10A单相三级电源插座。如果需要在配线间内放置网络设备,则还应根据接线间内放置设备的供电需求,配有另外的带4个AC双排插座的20A专用线路。此线路不应与其他大型设备并联,并且最好先连接到UPS,以确保对设备的供电及电源的质量。

1.5 设备间接地系统

本接地系统完全依照于中华人民共和国电子计算机房设计系统GB 50174-93规范进行实施。将机柜接地点用多芯铜制35M2\线缆引入汇流排,然后连接到建筑方做完的弱电接地盘上。本系统接地采取单点接地并同时采取等电位措施。

1.6产品选择

根据甲方要求,选用AVAYA综合布线产品。

1.6.1Avaya端对端PowerSUMTM超五类系统特点与功能

众所周知,自从TIA/EIA于1991年首先推出Catgory 5五类布线标准后,在近十年的时间里,综合布线的应用环境发生了天翻地覆的变化,传统五类系统在现在的高速网络环境中,特别是千兆以太网应用中,已无法满足用户使用的要求。为此,Avaya(原朗讯科技企业网络集团)于1996年10月首先端对端SYSTIMAX PowerSUM 超五类产品系列,以其优越精密的线对平行传输和阻抗匹配技术,使其UTP布线系统端对端(Point to Point)信道的衰减Attenuation,近端串音衰耗NEXT,ACR,EMI等指标,都大大超过TIA/EIA 568-B及ISO/IEC 11801行业标准。其独有的线缆和接插件匹配构造设计,更使其能在各种恶劣的安装环境下依然保持最佳的传输性能,多项的性能测试表明 PowerSum 系统不仅在衰减(Attenuation),近端串音衰减(NEXT)等性能指标上远远超离及其他系统,而且在实际应用中EMC各项指标亦超越等屏蔽电缆系统。

PowerSum系统具有如下的特点:

1.AVAYA公司的PowerSUM系列产品,其性能大大超过了TIA/EIA和ISO/IEC 11801对Catgory 5e标准产品的性能要求。随着国际标准的升级,超五类铜缆以其更高的性能逐渐成为市场的主流产品,目前正在逐步替代传统五类,但超五类标准在带宽要求上,仍与传统五类相同,达到100MHz。为了让用户获得最佳的性能价格比,AVAYA公司的PowerSUM系统,在信道带宽指标上,可以达到155MHz。大大超越了超五类国际标准的要求。

2.线对串扰一直是数字信号传输的最重要的破坏源,而用PowerSum 的计算方式,比传统的线对(Pair- to-Pair)的NEXT 性能测试值更准确严格,经证实朗讯科技PowerSum 产品系列有卓越的NEXT 性能表现,比其它的五类布线高出6-13dB ,因此其具有更强的抗干扰能力。

3.Powersun 系列产品是一整套端到端的系统解决方案, 其中包括110型及1100、PatchMax 超五类配线架,超五类UTP 线缆,D8CM 和110超五类快速跳线,MPS100E 信息插座,适用于室外环境的室外超五类线缆及其配套保安器件等Bell Labs 最新的技术,能使系统端对端总体SRL 性能及阻抗匹配获得最佳效果。

4.由于在抗串扰,平衡传输及阻抗匹配等技术方面获得重大突破朗讯科技SYSTIMAX PowerSum 系列能将传统的五类系统性能提高一倍,例如由Avaya 的PowerSum 产品安装的系统在100MHz 作端对端测试时ACR(信噪比)值超过20dB ,而其它厂家在广告上宣称的超五类线缆产品在100MHz 测试时ACR 值也仅为16dB.

5.由于具有极佳的ACR 及NEXT 性能指标值,使PowerSum 产品能支持发展中的网络并行传输方式,从而使在布线系统上传输高达622Mbps ATM 系统应用,而且经性能测试,PowerSum 材料还可提供550MHz 的模拟宽带视频应用, 而其它厂家的超5类产品只可达到仅为350MHz 的应用水平。

6.可实现最新的区域布线模式(Zone -Wiring),并且在100米范围内跳线长度无限制。 7.由于PowerSum 的高性能指标,其允许在单根8芯线缆内同时共享二个高速数据传输,使系统实现真正高性能的灵活性及可扩展性。

dB

155

Frequency (MHz) 100

P o w e r S u m has guaranteed performance out to 155MHz W O W !!!

Performance degrades when Channel NEXT

Competitor

“Claimed”

Equivalent

P o w e r S u m T r a n s m i s s i o n M a r g i n NEXT

P o w e r S u m

G u a r a n t e e d N E X T

UL实验室授予Avaya PowerSUM超五类布线系统证书PowerSUM 超五类(1061C+)四对线缆性能参数

Freq (MHz) Attu

dB/100m

PS NEXT

dB

NEXT

dB

ACR

dB/100m

ELFEXT

dB/100m

PS ELFEXT

dB/100m

0.772 1.7 70.0 72.0 70.3 78.0 76.0

1 1.9 68.3 70.3 68.4 75.8 73.8 4 3.8 59.3 61.3 57.5 63.7 61.7 8 5.4 54.8 56.8 51.4 57.7 55.7 10 6.0 53.3 55.3 49.3 55.8 53.8 16 7.7 50.3 52.3 44.6 51.7 49.7 20 8.6 48.8 50.8 42.

2 49.7 47.7 25 9.7 47.

3 49.3 39.7 47.8 45.8 31.25 10.9 45.9 47.9 37.0 45.9 43.9 62.5 15.8 41.

4 43.4 27.6 39.8 37.8 100 20.4 38.3 40.3 19.9 35.8 33.8 15

5 26.1 35.5 37.5 11.4 31.9 29.9 200 30.2 33.8 35.8 5.

6 29.

7 27.7 220 31.

8 33.2 35.2 3.4 28.

9 26.9 300 38.1 31.2 33.2 n/a 26.2 24.2 350 41.7 30.2 32.2 n/a 24.9 22.9

端对端PowerSum系统性能指标值

2视频监控系统

2.1项目概况及需求分析

滨海市水利基建管理处新办公楼共五层地下一层,主要用于内部办公。

在大厦内主要活动场所及重点区域(前厅、电梯内、走道、室外等)安装摄像机,向监控中心提供各监控现场的图像信息。监控中心采用硬盘录像,即方便即时监控,又可对监控资料进行存贮,方便以后资料的查询。系统可与报警系统、消防系统实现联动,即当有报警信号输入后,报警层的监控画面同时显示在电视墙上,便于保安人员监视情况。

2.2设计依据:

安全防范工程程序与要求GA/T75-94

安全防范系统通用图形符号GA/T74-94

防盗报警控制器通用技术条件GB12663-90

《智能建筑设计标准》GB/T50314-2000

《民用建筑电气设计规范》JGJ/TL6-92

《民用闭路监视电视系统工程技术规范》GB50198-94

甲方所提供的平面图纸

2.3验收标准:

本项目验收标准为:公安部《安全防范系统验收规则》GA308-2001

2.4前端设计

根据要求,本系统设置室外快球、室内匀速半球、室内半球和电梯轿厢专用摄像机,共14个监控点。

前厅

每层前厅设置一体化匀速半球形云台摄像机,可对通过主出入口、电梯及楼梯进出的各种情况进行全面实时监视,没有盲区。通过变焦及旋转可以清晰扑捉可视范围内的任何物体。考虑到前厅范围24小时会有照明设备,因此选择1LUX的摄像机,即使是很微弱的灯光也可满足需求。

走道

地下室设3台半球形摄像机,监视三个出入口。

一层走道两头均设置半球形摄像机,对进出办公区域公共走道情况进行监视。考虑到走道内24小时会有照明设备,因此选择1LUX的摄像机,即使是很微弱的灯光也可满足需求。

二层北侧走道尽头设置半球形摄像机,对进出办公区域公共走道情况进行监视。考虑到走道内24小时会有照明设备,因此选择1LUX的摄像机,即使是很微弱的灯光也可满足需求。

其他走道不设监控点。

电梯内

采用电梯专用的飞碟式黑白摄像机,体积小、隐蔽,适合在电梯狭小空间内使用,内置标配3.6mm 镜头,视场角92度,安装于与电梯操作面板对角的顶部,电梯内的一切置于保安监控系统下。

室外

选用彩色/黑白一体化高速球型摄像机,彩色转黑白、背光补偿等特性可以很好的适应室外和逆光等恶劣条件,利用多个预置位、巡航路线,可变速控制等特性,将室外情况完全掌控。再者考虑到其监控范围较大,监控对象较复杂,为了在出现意外情况下,摄像机能迅速定位也是采用一体化智能球的主要原因。同时配置多个红外灯辅助夜间照明。

2.5传输设计

所有视频信号采用同轴电缆SYV-75-5进行传输,控制线采用双芯带屏蔽双绞线RVVP2*1.0。各摄像机电源均采用集中从网络机房供电方式,强电电源线采用二芯护套线RVV2*1.0引至三层竖井,再从竖井变压后传到各监控点。

2.6终端设计

电视监控系统的主要控制设备位于三层网络机房,是整个系统的核心设备。所有前端设备均呈星型拓扑结构辐射到各前端设备现场。

●显示设备

监控室设置一台pc机配以解码卡,将硬盘录像机的压缩视频信号解码为模拟信号输出至4台21”纯平彩色监视器。

●控制及录像

硬盘录像机是本系统的主要控制设备。数字硬盘录像系统的主要功能如下:

?完成云台镜头控制

?将报警信号传至分控

?选择输入摄像机的图像

?可从多路摄像机的输入图像中任选一路或多路在屏幕上

?用硬盘对图像作数字化记录

?数字化硬盘存储及视频解压缩功能,可以完整的记录下摄像机的高清晰度画面,使画面回放时也能达到极高的清晰度

本项目选用一台16路。

硬盘录像机是监控中心的主要设备,前端摄像机传来的所有图像将在此进行综合管理和存贮。

可选择手动、动态检测或定时录像等模式,图像分辨率和帧率可调节,本方案配置可供以每路24小时实时录像1周左右,采用其它模式可以大幅度提高录像保存时间。

2.7电源设计

本系统主控部分采用单相交流220V、50HZ电源供电。在输入电流中,应避免混入脉冲干扰。系统配置交流稳压装置,功率为系统总功率的1.5倍。为防止供电电源意外停电或遭破坏,保证系统不间断工作,系统配置不间断电源(UPS)。同时配置了UPS前端防雷器及后端配电系统。

2.8接地系统

本接地系统包括监控和报警系统的保护接地和防雷接地提,完全依照于中华人民共和国电子计算机房设计系统GB 50174-93规范进行实施。将机柜接地点及避雷器接地点用多芯铜制35M2\线缆引入汇流排,然后连接到建筑方做完的弱电接地盘上。本系统接地采取单点接地并同时采取等电位措施。

2.9设备选型

主要设备选用成都科力监控产品。

成都科力电子研究所(成都科力实业有限公司)成立于1989 年,地处成都高新技术开发区,是成都市科委首批认定的高新技术企业。下设北京、上海、深圳分公司,武汉、西安、郑州、昆明、广西办事处、为国内一流专业生产安全防范系列产品的企业,公司具有独立的产品开发、研究、生产制造能力,技术水平在同行业居领先地位,近几年来,科力以“创CCVE 领域国内第一品牌”为目标,瞄准国际同类产品先进水平,独立开发了代表当今先进水平的MPEG-4 数字硬盘录像机、矩阵切换监控系统、多媒体监控系统、城市交通集中监控系统和双向控制闭路电视教学系统等多个系列产品,其中“ MPEG-4 数字硬盘录像机” 2002 年获国家级重点新产品证书。“双向控制闭路电视教学系统”获国家级火炬计划项目证书。目

前科力已成为国内矩阵监控领域生产品种最多、最全的企业,产品用户遍及作全国各地。长期以来,科力依靠自身雄厚的科技力量,独立开发、生产的CCVE 产品,其中“ M 系列矩阵切换监控系统”在国内首家通过公安部检测(公沪委检字第97029 号),其性能与国外先进产品相当。产品现已在全国金融、商业、工业、交通、饭店、文物、教育、司法等行业的逾千个工程中成功使用,多年来一直倍受用户赞誉及信赖,市场占有率稳步提高。

2.9.1室外一体化智能球

选用MTR640BW高速彩色—黑白自动转换一体化球形摄像机

◆豪华型外型观设计

◆精致5英寸球罩,更小巧

◆外形更具有隐蔽性

◆自动光圈自动对焦功能

◆水平清晰度480线

◆ 360℃水平连续旋转

◆水平速度0.5-250°/秒

◆垂直速度0.5-130°/秒

◆ 80个预置点

◆内置解码器RS485通讯

◆ 18倍超大变焦功能f4-88mm

◆ 1 Lux/0.01Lux最低照度

◆两预点之间线扫功能

◆ 4条可编程巡视轨迹,轨迹速度可达250°/秒

◆ DC 12V输入

技术指标

有效像素752(H)×582(V)

图像感应器 3.6mm(H)×2.71mm(V); 1/4inch 视频输出 1.0Vp-p

水平清晰度480TVL

信噪比≥50dB

最低照度1Lux/0.01Lux

光圈自动

对焦自动

焦距长度f4.1-73.8mm

倍率18倍×4

白平衡自动

背光补偿自动

左右旋转范围360°连续旋转

左右速度0.5-250°/秒

上下旋转范围0-90°

上下速度0.5-130°/秒

通讯RS485

控制上下、左右;镜头变倍;80个预置位左右线扫开 / 关

巡视轨迹 4 条

电源DC12V 2A

操作温度0-40℃

尺寸Φ134×175mm (H)

重量约 5Kg

2.9.2室内匀速半球

选用MTR630彩色一体化半球形摄像机

◆无变形6英寸球罩

◆低噪音设计,适用室内安装

◆自动光圈自动对焦功能

◆水平清晰度450线

◆360°水平连续旋转

◆水平速度0.5-100°/秒

◆垂直速度0.5-100°/秒

◆ 32个预置点

◆内置解码器RS485通讯

◆ 16光学变焦2倍电子放大

◆ 1Lux最低照度

◆两预点之间线扫功能

◆ 1条可编程巡视轨迹,轨迹速度可达100°/秒

◆ DC 12V输入

技术指标

有效像素752(H)×582(V)

图像感应器 3.6mm(H)×2.71mm(V); 1/4inch

视频输出 1.0Vp-p

水平清晰度450TVL

信噪比≥48dB

最低照度1Lux

光圈自动

对焦自动

焦距长度f3.9-63mm

倍率16倍×2

白平衡自动

背光补偿开 / 关

左右旋转范围360°连续旋转

左右速度0.5-100°/秒

上下旋转范围0-90°

上下速度0.5-100°/秒

通讯RS485

控制上下、左右;镜头变倍;32个预置位

左右线扫开 / 关

巡视轨迹 1 条

电源DC12V 2A

操作温度0~40℃

尺寸Φ176×185mm (H)

重量约 1.5Kg

2.9.3硬盘录像机

TM62系列数字硬盘录像机采用MPEG-4 压缩方式,支持 1-24路音、视频全实时监看、录像。最大输入为 64路音、视频。适用于各种音视频监控、远程图像传输及视讯会议等领域。

1.TM6264系列数字硬盘录像系统采用音、视频同卡,保证了音、视频完全同步。

2.采用 MPEG-4压缩方式,动态分配码流,相对MPEG-1、MPEG-2等压缩方式,数量仅为其1/8-1/2,数据量大小与画质设定级别、画面动态情况等有直接关系,如:普通画质时,每小时录像文件为100-180MB,静止画面时,每小时录像文件低于100MB。

3.数据压缩使用专用高速 DSP芯片实现,占用极少的计算机CPU资源,可以使用低CP如:Celeron733等,和其他同类产品相比,节约成本,并且可以实现图像实时回放。

4.1-24路音、视频实时录像、回放。音、视频完全同步,回放功能齐全。

5.单画面使用超高清晰度( 704*576)显示,单画面、多画面切换;多画面为一般清度(352*288)显示,具有多种显示模式。回放具有局部放大功能。

6.支持时钟、标题字符叠加。时钟可以选择部分显示或全部显示,标题可以修改。

7.带云台控制功能,具有报警联动录像功能,可以报警联动输出。

8.录像方式灵活,有手动、定时、报警等录像方式。

9.支持每路 99个区域的视频移动报警。灵敏度可调。

10.按设定的录像天数自动删除、覆盖,容量不足时告警。

11.历史操作记录保留备查。

12.支持各种网络,如: LAN、Internet、PSTN、ISDN等。可以远程控制、回放、下载、录像等。13.可控制 M系列矩阵切换主机。

14.可与 TM1608报警输入接口箱连接,实现报警联动录像。

15. 与 M800CIA-T/TK配套使用,实现对前端摄像机和云台的控制。

2.9.4红外灯

红外发光二极管矩阵发光体,低耗高效、寿命长。

L00系列850nm有轻微红暴。

铝合金外壳,全密封结构、适用于室内外,20Lux光控自动开关,白天不工作、夜间或可见光不足时红外灯自动打开。

DC12V或DC14V供电,由电网AC220V供电,电网电压波动范围在AC100~245V,都可稳定可靠工作。直流供电时,因红外管对电源电压十分敏感,对供电电压有较严格要求,供电电压高于额定电压可能使红外管过负荷而燃坏,低于额定电压可能使红外灯发光功率不足。

·可上下左右全方位调整

·电源导线与外壳之间绝缘电阻大于10 MΩ,AC500V介电强度试验1分钟无击穿或闪

作为红外夜视系统的重要组成部分的红外灯,对摄像机、镜头、电源、防护罩等有配套性要求,上述红外灯的辐照距离的测试条件为采用1/2″、0.02Lux最低照度、自动电子快门摄像机;1/2″、F1.2、相应焦距f的镜头、光圈最大时,防护罩的视窗玻璃为无自动除霜镀膜的光学玻璃。

L00系列红外灯参数见下表:

型号L20 L50 L70 L100 L150

电源DC12V DC12V DC12V DC14V

固定配有AC/DC电源一个,由电网电压 AC220V供电,与红外灯统调,

在电网电压波动在AC100V-245V时,红外灯均能稳定可靠工作。

功率6W 10W 20W 40W 70W

有效照射

距离

20米50米70米100米150米

照射角度45° 45°(加漫射玻璃在室内能达80°,但影响辐照距离)

波长850nM,有轻微红暴

外壳

钢外壳,密封结

构,室内外用

铝合金外壳,密封结构,室内室外均可用

光敏开关无光敏开关,20Lux可调

方位调整可上下左右全方位调整

重量350g 425g 1.16kg 1.5kg 1.7kg

尺寸76×128×146m125×30×98m173×165×130mm 250×205×150mm 258×210×135mm

m m 安装单镙钉或二镙钉安装

3防盗报警系统

防盗报警系统主要由报警传感器、报警控制器和信号传输部分组成。防盗器材最重要的部分是探测器,其灵敏度与稳定性决定系统是否能及时报警却又不发生误报。本工程采用了双鉴探头和门窗磁。

3.1设计依据:

安全防范工程程序与要求GA/T75-94

安全防范系统通用图形符号GA/T74-94

防盗报警控制器通用技术条件GB12663-90

《智能建筑设计标准》GB/T50314-2000

《民用建筑电气设计规范》JGJ/TL6-92

甲方所提供的平面图纸

3.2验收标准:

本项目验收标准为:公安部《安全防范系统验收规则》GA308-2001

3.3系统设计方案

防盗报警系统的选型首先要对防盗报警器的技术指标有所了解,对报警器的质量、效率及经济性各方面作出一定评价的比较通用的性能指标如下:探测率及误报率、警戒范围、报警传递方式、最大传输

距离、工作时间、探测灵敏度、功耗、工作电压、工作电流和环境温度。

除此之外,防盗报警系统设计应遵循如下原则:

●设备及系统在技术上应为主流成熟产品;

●系统应与电视监控系统有联动接口;

●设备必须具有高度的可靠性;

●系统应有足够的冗余度,以利扩展。

3.3.1双鉴探测器

在所有处长室及财务室设置双鉴探测器,在布防阶段有人闯入时,保安中心能及时收到报警信号,确保将其损失减小到最低。

双鉴探测器它是将两种探测技术(微波、被动红外)结合在一起,以“相与”的关系来触发报警,即只有当两种探测器同时或者相继在短暂的时间内都探测到目标时,才可发出报警信号,因此能够有效降低误报率。此外,当双鉴器中有一个失效发生故障时,也可发出报警信号,从而避免因一个探测器损坏时可能造成的漏报警。

本项目选用安定宝BT6360STC

产品说明:

微处理器控制(MAP)

微波/被动红外技术

内置诊断和监控

360°探测视区,安装高度为2.4m~4.9m,嵌合式或表面安装

微处理器自动在上电时启动自检

自检确认故障后,由故障输出输出故障情况

产品规格:

外观尺寸:13cm H x 13cm W x 6cm D;重量:397g

电源要求:10-12.9VDC;40mA,12VDC(典型)

故障输出:集电极开路;集电极与发射器之间的电压为3V@50mA

报警继电器:励磁C型(N.O./N.C.)干簧继电器,标称125mA@25VDC

指令输入:启动自检;启动:0-1.5V(低电压);不启动:5V以上(高电压);阻抗:110K(最小) 微波频率:中波段10.525GHz(USA)

防拆开关:天花板和外盖防拆;A型(常闭)开关,标称:25mA/30VDC

工作温度:0℃~49℃;5%~95%相对湿度,无霜

抗RF干扰:30V/m,10MHz~1000MHz

被动红外抗白光干扰:900Lux

探测范围:直径15米,半径7.6米

被动红外视区:(8′-11′透镜组合)3个360°区域;远区:36;中区:24;低区:16;俯视区:1;

(12′-16′透镜组合)2个360°区域;远区:40;中区:20;俯视区:1

灵敏度:探测视区内2-4步

3.3.2门窗磁

按照甲方要求,三层财务室的所有门和窗上安装门窗磁。当有未经授权的人闯入时可以及时的向保安监控中心进行报警。

3.3.3红外对射

在五层外檐安装一周红外对射,防止非法人员从屋顶爬下。

选用日本艾立富ABT-40。

1.抗强光达50,000LUX,内置自动调节强光过滤系统,避免受强光或汽车灯光的影响独特的光

学设计:

2.光电射束可穿透多层玻璃特殊的抗环境(如雨雪)等能力

3.当遇到浓雾或天气恶劣时探测器会自动增强灵敏度(AGC电路)

4.可选菲涅尔或双元非球面二次聚焦光学透镜实现了大口径光柱

5.自动环境识别电路(EDC),可以避免墙壁等反光干扰、模块化的设计便于探测器的添加及层叠

6.水平/垂直光学角度调整方便,易于校准、具有高水准的抗RFI/EMI能力

7.独特的数字滤波电路设计、感光余裕度达99%、内置光学瞄准镜、防雷击电路设计

8.使用C型继电器输出、射束遮断周期可调使其更加灵活适应性更强

相关主题