2 Pfg 1169/08.2007 Requirements for

cables for use in photovoltaic-systems

Contents

Seite Foreword (3)

1Scope (3)

2Normative references (3)

3Terms and definitions (5)

4Halogen-free PV-cable (6)

4.1Code designation (6)

4.2Characteristics (6)

4.3Construction (6)

4.4Test (8)

4.5Guideline for use (informative) (8)

4.6Current carrying capacity (8)

Annex A (normative) Test of mutual influence (15)

Annex B (normative) Test of absence of halogen (16)

Annex C (normative) Determination of halogens – Elemental test (17)

Annex D (normative) Test of long term resistance of insulation to D.C (19)

Annex E (normative) Cold impact test (20)

Annex F (normative) Dynamic penetration test (21)

Annex G (normative) Notch propagation (23)

Figure 1 – Arrangement of marking (8)

Figure F.1 – Arrangement for penetration test (22)

Table 1 – Current carrying capacity of PV-cables (9)

Table 2 – Conversion factor for deviating temperatures (9)

Table 3 – Tests for halogen free PV-cable (10)

Table 4 – Requirements for halogen free insulation and sheath compounds (13)

Table A.1 – Requirements (15)

Table B.1 – Test method, measurement, requirements (16)

Table B.2 – Test sequence (16)

Table E.1 – Parameter for cold impact test (20)

Foreword

This test specification contents the requirements listed in a manuscript of the working group AK 411.2.3 …Leitungen für PV-Systeme“ of the German committee for standardization (DKE). This manuscript is intended to be published as German pre-standard. Up to the date of publishing of the pre-standard this test-specification of TUV Rheinland will be used for test and assessment of cables for use in PV-systems (PV-cables).

1 Scope

2 PfG 1169/08.2007 applies to flexible single-core cables (cords) for use at the DC-side of photovoltaic-systems with a maximum permissible voltage of DC 1,8 kV (conductor/conductor, non earthed system). The cables are suitable for use in safety class II.

It is permitted to connect these cables as multiple-construction.

The cables are intended to operate at ambient temperature until 90°C

2 Normative references

The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60364-5-52, Erection of low voltage installations –Part 5: Selection and erection of electrical equipment –Chapter 52: Wiring systems

EN 50267-2-1, Common test methods for cables under fire conditions – Tests on gases evolved during combustion of materials from cables – Part 2-1: Procedures – Determination of the amount of halogen acid gas;

EN 50267-2-2, Common test methods for cables under fire conditions – Tests on gases evolved during combustion of materials from cables – Part 2-2: Procedures – Determination of degree of acidity of gases for materials by measuring pH and conductivity;

EN 50305, Railway applications – Railway rolling stock cables having special fire performance – Test methods

EN 50395, Electrical test methods for low voltage energy cables;

EN 50396, Electrical test methods for low voltage energy cables;

EN 60068-2-78, Environmental testing - Part 2-78: Tests -Test Cab: Damp heat, steady state (IEC 60068-

2-78)

EN 60216-1, Electrical insulating materials - Properties of thermal endurance - Part 1: Ageing procedures and evaluation of test results (IEC 60216-1);

EN 60216-2, Electrical insulating materials – Thermal endurance properties – Part 2: Determination of thermal endurance properties of electrical insulating materials – Choice of test criteria (IEC 60216-2);

EN 60228, Conductor of insulated cables (IEC 60228)

EN 60332-1-2, Tests on electric and optical fibre cables under fire conditions – Part 1-2: Test for vertical flame propagation for a single insulated wire or cable – Procedure for 1 kW pre-mixed flame; (IEC 60332-1-2)

EN 60684-2, Flexible insulating sleeving – Part 2: Methods of test (IEC 60684-2)

EN 60811-1-1, Insulating and sheathing materials of electric cables – Common test methods Part 1-1: General application – Measurement of thickness and overall dimensions – Test for determining the mechanical properties (IEC 60811-1-1)

EN 60811-1-2, Insulating and sheathing materials of electric and optical cables – Common test methods. Part 1-2: General application. Thermal ageing methods (IEC 60811-1-2)

EN 60811-1-3, Insulating and sheathing material of electric and optical cables – Common test methods – Part 1-3: General application – Methods for determining the density – Water absorption tests – Shrinkage test (IEC 60811-1-3)

EN 60811-1-4, Insulating and sheathing materials of electric and optical cables – Common test methods. Part 1-4: General application. Tests at low temperature. (IEC 60811-1-4)

EN 60811-2-1, Insulating and sheathing materials of electric and optical cables – Common test methods – Part 2-1: Methods specific to elastomeric compounds – Ozone resistance, hot set and mineral oil immersion tests (IEC 60811-2-1)

EN 60811-3-1, Insulating and sheathing materials of electric cables – Common test methods Part 3-1: Methods specific to PVC compounds – Pressure test at high temperature, test for resistance to cracking (IEC 60811-3-1)

HD 22.13, Rubber insulated cables of rated voltages up to and including 450/750 V Part 13: Single and multicore flexible cables, insulated and sheathed with crosslinked polymer and having low emission of smoke and corrosive gases;

HD 605, Power cables – Part 605: Additional test methods

HD 60364-7-712Electrical installations of buildings – Part 7-712: Requirements for special installations or locations – Solar photovoltaic (PV) power supply systems (IEC 60364-7-712, modified)

3 Terms and definitions

For the purposes of this document, following definitions apply.

3.1 Terms for test procedure

3.1.1

Type test (symbol T)

Tests required to be made before supplying a type of cable covered by this standard on a general commercial basis, in order to demonstrate satisfactory performance characteristics to meet the intended application. These tests are of such a nature that, after they have been made, they need not be repeated, unless changes are made in the cable materials or design or manufacturing process which might change the performance characteristics.

3.1.2

sample tests (symbol S)

Tests made on samples of completed cable or components taken from a completed cable, at a specified frequency, so as to verify that the finished product meets the specified requirements.

3.1.3

Routine tests (symbol R)

Tests made by the manufacturer on each manufactured length of cable to check that each length meets the specified requirements

3.2

Rated voltage

The rated voltage of the cable determines the construction and the tests of the cable with regard to the electrical properties.

The rated voltage is designated by two values of frequency voltage: U0/U in Volt

U0 rated power frequency voltage between conductor and earth (metallic screen of cable or ambient medium);

U rated power frequency voltage between two conductors of a multipole cable or of a system of single core cables.

The rated voltage of the cable for a given application shall be suitable for the operating conditions in the system in which the cable is used.

This requirement is applicable for both U o and U

The rated voltage between two conductors in a DC-system shall not exceed the 1,5 time value of rated voltage U of the cable, and the rated voltage between conductor and earth shall not exceed the 1,5 time value of rated voltage U o of the cable.

NOTE The operating voltage of a system may exceed is rated voltage permanent for 20%. A cable may be operated with a voltage which value is 20% higher than rated voltage under condition that the rated voltage is not less than the rated voltage of the system.

3.3

DC side

part of a PV installation from a PV cell to the DC terminals of the PV inverter

3.4

open-circuit voltage under standard test conditions U OC STC

voltage under standard test conditions across an unloaded (open) PV module, PV string, PV array, PV generator or on the DC side of the PV inverter

3.5

short-circuit current under standard test conditions I SC TC

short-circuit current of a PV module, PV string, PV array or PV generator under standard test conditions

4 Halogen free PV-cable

4.1 Code designation

PV1-F

4.2 Characteristics

4.2.1

Rated voltage

AC U 0/U 0,6/1 kV

DC 1,8 kV (conductor-conductor, non earthed system, circuit not under load).

If the cable is used in DC-systems the rated voltage between two conductors shall not exceed the 1,5 time value of rated voltage U of the cable. In with single-phase earthed DC-systems this value shall be multiplied with factor 0,5. 4.2.2

Temperature range

Ambient temperature:

–40 °C to +90 °C Max. temperature at conductor:

120 °C

The cables are intended to operate at ambient temperature until 90°C. For this a temperature index of

120°C applies to the insulation and the sheath, bas ed on EN 60216-1 (20.000h, 50% residual elongation). Note

The expected period of use is 25 years.

The permitted short-circuit-temperature refer to a period of 5s is 200°C.

4.3 Construction

4.3.1

Conductor Number of conductors: 1

The conductor shall be class 5, according to EN 60228. The single wires must be tinned. Preferred diameters: 2,5, 4, 6, 10, 16 mm 2

4.3.2

Separation layer

A separation layer of a suitable halogen free material may be applied around the conductor.

额定电压

导体工作温度

导体

绝缘

4.3.3 Insulation

The insulation shall be a suitable halogen free material applied around the conductor.

The insulation shall be extruded and shall consist of one or several adjacent adherent layers. It shall be solid and homogeneous, it must be possible to remove it without damage to the insulation itself, to the conductor and to the tin coating.

The insulation shall be smooth, consistently applied and largely circular. Compliance shall be checked by inspection and by manual test.

The wall thickness of insulation is specified by the manufacturer, but it must not fall short of the minimum value of 0,5mm.

4.3.4 Separation layer

A separation layer of a suitable halogen free material may be applied around the insulation.

4.3.5 Sheath

The core must be covered by a sheath.

The sheath around the core must be of a suitable halogen free material.

The sheath shall be extruded and shall consist of one or several adjacent adherent layers. The sheath shall be smooth and consistently applied.

The wall thickness of sheath is specified by the manufacturer, but it must not fall short of the minimum value of 0,5mm.

4.3.6 Outer diameter

The average value of the outer diameter shall be within the limits specified by the manufacturer.

4.3.7 Multiple construction

Each single-core cable in a multiple construction shall pass the requirements of this document. Each additional component in a multiple construction shall pass the requirements of this document.

4.3.8 Marking

4.3.8.1 General

The cable shall be marked as follows:

a) Trademark;

b) Code designation;

c) Rated diameter.

Marking may be by printing or by reproduction in relief on or in the sheath.

4.3.8.2 Trademark

Cables shall be provided with an indication of the manufacturer, which consist of a consecutively marking with company name or company sign or with (if trademarked) an identification number.

4.3.8.3 Code designation

Cables shall be provided with an code designation according to 4.1 applied consecutively on sheath.

4.3.8.4 Arrangement of marking

Each marking is considered as consecutive if the spacing between the end of a marking and the begin of the following identical marking does not exceed following value:

– 550mm, for marking on sheath or outer jacket.

Following figure shows an example of marking on sheath.

Figure 1 – Arrangement of marking

4.3.8.5 Durability

Printed markings shall be durable. Compliance with this requirement shall be checked by the test given in 5.1 of EN 50396.

4.3.8.6 Legibility

Each marking shall be legible.

4.4 Test

Compliance with the requirements of 4.3 shall be checked by visual inspection and tests according to table

3.

4.5 Guideline for use (informative)

Cables according to this standard are intended for use in PV-systems according to EN 60364-7-712.

4.6 Current carrying capacity

Ambient temperature: 60°C

Max. temperature at conductor: 120 °C

Table 1 – Current carrying capacity of PV-cables

Kind of installation

Rated diameter Single cable free in

air Single cable on

surfaces

To cables adjacent on

surfaces

mm2 A A A

1,5 30 29 24

2,5 41 39 33

4 5

5 52 44

6 70 6

7 57

10 98 93 79

16 132 125 107

25 176 167 142

35 218 207 176

Table 2 – Conversion factor for deviating temperatures

Ambient temperature Conversion factor

°C

Up to 60 1,00

70 0,91

80 0,82

90 0,71

100 0,58

110 0,41

Reduction factor for accumulation according to IEC 60364-5-52, Table B.52-17

Table 3 – Tests for halogen free PV-cable

No. Test Requirements

of test standard clause

5 Resistance against acid and alkaline

solution

T EN 60811-2-1 10 5.1Chemical stress

acid: N-Oxal-acid

alkaline solution: N-sodium hydroxide solution

temperature °C 23

duration h 168

5.2Tensile strength:

variation, max. % ± 30

5.3Elongation at break, min. % 100

6 Test of influence T Annex A

7 Cold impact test at –40 °C T Annex E

8 Cold bending test

Diameter of cable < 12,5 mm

T EN 60811-1-4 8.2 8.1 Test conditions:

– temperature °C –40 ± 2

– duration of conditioning h 16 EN 60811-1-4 8.2.3 8.2 Results to be obtained Absence of

cracks

9 Cold elongation test

Diameter of cable ≥ 12,5 mm

Table 3 10 Ozone resistance at complete cable T

10.1 Method B EN 50396 8.1.3

– temperature °C 40 ± 2

– relative humidity % 55 ± 5

– duration h 72

– Ozone concentration %

(by volume)

(200 ± 50) × 10–6

10.2 Results to be obtained Absence of

cracks.

11 Weathering/UV-resistance T HD 605/A1 2.4.20 11.1 Conditions:

– duration h 720

– temperature °C

(Black-Standard-temperature)

63

– relative humidity % 65

– min. power at W/m2

wavelength 300 nm to 400 nm

60 ± 2

– duration spraying/drying min 18/102

Results to be obtained Absence of

cracks.

12 Dynamic penetration test T Annex F

13 Notch propagation T Annex G

No. Test Requirements

of test standard clause

14 Shrinkage test at complete cable T EN 60811-1-3 11((sheath)) 14.1 Conditions:

– temperature °C 120

– duration h 1

– Distance L of sample mm 300

14.2 Results to be obtained:

– Maximum shrinkage. % 2

15 Test under fire conditions

15.1 Test for vertical flame propagation at complete

cable

T, S EN 60332-1-2

15.2 Assessment of halogen T, S

15.2.1 Absence of halogen Annex B 15.2.2 Determination of halogens – Annex C

Table 4 – Requirements for halogen free insulation and sheath compounds

1 2 3 4 5 6 7

Test method described in Type of compound

Ref. No. Test Unit

standard clause insulation sheath

1 Mechanical characteristics

1.1 Properties before ageing EN 60811-1-1 9.2

1.1.1 Values to be obtained for the tensile strength:

– median, min. N/mm26,5 8,0

1.1.2 Values to be obtained for the elongation at

break:

– median, min. % 125 125 1.2 Properties after ageing in oven EN 60811-1-2 8.1

1.2.1 Ageing conditions:

– temperature °C 150 ± 2 150 ± 2 – duration of treatment h 7 × 24 7 × 24 1.2.2 Values to be obtained for the tensile strength:c

– median, min. N/mm2– – – variation, max. % –30a–30a

1.2.3 Values to be obtained for the elongation at

break:c

– median, min. % – – – variation, max. % – 30a– 30a 1.3 Hot set test d EN 60811-2-1 9

1.3.1 Conditions

– Temperature °C 200± 3 200± 3 – Time under load min 15 15 – mechanical stress N/cm220 20 1.3.2 Values to be obtained

– elongation under load, max. % 100 100 – permanent elongation after cooling, max. % 25 25 1.4 Thermal endurance properties EN 60216-2

1.4.1 Conditions

Either test of elongation at break or bending test

shall be performed.

– Temperature index 120 120 – elongation at break c% 50 50 – bending test EN 50305 7.2 2 D 2 D 1.5 Cold elongation test EN 60811-1-4 8.4

1.5.1 Conditions:

– temperature °C –40 ± 2 –40 ± 2 – duration h EN 60811-1-4 8.4.4 und 8.4.5 b b 1.5.2 Values to be obtained:

– elongation at break, min. % 30 30

1 2 3 4 5 6 7

Test method described in Type of compound

Ref. No. Test Unit

standard clause insulation sheath

a No positive value for variation fixed.

b See test method in column 4 and 5.

c This test shall be performe

d at test samples of insulation and sheath compound.

d This test shall b

e performed only at cross-linked insulation and sheath compound

Test of mutual influence

A.1 Conditions

Test samples must be aged for 7 days at (135 ± 2) °C at conditions according to table 2

A.2 Requirements

After ageing the insulation and the sheath shall pass the requirements of table A.1.

Table A.1 – Requirements

Tests units insulation sheath

Tensile strength – median, min. N/mm2– –

– variation a, max. % ± 30 –30 b Elongation at break – median, min. % – –

– variation a, max. % ± 30 ± 30

a Variation: difference between the median value obtained after ageing and the median value obtained without ageing expressed as a

percentage of the latter.

b Positive tolerances are not limited.

Test of absence of halogen

B.1 Requirements of extruded materials

Insulation and sheath shall pass the requirements as follows: a) Type test

The material must be tested as described in table B.1.

Table B.1 – Test method, measurement, requirements

Test method

Measurement

requirements

1 EN 50267-2-

2 pH and conductivity pH ≥ 4,

3 und

conductivity ≤ 10 μS/mm a 2 EN 50267-2-1 Chlorine- and Bromine content, expressed in HCI ≤ 0,5 %

3a

Annex C

Halogen: Fluoride

If negative the test should be finished. No further test is necessary.

The material shall be accepted.

If positive, test of 3b shall be performed 3b

EN 60684-2

Fluoride content

≤ 0,1 %

a If discrepancies regarding conductivity appear, e.g. the recommended value is exceeded even if there is compliance with the

recommended ph-value, other test method may be applied after agreement with all participants.

b) Selection test

The material shall be tested according to test sequence of table B.2.

Table B.2 – Test sequence

Test method Measurement

Value Result

If negative the test should be finished. No further test is necessary.

The material shall be accepted. Phase 0 HD 22.13,

Annex C

Halogen: Fluoride, Chloride and Bromide

If positive continue with phase 1.

< 4,3 The material shall be revised. pH ≥ 4,3

Conductivity shall be tested. conductivity ≤ 2,5 μS/mm

The material shall be accepted. No further test is necessary.

conductivity > 10 μS/mm The material shall be revised.

Phase 1 EN 50267-2-2 conductivity (s)

> 2,5 μS/mm but ≤ 10 μS/mm Test according to EN 50267-2-1 shall be performed > 0,5 % The material shall be revised.

Phase 2 EN 50267-2-1

Chlorine- and Bromine content, expressed in HCI

≤ 0,5 % Test according to EN 60684-2 shall be performed. > 0,1 % The material shall be revised. Phase 3 EN 60684-2

Fluoride content

≤ 0,1 %

The material shall be accepted.

Determination of halogens – Elemental test

Warning

Owing to its potentially hazardous nature, the fusion operation should be carried out in a fume cupboard, using a safety screen.

C.1 Equipment

Bunsen burner

3 small/medium soda glass test tubes (approximately 50 mm x 10 mm)

Test tube holder

Evaporating basin/mortar

Wire gauze;

Funnel

Filter paper

C.2 Materials

Unknown sample

Sodium metal

Dilute nitric acid (5 %)

Aqueous silver nitrate (5 %)

Dilute ammonia (10 %)

Freshly made up zirconium-alizarin red S reagent

Glacial acetic acid

Acid/pH indicator papers

C.3 Procedure

C.3.1 Sodium fusion

Place 200 mg – 250 mg of the sample into the bottom of a small soda glass test tube. Add 10 ml of distilled/de-ionized water to the evaporating basin and place this in the fume cupboard behind the safety screen. Whilst holding the test tube firmly with the test tube holder at an angle of 45° - 60° to the vertical, introduce a piece of freshly cut, clean sodium (about the size of a small pea) (200 mg – 250 mg) into the mouth of the test tube without allowing it to come into contact with the sample. With the safety screen in place, heat the sodium gently until it melts and runs down on to the sample (there may be a vigorous reaction when the molten sodium reaches the sample if halogens are present). Heat the tube gently for about 1 min, then more strongly until the lower 20 mm of the tube glows red hot. Plunge the red hot tube into the water in the evaporating basin, immediately placing the gauze on top. (The gauze prevents any loss of material when the tube shatters on contact with the water.) Allow any non reacted sodium to react before grinding up the solution and glass. Filter, and separate the filtrate into two equal portions.

C.3.2 Chlorine and bromine

To the first portion of the filtrate, add sufficient nitric acid to make the solution acidic. Boil this solution until its total volume has been reduced by half (this is to remove any HCN or H2S, if present, which would interfere with the test). Add 1 ml silver nitrate solution; a white or yellowish-white precipitate indicates the presence of halogen (Cl, Br) in the original sample. (If the liquor is decanted, and the precipitate is white and readily soluble in dilute ammonia, then chloride is present.)

C.3.3 Fluorine

To the second portion of the filtrate, acidify with glacial acetic acid. Boil this solution until its total volume has been reduced by half. Add 2 to 3 drops freshly prepared zirconium lake reagent (equal volumes of: a) Alizarin solution: 0,05 g Alizarin Red-S in 50 ml distilled water, b) Zirconium solution: 0,05 g zirconium nitrate in 10 ml concentrated HCl diluted with 50 ml distilled water). Heat at 40 °C for 1 h. The presence of fluoride is indicated by the red/pink colouration being bleached to yellow.

Test of long term resistance of insulation to D.C.

A test sample with a length of minimum 5m shall be immersed into water containing 3 % NaCl. Further on minimum 300mm of the sample shall stick out of the water. The water-bath shall be retained for (240 ± 2) h at a high temperature of (85 ± 2) °C and a D.C.-vol tage 0,9kV shall be applied between conductor and water whereby the conductor shall be connected to the positive potential.

The current of this circuit shall be measured with a period of not more than 24h. If possible a continuous measurement shall be preferred.

The measured values shall be recorded in a time-current-curve which identifies a stable progress.

NOTE A stable progress is e.g. an increase of less than 10% of leakage current on the average for a time of 24h (This is part of the inspection based on practical experiences)

After storing the samples shall be taken out of the salt-water-solution and a voltage test according to Ref.-No. 1.2 of table 1 shall be performed. The test voltage shall be the rated voltage (U) of the cable.

Cold impact test

The cold impact test shall be performed at –40°C ac cording to clause 8.5 of EN 60811-1-4, but the mass of hammer, the mass of test probe and the height shall comply with table 2.

Table E.1 – Parameter for cold impact test

Diameter of cable (D) Mass of hammer Mass of test probe height mm g g mm

D < 15 1 000 200 100

15 < D≤ 25 1 500 200 150

D > 25 2 000 200 200

The inner and outer surface of sheath shall be inspected with normal or corrective visual faculty without magnification. Only the outer surface of the insulation shall be inspected. No cracks must be determined

《光伏发电系统专用电缆产品认证技术规范》

《光伏发电系统专用电缆产品认证技术规范》 编制说明(申请备案稿) 1.背景 世界常规能源供应短缺危机日益严重,化石能源的大量开发利用已成为造成自然环境污染和人类生存环境恶化的主要原因之一,寻找新兴能源已成为世界热点问题。在各种新能源中,太阳能光伏发电具有无污染、可持续、总量大、分布广、应用形式多样等优点,受到世界各国的高度重视。我国光伏产业在制造水平、产业体系、技术研发等方面具有良好的发展基础,国内外市场前景总体看好。根据能源局印发的《可再生能源发展“十二五”规划》,显示我国对光伏发电今后几年的发展目标做了一个大幅的提升,到2015年中国累计光伏发电的装机容量要达到2100万千瓦,光伏产业的发展也带动配套光伏发电系统专用电缆(以下简称光伏电缆)产品的大量生产。 在光伏发电系统中,逆变器之前的直流侧(DC side)的大量直流电缆需户外敷设,环境条件恶劣,其电缆应根据具体使用场合应具备抗紫外线、臭氧、耐高低温和化学侵蚀等特殊性能。普通材质电缆在这些特殊环境下长期使用,将导致电缆护套脆化易碎,甚至绝缘层分解,而损坏电缆系统,同时增大电缆短路的风险。 因此对于光伏发电电站中户外敷设较多的光伏组件与组件之间的串联电缆、组串之间及组串至直流配电箱(汇流箱)之间的并联电缆和直流配电箱至逆变器之间的电缆,包括部分户外敷设的交流侧(AC side)电缆(逆变器之后的交流电缆),应使用光伏发电系统专用电缆(以下简称光伏电缆),该类电缆一般采用辐照交联聚烯烃绝缘和护套,需通过严苛的耐酸碱、耐湿热、耐气候以及25年热寿命等测试要求。 然而,对于该类新能源产业的光伏电缆,目前国内尚未制定发布相应的产品国家标准、行业标准或技术规范,导致行业内从产品的生产到检测、安装、使用都缺乏统一认可的指导及评定准则,国内生产企业只能参照企业标准或者国外标准来进行生产,光伏电站工程采购方也难以实现对其安全和质量进行技术要求和规范化,缺乏产品选型、设计和检验验收的依据,也一定程度上制约了整个光伏电缆产业的良性快速发展。 因此,从促进光伏电缆行业健康发展出发,为满足行业相关企业单位对光伏电缆的技术参考和考核的需求,本中心联合上海电缆研究所(国家电线电缆质量监督检验中心)、中国三峡新能源有限公司以及国内主要的光伏电缆与电缆料生产企业,在参考国外相关标准(TUV 1169 /1990/1940及UL4703标准)、国内相关标准(GB/T 12706,JB/T 10491等)以及国内企标等技术文件的基础上,起草了本技术规范,并将最终为光伏电缆产品认证提供依据,以便向社会及公众提供更多可信赖的参考依据及质量信息。2.工作过程综述 2.1技术要求制定原则 为使本技术规范能够符合生产、设计和使用单位为保障产品安全运行而对产品提出的技术要求,有助于完善对光伏电缆质量的检测,并满足科学、规范地开展认证工作的需要,在技术要求制定过程中,

UL电线电缆标准介绍

UL電線電纜標準介紹 目錄 一、UL電線電纜標準概況 二、電線電纜的基本測詴方法 (1)基本結構(2)燃燒測詴 (3)耐電壓測詴(4)火花測詴 (5)絕緣電阻測詴(6)老化前和老化後拉伸測詴 (7)其他詴驗簡介 三、常見UL758電線電纜及說明 UL Style Pages簡介 UL即將推出的UL758標準的情況介紹 四、常見UL444通訊電纜及說明 五、UL電線電纜製造廠商應注意的事項 UL FUS Procedure(檢驗細則)的構成 製造商的基本責任 六、UL電線電纜產品及包裝印字要求 一、UL電線電纜標準概況: 二、電線電纜的基本測詴方法 基本結構 (一)導線 1、導體電阻:除TPT、TS和TST等錫芯電線外,UL不要求測量電線電纜產品的導體電阻。 2、線徑:通常電線電纜的線徑都是偶數AWG,如18AWG、16AWG等,奇數AWG 電線屬於特殊例外。 3、決定導體截面積的方法有二種: A、測量每一根絞合芯線截面積之和,測量時至少要取7根苡線直徑的帄均值作為帄均芯線直徑。D 以Mils計算:導體截面積CMA=nd2(CMA:Circular Mil Area) 以毫米計算:導體=0.7854*nd2 其中n為導體結構中芯線的根數。芯線直徑的測量:根據UL1581第200節,每根芯線直徑頇使用精度達到0.01mm(0.001英寸),兩個端面都是帄面的千分尺進行測量。 B、稱重法,見UL1581第210節。 測量過程中發現測量值小於要求值(UL1581,Table20.1),可用兩種方法中的另一種加以證實。(注:DC電阻測量法不能用來作為測量CMA的最終判斷標準)。 導體絕緣厚度

光伏系统电缆设计选型与施工

光伏系统电缆设计选型与施工 在光伏电站建设过程中除主要设备,如光伏组件、逆变器、升压变压器以外,配套连接的光伏电缆材料对光伏电站的整体盈利的能力、运行的安全性、是否高效,同样起着至关重要的作用,下面就对光伏电站中常见的电缆及材料的用途和使用环境做详细的介绍。 电缆按照光伏电站的系统可分为直流电缆及交流电缆,根据用途及使用环境的不同分类如下: 一、直流电缆 (1)组件与组件之间的串联电缆。 (2)组串之间及其组串至直流配电箱(汇流箱)之间的并联电缆。 (3)直流配电箱至逆变器之间电缆。 以上电缆均为直流电缆,户外敷设较多,需防潮、防暴晒、耐寒、耐热、抗紫外线,某些特殊的环境下还需防酸碱等化学物质。 二、交流电缆 (1)逆变器至升压变压器的连接电缆。 (2)升压变压器至配电装置的连接电缆。 (3)配电装置至电网或用户的连接电缆。 此部分电缆为交流负荷电缆,户内环境敷设较多,可按照一般电力电缆选型要求选择。 三、光伏专用电缆 光伏电站中大量的直流电缆需户外敷设,环境条件恶劣,其电缆材料应根据抗紫外线、臭氧、剧烈温度变化和化学侵蚀情况而定。普通材质电缆在该种环境下长期使用,将导致电缆护套易碎,甚至会分解电缆绝缘层。这些情况会直接损坏电缆系统,同时也会增大电缆短路的风险,从中长期看,发生火灾或人员伤害的可能性也更高,大大影响系统的使用寿命。因此,在光伏电站中使用光伏专用电缆和部件是非常有必要的。光伏专用电缆和部件不仅具有最佳的耐风雨性、耐紫外线和臭氧侵蚀性,而且能承受更大范围的温度变化。 四、电缆设计选型的原则: (1)电缆的耐压值要大于系统的最高电压。如380V输出的交流电缆,要选举450/750V 的电缆 (2)光伏方阵内部和方阵之间的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.56倍。 (3)交流负载的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.25倍。 (4)逆变器的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.25倍。 (5)考虑温度对电缆的性能的影响。温度越高,电缆的载流量就越少,电缆要尽量安装在通风散热的地方。 (6)考虑电压降不要超过2%。 直流回路在运行中常常受到多种不利因素的影响而造成接地,使得系统不能正常运行。如挤压、电缆制造不良、绝缘材料不合格、绝缘性能低、直流系统绝缘老化、或存在某些损伤缺陷均可引起接地或成为一种接地隐患。另外户外环境小动物侵入或撕咬也会造成直流接地故障。因此在这种情况下一般使用铠装、带防鼠剂功能护套的电缆。 分布式光伏常用逆变器电缆选择:

常用电缆种类及选型计算方法

电缆种类及选型计算 电缆种类及选型计算 一、电缆的定义及分类 广义的电线电缆亦简称为电缆。狭义的电缆是指绝缘电缆。它可定义为:由下列部分组成的集合体,一根或多根绝缘线芯,以及它们各自可能具有的包覆层,总保护层及外护层。电缆亦可有附加的没有绝缘的导体。 我国的电线电缆产品按其用途分成下列五大类: 1.裸电线 2.绕组线 3.电力电缆 4.通信电缆和通信光缆 5.电气装备用电线电缆 电线电缆的基本结构: 1.导体传导电流的物体,电线电缆的规格都以导体的截面表示 2.绝缘外层绝缘材料按其耐受电压程度 二、工作电流及计算 电(线)缆工作电流计算公式: 单相 I=P÷(U×cosΦ)

P-功率(W);U-电压(220V);cosΦ-功率因素(0.8);I-相线电流(A) 三相 I=P÷(U×1.732×cosΦ) P-功率(W);U-电压(380V);cosΦ-功率因素(0.8);I-相线电流(A) 一般铜导线的安全截流量为5-8A/平方毫米,铝导线的安全截流量为3-5A/平方毫米。 在单相220V线路中,每1KW功率的电流在4-5A左右,在三相负载平衡的三相电路中,每1KW 功率的电流在2A左右。 也就是说在单相电路中,每1平方毫米的铜导线可以承受1KW功率荷载;三相平衡电路可以承受2-2.5KW的功率。 但是电缆的工作电流越大,每平方毫米能承受的安全电流就越小。 电缆允许的安全工作电流口诀: 十下五(十以下乘以五) 百上二(百以上乘以二) 二五三五四三界(二五乘以四,三五乘以三) 七零九五两倍半(七零和九五线都乘以二点五) 穿管温度八九折(随着温度的变化而变化,在算好的安全电流数上乘以零点八或零点九) 铜线升级算(在同截面铝芯线的基础上升一级,如二点五铜芯线就是在二点五铝芯线上升一级,

电力电缆截面选择

电力电缆截面的选择 电力电缆截面 1 电力电缆缆芯截面选择的基本要求。 1.1 最大工作电流作用下的缆芯温度,不得超过按电缆使用寿命确定的允许值。持续工作回路的缆芯工作温度,应符合附录A的规定。 1.2 最大短路电流作用时间产生的热效应,应满足热稳定条件。对非熔断器保护的回路,满足热稳定条件可按短路电流作用下缆芯温度不超过附录A所列允许值。 1.3 连接回路在最大工作电流作用下的电压降,不得超过该回路允许值。 1.4 较长距离的大电流回路或35kV以上高压电缆,当符合上述条款时,宜选择经济截面,可按“年费用支出最小”原则。 1.5 铝芯电缆截面,不宜小于4。 1.6 水下电缆敷设当需缆芯承受拉力且较合理时,可按抗拉要求选用截面。 2 对10kV及以下常用电缆按持续工作电流确定允许最小缆芯截面时,宜满足附录B电缆允许持续载流量(建议性基础值)、以及由附录C按下列使用条件差异影响计入校正系数所确定的允许载流量。 (1)环境温度差异。 (2)直埋敷设时土壤热阻系数差异。 (3)电缆多根并列的影响。 (4)户外架空敷设无遮阳时的日照影响。

3 不属于本规范第2条规定的其他情况下,电缆按持续工作电流确定允许最小缆芯截面时,应经计算或测试验证,且计算内容或参数选择应符合下列规定: (1)中频供电回路使用非同轴电缆,应计入非工频情况下集肤效应和邻近效应增大损耗发热的影响。 (2)单芯高压电缆以交叉互联接地当单元系统中三个区段不等长时,应计入金属护层的附加损耗发热影响。 (3)敷设于塑料保护管中的电缆,应计入热阻影响;排管中不同孔位的电缆还应分别计入互热因素的影响。 (4)敷设于封闭、半封闭或透气式耐火槽盒中的电缆,应计入包含该型材质及其盒体厚度、尺寸等因素对热阻增大的影响。 (5)施加在电缆上的防火涂料、包带等覆盖层厚度大于1.50mm时,应计入其热阻影响。 (6)沟内电缆埋砂且无经常性水份补充时,应按砂质情况选取大于2.0℃·m/W 的热阻系数计入对电缆热阻增大的影响。 4 缆芯工作温度大于70℃的电缆,计算持续允许载流量时,尚应符合下列规定: (1)数量较多的该类电缆敷设于未装机械通风的隧道、竖井时,应计入对环境温升的影响。 (2)电缆直埋敷设在干燥或潮湿土壤中,除实施换土处理等能避免水份迁移的情况外,土壤热阻系数宜选取不小于2.0℃·m/W。 5 确定电缆持续允许载流量的环境温度,应按使用地区的气象温度多年平均值,并计入实际环境的温升影响。宜符合表5的规定: 电缆持续允许载流量的环境温度确定(℃)表5

太阳能光伏电缆标准

太阳能光伏电缆标准 Document number:NOCG-YUNOO-BUYTT-UU986-1986UT

一、应用范围 特性:低烟无卤、优良的耐寒、耐紫外线、耐臭氧和耐气候性。阻燃、耐切痕、耐穿透。线缆保护级别Ⅱ级。 环境温度:-40℃~+90℃;导体最高温度:120℃(允许5s内短路温度200℃); 额定电压:1kV 设计寿命:25年 二、结构 导体:IEC60228 5类绞合镀锡铜线PV1-F 、4、6、10mm2 绝缘:交联低烟无卤阻燃聚烯烃双层绝缘厚度﹥,并符合客户给定的限值。 护套:交联低烟无卤阻燃聚烯烃厚度﹥ 采用150℃无卤阻燃光伏电缆辐照绝缘料(因为最高温度为120℃,必须高于它),是以无卤无毒改性聚烯烃树脂为主要原料,加入无卤无毒阻燃剂、热稳定剂、消烟剂、防霉剂等助剂,不含卤素(欧洲特别强调)、重金属、磷元素。且符合ROHS,浸水后绝缘电阻变化小。 PV1-F太阳能光伏发电设备用电缆,是根据光伏发电设备所处的特殊环 境条件设计的,主要适用于直流电压端,发电设备的引出链接和组件

间汇流连接,最高电压的光伏发电设备系统。PHOTOVOLTAIC EQUIPMENT HALOGEN-FREE PV1-F CABLE应用标准:2 Pfg 1169/产品规格:、 mm2、4 mm2、6 mm2、10 mm2 产品用途:用于太阳能光伏系统连接,可适用于昼夜温差大的沙漠和有盐雾潮湿的沿海以及高原辐射强的地区。 产品特性:工作温度–40℃~90℃弯曲半径≤5D短路温度电缆短路时(最长持续的时间不超过5S)导体最高温度不超过250℃耐气候性符合UV(UVISO 4892-2A)耐臭氧符合IEC60811-2-1阻燃特性单根垂直燃烧(符合IEC60332-1)具有优异的耐酸碱性和耐湿热性

电气线路敷设中如何正确选择线缆的种类

电气线路敷设中如何正确选择线缆的种类 线缆的敷设,一般取决线缆的特性,体现线缆特性的是线缆的型号。首先我们介绍下电气线路常用线缆型号的含义; 一、电气线路常用线缆型号 1、普通电线电缆型号 普通电线电缆、不具有阻燃、耐火、无卤及低烟的特性 额定电压 导体规格 无者:非铠表电缆 22:钢带铠表 32:钢丝铠表 无者:为无护套 V:聚氯乙烯护套 Y:聚烯烃护套 导体 无者:铜导体 L:铝导体 绝缘材料 V:聚氯乙烯 YJ:交联聚乙烯 用途: 无:电力电缆 B:布线 K:控制电缆 如:BV——就是聚氯乙烯绝缘的铜芯电线 BW——就是聚氯乙烯护套聚氯乙烯绝缘铜芯电线 YJV——交联聚乙烯绝缘、聚氯乙烯护套无铠装铜芯电力电缆 YJV22——交联聚乙烯绝缘、聚氯乙烯护套钢带铠装铜芯电力电缆 KYJV22——交联聚乙烯绝缘、聚氯乙烯护套钢带铠装铜芯控制电缆

2、阻燃线缆的型号 火灾发生时,阻止或延缓火焰在电缆上蔓延,需用阻燃型线缆。这种线缆通常是在上述普通线缆的绝缘和护套材料中加阻燃剂、或者对材料进行一种处理。一般用“Z”表示,它分有A、B、C、D四个阻燃等级,按照阻燃等级,在普通线缆的型号前加ZA或ZB、ZC、ZD。 对于电缆:特级防火等级的建筑物,应选A级阻燃的电缆 一级防火等级的建筑物,应选B级阻燃的电缆 二、三级防火等级的建筑物,应选C级阻燃的电缆 对于导线:特级防火等级的建筑物,电线截石50 mm2以上选B级阻燃的电线特级防火等级的建筑物,电线截石35 mm2以下选C级阻燃的电线 一级防火等级的建筑物,电线截石50 mm2以上选C级阻燃的电线 一级防火等级的建筑物,电线截石35 mm2以下选D级阻燃的电线 二、三级防火等级的建筑物,均选D级阻燃等级的电线 另外在防火封堵通道中敷设电缆时,还要根据电缆的非金属含量进行电缆阻燃等级的选 择,非金属含量是用升/每米为单位表示的。 非金属含量在7-14 L/m以上,选A级阻燃等级的电缆 非金属含量在3.5-7 L /m以上,选B级阻燃等级的电缆 非金属含量在1.5-3.5 L /m以上,选C级阻燃等级的电缆 还有一种电缆、无卤低烟电缆,这种电缆的外护套是聚烯烃,聚烯烃不含卤,发烟率很低,火中释放的毒性指数仅为聚氯乙烯的5%。也有上述的四个阻燃等级,电缆型号为:WDZ(A、B、C)—YJY。 3、耐火电线电缆型号 火灾发生时,为保证重要设备能正常工作,所以需要用具有耐火特性的线缆,通常这种线缆是在铜导体上缠包云母耐火带,保证线缆持续通电一段时间,它的实验数据是一般供火温放在750oC~800 oC可以维持90分。 耐火线缆可分为:阻燃耐火线缆和非阻燃耐火线缆,这就是看它的非金属材料(绝缘和护套)是不是具有阻燃性能。穿耐火金属管敷设的耐火线缆是不需要有阻燃特性的,而在实际工程中,电线、电缆往往是成束敷设的,考虑到非阻燃

光伏电缆特性介绍

PV-电缆(光伏组件用电 缆) 1、技术规范 PV-电缆(光伏组件用电缆)目前尚无国家或行业标准,本试验技术规范所涉及到的要求来自于德国标准化委员会PV-系统用电线K411.2.3工作组的初稿。 这个初稿将作为德国国家标准报批稿进行发布。 德国莱茵TUV(上海)将用此技术规范对PV-电缆的性能进行检测和评估。 在德国莱茵TUV公司内部此技术规范的文件编号为2PfG 1169/08.2007。 2、使用范围 2PfG 1169/08.2007适用于最高允许1.8kV(线芯对线芯,非接地系统)直流电压、在光伏系统中CD侧使用的单芯软电缆(电线)。 该产品适合于Ⅱ类安全等级下使用。 电缆运行的环境温度最高到90℃。 电缆可以多根并联使用。 3、特殊名词术语 PV 系统(photovoltaic system):光伏系统(太阳能系统)。 DC侧(DC side):光伏装置中从光伏电池到光伏换流器直流端子之间的部分。 标准试验条件下的开路电压(UOC STC):在标准试验条件下,未加载(开路)的光伏组件、光伏电线、光伏列阵、光伏发电机或光伏换流器直流侧的电压。 标准试验条件下的短路电流(ISC TC):在标准试验条件下,光伏组件、光伏电线、光伏列阵或光伏发电机的短路电流。 4、无卤PV-电缆的基本信息 4.1电缆型号 PV1-F 4.2电缆特性 ●额定电压: AC U0/U=0.6/1kV

DC 1.8kV(线芯对线芯,非接地系统,没有负载下的回路) 如果电缆使用在直流系统中,其导体间的额定电压应不大于电缆AC额定值U的1.5倍。在单相接地直流系统中,此数值应乘以0.5的系数。 ●温度范围: 环境温度: -40℃到+90℃ 导体最高工作温度:120℃ 电缆运行的环境温度最高到90℃。依据EN60216-1标准进行考核,其绝缘和护套的温度指数是120℃。 期望使用寿命是25年 5秒钟的短路温度是200℃ 4.3电缆结构 ●导体 导体芯数: 1 导体是EN60228(IEC60228、GB/T3956)中的第5类导体,而且必须是镀锡的。 ●导体的截面 1.5, 2.5,4,6,10,16,25,35mm2。 ●导体隔离层 在导体周围可以使用一层合适的无卤材料作为隔离层。 ●绝缘 绝缘应是挤出型的无卤材料,应是一层或紧密粘附着的几层组成。绝缘应是实心且材质均匀,在剥离绝缘时必须尽可能不要损伤绝缘本身、导体和镀锡层。 绝缘厚度由生产商规定,但最小值必须≥0.5mm。 建议的绝缘厚度 标称截面(mm2) 1.5 2.5 4 6 25 35

电缆选型计算

电缆选择计算(参考土木工程施工手册) 箱式变压器至1号竖井1级配电箱电缆选择计算. 查负荷机具表使用设备容量如下: 空压机二台:P a =180KW 轴流式通风机两台:P b =56KW 抓斗一台:P c =26KW 砼搅拌机400L :P d =5.5KW 砼喷射机: P e =8KW 施工机械风镐: P f =74KW 浆液搅拌设备: P g =30KW 污水泵: P h =33KW 直流电焊机:P i =104KW 交流电焊机:P g =115.8KW 维修设备: P i =30KW 隧道照明: P 4=15KA 根据施工现场用电划分: ??? ? ??+++=∑∑∑∑44332211P K P K P K cos P K 05.1P ? KW P P P P P P P P h g f e d c b a 452P 1=+++++++=∑ KW P P i 8.219P g 2=+=∑ KW 5341508.2196.075.04526.005.1P P K P K P K cos P K 05.1P 44332211=?? ? ??++?+?=???? ??+++=∑∑∑∑?

变电箱体选型为P=800KVA 按照允许电流选择,按公式计算: A 1081732 .175.038.0534 3cos =??= = ? U P I A 1620732 .175.038.0800 3cos =??== ? U P I 总 电缆按有可能出现的最大负荷为4掌子面同期施工,选择电缆。所以必须考虑有一定的余量,根据上述负荷计算电流和施工中期负荷增加的可能。查电缆载流表得知应选择: 现场从变电箱体引出5台1级配电箱将电缆载流均分324A 橡皮绝缘电力电缆选择95 21853?+?:载流370A 电压降计算: 根据公式:s C M S ?=∑ 式中 S-配电线路电压损失的百分数; M-导线长乘有功功率(KW*m ) S-导线截面(mm 2) C-常熟:三相四线时,铜线77 根据实际测量,箱式变压器至各1级配电箱最远电气最远距离50米。 将各字母数值代入公式:% 8.1185 7750534s C M S =??= ?=∑ 根据计算得知:计算结果小于8%(混合电路)符合规范要求。

光伏电缆技术及其标准的发展

光伏电缆技术极其标准的发展 所有的太阳能电池,均产生直流电并需要转换交流电。具有一定容量的光电源,需要许多千个单元模块组成,并将每一个单元模块有规则的连接起来,可想而知PV电缆结构中包括很多的绝缘细线。初期研究光伏电池,主要精力是对元件及其组合方面,目前对于PV电缆的研究也提到了日程。近十年来,全球光能发电市场高速增长,而光伏电缆仍没有国际标准,因此可借鉴的标准和试验,需加以调整,如寿命循环试验等,尤其应当注意的是电缆长期暴露在强烈紫外线下的老化问题。 光伏电池由大到小,一般居民屋顶的小型PV为几千瓦峰值 (kWp-Kilowatt peak),工业用的中型PV为几兆瓦峰值(MWp),大型发电场PV达2千兆瓦峰值(2GWp)。2008年全球新安装系统的PV市场为5.6 GW,大多数人预测每年约8~10GW的能力。PV用电缆通常考虑只在系统的直流部分,不包括栅极接线、系统控制电缆及其他连接电线等。PV电缆与PV安装容量的关系大致如下:1 MW约相当配套40~60km PV cable,这与晶体和薄膜组件的排列和数量直接相关,其连接原理见图1,图中未画出变流器。

图1 细线电缆和模块电缆与模块连接原理 PV电缆长期暴露在阳光下,或者长期浸泡在水中,还有环境温度的急剧变化,因此用户对于电缆的寿命问题即为关注。因为没有国际标准(如IEC标准),制造者也觉得缺乏依据,所以PV电缆在发展过程中,对其质量和寿命问题出现了争论,但大多数专家持赞同意见。 由UL出版和发行的《光电伏打电线的调查大纲》UL-4703(及其相关标准和基准);另外由TüV(德国技术上检验局)印刷的《在光伏系统使用的电缆要求》2Pfg-1169"(及其相关的标准和基准),成为目前主要的参考文件。将来也许会成为公认的标准。 电缆导体由很细的镀锡组成,符合IEC 60228 class,截面大都为4.00 mm2 and 6.00 mm2,分别由56根单线和84根单线组成;绝缘层护套符合TüV和UL要求,热塑或交联惨了均可使用,这些属于常规规定,绝缘厚度曲0.5 mm。

太阳能光伏电缆标准

一、应用范围 特性:低烟无卤、优良的耐寒、耐紫外线、耐臭氧和耐气候性。阻燃、耐切痕、耐穿透。线缆保护级别Ⅱ级。 环境温度:-40℃~+90℃;导体最高温度:120℃(允许5s内短路温度200℃); 额定电压:AC0.6/1kV DC1.8kV 设计寿命:25年 二、结构 导体:IEC60228 5类绞合镀锡铜线PV1-F 2.5、4、6、 10mm2 绝缘:交联低烟无卤阻燃聚烯烃双层绝缘厚度﹥0.5mm,并符合客户给定的限值。护套:交联低烟无卤阻燃聚烯烃厚度﹥0.5mm 采用150℃无卤阻燃光伏电缆辐照绝缘料(因为最高温度为120℃,必须高于它),是以无卤无毒改性聚烯烃树脂为主要原料,加入无卤无毒阻燃剂、热稳定剂、消烟剂、防霉剂等助剂,不含卤素(欧洲特别强调)、重金属、磷元素。且符合ROHS,浸水后绝缘电阻变化小。 下表为典型结构: PV1-F太阳能光伏发电设备用电缆,是根据光伏发电设备所处的特殊环境条件设计的,主要适用于直流电压端,发电设备的引出链接和组件间汇流连接,最高电压DC1.8kV的光伏发电设备系统。PHOTOVOLTAIC

EQUIPMENT HALOGEN-FREE PV1-F CABLE应用标准:2 Pfg 1169/08.2007产品规格:1.5mm2、2.5 mm2、4 mm2、6 mm2、10 mm2

产品用途:用于太阳能光伏系统连接,可适用于昼夜温差大的沙漠和有盐雾潮湿的沿海以及高原辐射强的地区。 产品特性:工作温度–40℃~90℃弯曲半径≤5D短路温度电缆短路时(最长持续的时间不超过5S)导体最高温度不超过250℃耐气候性符合UV(UVISO 4892-2A)耐臭氧符合IEC60811-2-1阻燃特性单根垂直燃烧(符合IEC60332-1)具有优异的耐酸碱性和耐湿热性 (资料素材和资料部分来自网络,供参考。可复制、编制,期待你的好评与关注)

光伏系统中电缆的选取设计方案方法

光伏系统中电缆的选取设计方法 一、光伏系统中电缆的选择主要考虑如下因素: 1、电缆的绝缘性能。 2、电缆的耐热阻燃性能。 3、电缆的防潮,防光。 4、电缆的敷设方式。 5、电缆芯的类型(铜芯,铝芯>。 6、电缆的大小规格。 二、光伏系统中不同的部件之间的连接,因为环境和要求的不同,选择的电缆也不相同。以下分别列出不同连接部分的技术要求: 1>元件与元件之间的连接 必须进行UL测试,耐热90℃,防酸,防化学物质,防潮,防曝晒。 2>方阵内部和方阵之间的连接 可以露天或者埋在地下,要求防潮、防曝晒。建议穿管安装,导管必须耐热90℃。 3>蓄电池和逆变器之间的接线 可以使用通过UL测试的多股软线,或者使用通过UL测试的电焊机电缆。 4>室内接线(环境干燥> 可以使用较短的直流连线。 三、电缆大小规格设计,必须遵循以下原则: 1>蓄电池到室内设备的短距离直流连接,选取电缆的额定电流为计算电缆连续电流的1.25倍。 2>交流负载的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.25倍。 3>逆变器的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.25倍。 4>方阵内部和方阵之间的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.56倍。 5>考虑温度对电缆的性能的影响。 6>考虑电压降不要超过2%。

7>适当的电缆尺径选取基于两个因素,电流强度与电路电压损失。完整的计算公式为:线损 = 电流×电路总线长×线缆电压因子式中线缆电压因子可由电缆制造商处获得。 太阳能跟踪器 太阳能跟踪器是保持太阳能电池板随时正对太阳,让太阳光的光线随时垂直照射太阳能电池板的动力装置,采用太阳能跟踪器能显著提高太阳能光伏组件的发电效率。 目前世界上通用的太阳能跟踪器都需要根据安放点的经纬度等资讯计算一年中的每天不同时刻太阳所在的角度,将一年中每个时刻的太阳位置存储到PLC、单片机或电脑软件中,都要靠计算该固定地点每一时刻的太阳位置以实现跟踪。 采用的是电脑资料理论,需要地球经纬度地区的的资料和设定,一旦安装,就不便移动或装拆,每次移动完就必须重新计算参数、设定资料和调整各个参数。原理、电路、技术、设备都很复杂,非专业人士不能够随便操作。 太阳能背板 太阳能背板位于太阳能电池板的背面,对电池片起保护和支撑作用,具有可靠的绝缘性、阻水性、耐老化性。 一般具有三层结构( PVDF/PET/PVDF >,外层保护层 PVDF 具有良好的抗环境侵蚀能力,中间层为 PET 聚脂薄膜具有良好的绝缘性能,内层 PVDF 和 EVA 具有良好的粘接性能。太阳能电池板截面有五层:光伏玻璃、EVA、太阳能电池片、EVA和背板。 太阳能背板材料

电缆选择计算

UPS电缆配置指导书 已知负载功率100 kva 电缆往返长度200 M 电缆电阻率欧姆mm2/m 电缆压降5% 设备项电流=设备负载/项数/项电压 =100kva/3/220= 电缆最大压降= 电缆压降*电缆项电压 = 220v*5% =11V 压降电阻=最大压降/每项电流 = 11V/151A=欧姆 横截面积=电缆长度/压降电阻*电缆电阻

=100m/*=

线缆压降计算 设:线缆电缆:3x25+1x16 设备总功率=45KW 电流I=P/(U*1~3)*功率因数=70A 电缆横截面积=25mm2 电缆长度=1400m 铜缆电阻=欧姆 电缆电阻R=*L/S(电缆电阻*长度/横截面积) 由此得知线缆总电阻为欧姆 压降公式=U=IR/2= 线缆电流*线缆总电阻/2=70*2= 线电压220V 经过1400米出传输线压降为= 根号3= 故线间电压约为323V

线路压降与线径的平方成反比。线径增加一倍,压降变为原来的四分之一 铜芯电线按每平方载流4~6A(长线取小值)选取

线缆种类: 1 4 6 10 16 25 35 50 7O 95 l20 150 185...... 一、电流计算: 口诀:电力加倍,电热加半。 单相千瓦,四五安。 单相三八, 两安半。 说明:口诀是以380/220V 三相四线系统中的三相设备为准,计算每千瓦的安数。对于某些单相或电压不同的单相设备,其每千瓦的安数.口诀中另外作了说明 1、电力加倍: 电力专指电动机在380V三相时力率电 动机每KW电流按照2倍计算。即千瓦数加一倍。 例:电动机按照“电力加倍”计算电流11A 40KW水泵新风按照“电力加倍”计算电流80A

1169∕08—2007 光伏电缆标准

2 Pfg 1169/08.2007 Requirements for cables for use in photovoltaic-systems

Contents Seite Foreword (3) 1Scope (3) 2Normative references (3) 3Terms and definitions (5) 4Halogen-free PV-cable (6) 4.1Code designation (6) 4.2Characteristics (6) 4.3Construction (6) 4.4Test (8) 4.5Guideline for use (informative) (8) 4.6Current carrying capacity (8) Annex A (normative) Test of mutual influence (15) Annex B (normative) Test of absence of halogen (16) Annex C (normative) Determination of halogens – Elemental test (17) Annex D (normative) Test of long term resistance of insulation to D.C (19) Annex E (normative) Cold impact test (20) Annex F (normative) Dynamic penetration test (21) Annex G (normative) Notch propagation (23) Figure 1 – Arrangement of marking (8) Figure F.1 – Arrangement for penetration test (22) Table 1 – Current carrying capacity of PV-cables (9) Table 2 – Conversion factor for deviating temperatures (9) Table 3 – Tests for halogen free PV-cable (10) Table 4 – Requirements for halogen free insulation and sheath compounds (13) Table A.1 – Requirements (15) Table B.1 – Test method, measurement, requirements (16) Table B.2 – Test sequence (16) Table E.1 – Parameter for cold impact test (20)

电缆选型计算

电缆选型计算.电力工程电缆设计 电缆导体材质1.

7.8.6 ,DL/T5222,7.8.5控制电缆应采用铜导体。,3.1.1 GB50217 电力电缆芯数2. 注意电压范围,3.2.4GB50217 3.2.3 电缆绝缘水平3.

主回路电缆绝缘电压选择3.3.2条Z,1 GB50217不应低于控制电缆额定电压的选择,3.3.5 该回路工作电压,应2 220kV 及以上高压配电装置敷设的控制电缆,选用450/750V。;外除上述情况外,控制电缆宜选用 450/750V3 部电气干扰影响很小时,可选用较低的额 定电压。 DL5136中电力电缆导体截面选择4. 4.1电缆敷设方式 )、(土壤中:壕沟直埋 空气中:、电缆构筑物:常用电缆构筑物有 电缆隧道、电缆1沟、排管、吊架及桥架等,此外还有主控、集控室下面电缆夹层及垂 直敷设电缆的竖井等。、电缆桥架2 梯架、大电缆托盘、小动力 槽式、控制,通讯电缆电力电缆截面选择4.2 硬导体软导体电缆 1按回路持续1按回路持续1按回路持续工 导体工作电流选择作电流选择工作电流

选择 22按经济电流2按经济电流密按经济电流截面 密度选密度选度选按短路热的定选 按电晕电压按电压损按电晕条导校校按短路热按电晕对无截电干扰校定校按短路动的定校按机械共条件校电缆截面应满足持续允许电流、短路热稳定、允许电压降等要求,当最大负荷利用小时T>5000h 且长度超过20m时,还应按经济电流密度选取。动力回路铝芯电2缆截面不宜小于6mm 。(一)

按持续允许电流选择(二)按短路热稳定选择(三)按电压损失校验以下分别描述(一)按持续允许电流选择 1.敷设在空气中和土壤中的电缆允许载流量按下式计算:Klru≥I (K为综合校正系数,见下表) I-计算工作电流( A ) Iru-电缆在标准敷设条件下的额定载流量(A) , 2.电缆载流量的修正: GB5222 持%100及以下常用电缆按10kV 3.7.2 中GB50217. 续工作电流确定电缆导体允许最小截面,宜符合本规范的规定,其载流量按照下列使用条件差C和附录D附录异影响计入校正系数后的实际允许值应大于回路的工作电流。 1、环境温度差异。 2、直埋敷设时土壤热阻系数差异。

电缆选择计算

UPS电缆配置指导书 已知负载功率 100 kva 电缆往返长度 200 M 电缆电阻率欧姆mm2/m 电缆压降 5% 设备项电流=设备负载/项数/项电压 =100kva/3/220= 电缆最大压降= 电缆压降*电缆项电压 = 220v*5% =11V 压降电阻=最大压降/每项电流 = 11V/151A=欧姆 横截面积=电缆长度/压降电阻*电缆电阻 =100m/*=

线缆压降计算 设:线缆电缆: 3x25+1x16 设备总功率=45KW 电流I=P/(U*1~3)*功率因数=70A 电缆横截面积=25mm2 电缆长度=1400m 铜缆电阻=欧姆 电缆电阻R=*L/S(电缆电阻*长度/横截面积) 由此得知线缆总电阻为欧姆 压降公式=U=IR/2= 线缆电流*线缆总电阻/2=70*2= 线电压220V 经过1400米出传输线压降为= 根号3= 故线间电压约为323V 线路压降与线径的平方成反比。线径增加一倍,压降变为原来的四分之一 铜芯电线按每平方载流4~6A(长线取小值)选取

线缆种类: 1 4 6 10 16 25 35 50 7O 95 l20 150 185...... 一、电流计算: 口诀:电力加倍,电热加半。 单相千瓦,四五安。 单相三八, 两安半。 说明:口诀是以380/220V 三相四线系统中的三相设备为准,计算每千瓦的安数。对于某些单相或电压不同的单相设备,其每千瓦的安数.口诀中另外作了说明 1、电力加倍: 电力专指电动机在380V三相时力率电 动机每KW电流按照2倍计算。即千瓦数加一倍。 例:电动机按照“电力加倍”计算电流11A 40KW水泵新风按照“电力加倍”计算电流80A 2、电热加半:电热专指电阻加热的电阻炉。三相380V 电热设备每KW电流按照倍计算。即千瓦数的一倍半。(包含整流器、变压器、照明等) 例:3KW电加热器按照“电热加半”计算电流 15KW电阻炉按照“电热加半”计算电流为23A

光伏电站中常见电缆及材料介绍

近年来,太阳能(PV)发电的应用日趋广泛,发展迅速,在光伏电站建设过程中除主要设备,如光伏组件、逆变器、升压变压器以外配套连接的光伏电缆材料对光伏电站的整体盈利的能力、运行的安全性、是否高效,同样起着至关重要的作用,下面就对光伏电站中常见的电缆及材料的用途和使用环境做详细的介绍。 电缆按照光伏电站的系统可分为直流电缆及交流电缆,根据用途及使用环境的不同分类如下: 1.直流电缆 (1)组件与组件之间的串联电缆。 (2)组串之间及其组串至直流配电箱(汇流箱)之间的并联电缆。 (3)直流配电箱至逆变器之间电缆。 以上电缆均为直流电缆,户外敷设较多,需防潮、防暴晒、耐寒、耐热、抗紫外线,某些特殊的环境下还需防酸碱等化学物质。 2.交流电缆 (1)逆变器至升压变压器的连接电缆。 (2)升压变压器至配电装置的连接电缆。 (3)配电装置至电网或用户的连接电缆。 此部分电缆为交流负荷电缆,户内环境敷设较多,可按照一般电力电缆选型要求选择。 3.光伏专用电缆 光伏电站中大量的直流电缆需户外敷设,环境条件恶劣,其电缆材料应根据抗紫外线、臭氧、剧烈温度变化和化学侵蚀情况而定。普通材质电缆在该种环境下长期使用,将导致电缆护套易碎,甚至会分解电缆绝缘层。这些情况会直接损坏电缆系统,同时也会增大电缆短路的风险,从中长期看,发生火灾或人员伤害的可能性也更高,大大影响系统的使用寿命。 因此,在光伏电站中使用光伏专用电缆和部件是非常有必要的。随着光伏产业的不断发展,光伏配套部件市场逐步形成,就电缆而言,已开发出了多种规格的光伏专业电缆产品。近期研制开发的电子束交叉链接电缆,额定温度为120℃,可抵御恶劣气候环境和经受机械冲击。又如RADOX电缆是根据国际标准IEC216研制的一种太阳能专用电缆,在户外环境下,使用寿命是橡胶电缆的8倍,是PVC电缆的32倍。光伏专用电缆和部件不仅具有最佳的耐风雨

电缆选择计算书

技术资料 电缆截面选择计算书 计算:黄永青 2005年7月28日

1.计算条件 A.环境温度:40℃。 B.敷设方式: - 穿金属管敷设; - 金属桥架敷设; - 地沟敷设; - 穿塑料管敷设。 C.使用导线:铜导体电力电缆 - 6~10kV高压:XLPE(交联聚乙烯绝缘)电力电缆。 - 380V低压:PVC(聚氯乙烯绝缘)或XLPE电力电缆。 2.导线截面选择原则 2.1 导线的载流量 1)载流量的校正 A.温度校正 K1=√(θn-θa)/(θn-θc) 式中:θn:导线线芯允许最高工作温度,℃; XLPE绝缘电缆为90℃,PVC绝缘电缆为70℃。 θa:敷设处的环境温度,℃; θc:已知载流量数据的对应温度,℃。 2)敷设方式的校正 国标《电力工程电缆设计规范》GB50217-94中给出了不同敷设方式的校正系数。综合常用的几种敷设方式的校正系数,并考虑到以往

工程的经验及经济性,取敷设方式校正系数K2=0.7 3)载流量的校正系数 K=K1×K2 2.2电力电缆载流量表 表1 6~10kV XLPE绝缘铜芯电力电缆载流量表 表2 0.6/1kV PVC绝缘电力电缆载流量表 表3 0.6/1kV XLPE绝缘电力电缆载流量表

2.3 短路保护协调 1)6~10kV回路电力电缆短路保护协调 S≥I×√t×102/C 式中:S:电缆截面,mm2; I:短路电流周期分量有效值,A; t:短路切除时间,秒。 C:电动机馈线C=15320;其他馈线C=13666 2)380V低压回路电力电缆短路保护协调 - 配电线路的短路保护协调 S≥I×√t/K 式中:S:电缆截面,mm2; I:短路电流有效值(均方根值),A; t:短路电流持续作用时间,秒。 K:PVC绝缘电缆K=115;XLPE绝缘电缆K=143 - 380V电动机回路短路保护协调 电缆的允许电流大于线路短路保护熔断器熔体额定电流的40%。 2.4 电缆的最小截面 A.6~10kV电力电缆:根据铜冶炼厂实际使用经验,采用断路器时, 最小截面70~95 mm2。(在新设计的工程中应根据短路电流数据进行计算) B.低压电力电缆:最小截面:4 mm2。

太阳能光伏电缆标准

PV1-F太阳能光伏电缆技术指标 一、应用范围 特性:低烟无卤、优良的耐寒、耐紫外线、耐臭氧和耐气候性。阻燃、耐切痕、耐穿透。线缆保护级别Ⅱ级。 环境温度:-40℃~+90℃;导体最高温度:120℃(允许5s内短路温度200℃); 额定电压:AC0.6/1kV DC1.8kV 设计寿命:25年 二、结构 导体:IEC60228 5类绞合镀锡铜线PV1-F2.5、4、6、10mm2 绝缘:交联低烟无卤阻燃聚烯烃双层绝缘厚度﹥0.5mm,并符合客户给定的限值。护套:交联低烟无卤阻燃聚烯烃厚度﹥0.5mm 采用150℃无卤阻燃光伏电缆辐照绝缘料(因为最高温度为120℃,必须高于它),是以无卤无毒改性聚烯烃树脂为主要原料,加入无卤无毒阻燃剂、热稳定剂、消烟剂、防霉剂等助剂,不含卤素(欧洲特别强调)、重金属、磷元素。且符合ROHS,浸水后绝缘电阻变化小。 下表为典型结构: 型号规格mm2导体根数导体直径成品外径mm PV1-F 1.5300.255~ 5.5 PV1-F 2.5510.25 5.5~6 PV1-F4560.36~ 6.5 PV1-F6840.3 6.8~7.3 PV1-F10800.48.5~9.2 PV1-F太阳能光伏发电设备用电缆,是根据光伏发电设备所处的特殊环境条件设计的,主要适用于直流电压端,发电设备的引出链接和组件间汇流连接,最高电压DC1.8kV的光伏发电设备系统。PHOTOVOLTAIC EQUIPMENT HALOGEN-FREE PV1-F CABLE应用标准:2 Pfg 1169/08.2007产品规格:1.5mm2、2.5 mm2、4 mm2、6 mm2、10 mm2

光伏系统中电缆的选取设计方法

光伏系统中电缆的选取设计方法 光伏电缆的特性是由其电缆专用绝缘料和护套料决定的,我们称之为交联PE,经过辐照加速器辐照以后,电缆料的分子结构会发生改变,从而提供其个方面的性能。 在安装和维护期间,电缆可在屋顶结构的锐边上布线,同时电缆须承受压力、弯折、张力、交叉拉伸载荷及强力冲击.如果电缆护套强度不够,则电缆绝缘层将会受到严重损坏,从而影响整个电缆的使用寿命,或者导致短路、火灾和人员伤害危险等问题的出现。 一、光伏系统中电缆的选择主要考虑如下因素: 1、电缆的绝缘性能; 2、电缆的耐热阻燃性能; 3、电缆的防潮,防光; 4、电缆的敷设方式; 5、电缆芯的类型(铜芯,铝芯); 6、电缆的大小规格。 二、光伏系统中不同的部件之间的连接,因为环境和要求的不同,选择的电缆也不相同。以下分别列出不同连接部分的技术要求: 1)元件与元件之间的连接 必须进行UL测试,耐热90℃,防酸,防化学物质,防潮,防曝晒。 2)方阵内部和方阵之间的连接 可以露天或者埋在地下,要求防潮、防曝晒。建议穿管安装,导管必须耐热90℃。 3)蓄电池和逆变器之间的接线 可以使用通过UL测试的多股软线,或者使用通过UL测试的电焊机电缆。 4)室内接线(环境干燥) 可以使用较短的直流连线。 三、电缆大小规格设计,必须遵循以下原则:

1)蓄电池到室内设备的短距离直流连接,选取电缆的额定电流为计算电缆连续电流的1.25倍。 2)交流负载的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.25倍。 3)逆变器的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.25倍。 4)方阵内部和方阵之间的连接,选取的电缆额定电流为计算所得电缆中最大连续电流的1.56倍。 5)考虑温度对电缆的性能的影响。 6)考虑电压降不要超过2%。 7)适当的电缆尺径选取基于两个因素,电流强度与电路电压损失。完整的计算公式为: 线损= 电流×电路总线长×线缆电压因子 式中线缆电压因子可由电缆制造商处获得。